25 KVA Single Phase Pole Transformer-25/0.347 KV|Canada 2024

25 KVA Single Phase Pole Transformer-25/0.347 KV|Canada 2024

Naha ea thomello: Canada 2024
Matla: 25 kVA
Matla: 25/0.347kV
Tšobotsi:{0}voltage double bushings e phahameng
Romela Inquiry

 

25 kVA single phase pole transformer

25 kVA single phase pole transformer – e tshepehang, e sebetsa hantle, le lehadima{1}}e sireleditsweng ka ntle

 

 

01 Kakaretso

1.1 Tlhaloso ea Morero

Li-transformer tse tharo tsa 25 kVA single-phase pole{2}}li fane ka moreki oa Canada ke Scotech ka 2024 e le karolo ea odara{4}e robong. E lumellana ka botlalo le litekanyetso tsa CSA C2.2-06. E lekantsoe bakeng sa motlakase oa mantlha oa 25 kV le motlakase oa bobeli oa 0.347 kV, o fanang ka kakaretso ea matla a 25 kVA tlas'a mojaro o sa khaotseng. E sebelisa pholiso ea oli ea tlhaho ea ONAN, oli ea diminerale e le setsi sa insulating, polarity e eketsang, le sehlopha sa vector Ii6.

Transformer ena e na le mapheo a aluminium, e fokotsa boima le litšenyehelo, e etsa hore ho be bonolo ho kenya le ho tsamaisa. Ho se sebetse ha eona ka 2.8%. E na le NLTC (No{4}}Load Tap Changer) e nang le mohato oa 2.5%, e lumellang ho lokisoa ha motlakase nakong ea ts'ebetso ho boloka motlakase o tsitsitse. E boetse e na le lintho tse thibelang lehalima tsa 33 kV polymer le lihlahla tse peli tse phahameng{8}} tsa motlakase bakeng sa ho sireletsa lehalima le ho feta.

Phetoho ena ea motlakase e tloaelehile Amerika Leboea le litsamaiso tsa kabo ea Canada. Moetso ona o thusa baahi ba mahaeng, libaka tsa bolulo, le likhoebo tse nyane moo ho nang le matla a lekaneng a -mokhahlelo a hlokahalang. Khokahano ea mantlha ea 25 kV e e etsa khetho e matla bakeng sa lisebelisoa tsa ho fepa kapa tsa loop libakeng tse kantle tse nang le lehalima le phahameng. Ho sa tsotellehe hore na e sebelisoa meleng e meholo ea mahaeng kapa qetellong ea marang-rang a lesale, transformer ena e fana ka ts'ebetso e tsitsitseng le e ka tšeptjoang.

 

1.2 Tlhaloso ea Setsebi

Tlhaloso ea 25 kVA ea karolo e le 'ngoe ea pole transformer le leqephe la data

E fetisetsoa ho
Canada
Selemo
2024
Mofuta
Pole Mounted Transformer
Standard
CSA C2.2-06
Rated Power
25kVA
Khafetsa
60HZ
Polarity
Kekeletso
Mokhahlelo
1
Mofuta oa ho Pholisa
ONA
Mokelikeli o thibelang metsi
Oli ea Liminerale
Voltage ea mantlha
25 kV
Motlakase oa bobeli
0.347 kV
Sehlopha sa Vector
Ii6
Lintho Tse Hlahang
Aluminium
Tšitiso
2.8%
Katleho
98.63%
Tlanya Changer
NLTC
Tlanya Range
±2*2.5%
Ha ho Tahlehelo ea Mojaro
83 kV
Ho Lahleheloa ke Moroalo
404 kV
Lisebelisoa
Motshwari

 

1.3 Litšoantšo

25 kVA setaele se le seng sa karolo e le 'ngoe ea li-transformer le nameplate

25 kVA single phase pole transformer drawing 25 kVA single phase pole transformer nameplate

 

 

02 Tlhahiso

2.1 Ntlha ea bohlokoa

The transformer core ke karolo ea bohlokoa e etsang potoloho ea makenete le ho nolofalletsa phetisetso ea matla lipakeng tsa mapheo a mantlha le a bobeli. E sebelisa{{1}mabele a boleng bo holimo- a silicon a tšelelitsoeng ka stakaneng le a sirelelitsoeng ho fokotsa tahlehelo ea hona joale ea eddy. Koko e na le moetso oa mantlha-o nang le litšiea tse khutlonnetsepa, tse ntlafalitsoeng hore li khone ho phalla hantle le ho sebetsa hantle haholo tšebetsong e tsoelang pele ea indasteri.

 

2.2 Ho tsubella

Maqhubu a aluminium a hlahisoa tlas'a taolo e thata ea tataiso, polarity le tsitsipano. Khoele ea LV e etsoa maqeba pele, e lateloe ke khoele ea HV, e kentsoeng ka har'a mohatla o kopaneng 'me ha e sosobane. Ho nepahala ha phetoho ho ka hare ho ± 0.3%. Li-ducts tsa oli ea radial E kholo ho feta kapa e lekana le 3 mm le compression e tiileng e boloka ho pholile ka katleho le matla a mochine, ho thibela ho senyeha ha mosebetsi nakong ea ts'ebetso.

25 kVA single phase pole transformer winding

 

2.3 Tanka

25 kVA single phase pole transformer oil tank

Tanka ea oli e hahiloe ho fihlela litekanyetso tse thata tsa ho kenya seboholi. E na le li-flange tse matla le litšehetso, e khona ho jara boima le ho thothomela, 'me e na le masoba a sireletsehileng a ho kenya. Lisebelisoa tsa tanka li mamella mocheso o phahameng le khatello. Li-gaskets li netefatsa hore ha ho na ho lutla ha oli. Bokaholimo bo tšoaroa khahlano le kutu. Bokaholimo bo fana ka sebaka se lekaneng bakeng sa ho tlosoa habonolo le ho nkela ba ts'oarang sebaka ntle le ho sekisetsa ho tiisa.

 

2.4 Kopano ea ho Qetela

Kopano ea Core le Maqhubu
Kenya li-winding tse phahameng{{0}le tse tlase{1}} tsa maqhubu a motlakase holim'a mantlha, 'me u netefatse hore li-insulation le concentricity.
Ho kenya 'mele
Beha kopano ea mantlha le ea matsoeli ka har'a tanka ea oli.
Kenya li-lead le lihlahla tsa insulating, ho etsa bonnete ba ho tiisa ka nepo.
Ho Tlatsa Transformer Oli
Entela oli ea transformer e tlhotliloeng, ho netefatsa hore e hloekile ebile ha e na litšila.
Kenya Lisebelisoa tsa Kantle
Hokela li-valve tsa polokeho, li-gauge tsa boemo ba oli, le likhokahano tsa terminal.

25 kVA single phase pole transformer active part

 

 

03 Teko

Teko ea Teko le Teko e Tloaelehileng

CSA C2.2-06(R2022) E le 'ngoe-mohato o le Mong-mehato e meraro{4}}li-transformer tse tlatsitsoeng ka metsi
CSA C802.1-13(R2022) Bonyane bo sebetsang hantle bakeng sa li-transformer tse tletseng metsi
 

1. Litekanyo tsa ho hanyetsa
2. Karo-karolelano Liteko
3. Polarity Test
4. Ha ho Tahlehelo ea Mojaro 'me Ha ho na Mojaro Hona Joale
5. Litahlehelo tsa Meroalo le Matla a Matla a Impedance
6. Teko ea Voltage e sebelisitsoeng
7. Induced Voltage E mamella Teko
8. Tekanyo ea ho hanyetsa Insulation
9. Teko ea Leak e nang le Khatello bakeng sa Li-transformers tse qoelitsoeng ka Metsi
10. Tlhahlobo ea oli
 

Liphetho tsa liteko

Che.

Ntho ea Teko

Yuniti

Kamohelo

Litekanyetso

Litekanyetso Tse Lekanyelitsoeng

Qetello

1

Litekanyo tsa ho hanyetsa

/

/

/

Feta

2

Liteko tsa karo-karolelano

/

Phapang ea karo-karolelano ea motlakase ho theipi ea mantlha: Ka tlase ho kapa ho lekana le 0.5%

Letšoao la khokahano: Ii6

0.11~0.12

Feta

3

Liteko tsa polarity

/

Kekeletso

Kekeletso

Feta

4

Ha ho{{0}tahlehelo ea thepa le thabo ea hona joale

%

I0 :: fana ka boleng bo lekantsoeng(100%)

0.38

Feta

kW

P0: fana ka boleng bo lekantsoeng(100%)

0.0681

%

I0 :: fana ka boleng bo lekantsoeng(105%)

0.40

kW

P0: fana ka boleng bo lekantsoeng(105%)

0.0766

/

mamello ea ho se lahleheloe ke moroalo ke +10%

/

5

Litahlehelo tsa meroalo, motlakase oa impedance, tahlehelo e felletseng le bokhoni

/

T:85 likhato

mamello bakeng sa impedance ke ± 7.5%

mamello ea tahlehelo ea boima kaofela ke +6%

/

Feta

%

Z%: boleng bo lekantsoeng

2.60

kW

Pk: boleng bo lekantsoeng

0.366

kW

Pt: boleng bo lekantsoeng

0.4341

%

Katleho e seng ka tlase ho 98.63%

98.81

6

Teko ea Voltage e sebelisitsoeng

/

LV: 10kV 60s

HV: 40kV 60s

Ha ho ho putlama ha motlakase oa liteko

Feta

7

Teko ea ho mamella Voltage e kentsoeng

/

Matla a sebelisoang (KV): 2Ur

Ha ho ho putlama ha motlakase oa liteko

Feta

Nako:40

Hangata (HZ): 180

8

Tekanyo ea ho hanyetsa Insulation

HV{{0}LV·to·Ground

306

Feta

LV-HV ho ea fatše

422

HV&LV ho ea fatše

129

9

Leakage Test

/

Khatello e sebelisitsoeng: 20kPA

Ha ho na leakage le che

Tšenyo

Feta

Nako: 12h

10

Tlhahlobo ea oli

kV

Matla a Dielectric

61.0

 

mg/kg

Mongobo

13.6

%

Ntho ea ho senya

0.158

mg/kg

Furan Analysis

Ka tlase ho kapa ho lekana le 0.1

/

Tlhahlobo ea Khase ea Chromatography

/

image013
image015

 

 

04 Ho paka le ho Romela

25 kVA single phase pole transformer packing
 
25 kVA single phase pole transformer shipping
 
 

05 Sebaka le Kakaretso

25 kVA single phase pole transformer

E tšepahala ebile e sebetsa hantle, transformer ena ea 25 kVA e kopana le maemo a CSA C2.2-06 a nang le lintlha tse 25 kV/0.347 kV, matsoelintsoeke a aluminium, le ONAN cooling. E na le NLTC tap changer le 33 kV e tšoarang lehalima, e netefatsa hore motlakase o tsitsitse le ts'ireletso. E loketse likhoebo tsa mahaeng, tsa bolulo le tsa likhoebo tse nyane, 'me e fana ka motlakase o bolokehileng, o tšoarellang, hape o bonolo{8}ho kenya motlakase oa kantle.

 

Hot Tags: single phase pole transformer, moetsi, mofani oa thepa, theko, litšenyehelo