1000 kVA Pad Mount Transformer-13.8/0.46 kV|Guyana 2025
Matla: 1000kVA
Matla: 13.8kV-460Y/266V
Tšobotsi: ELSP ea hajoale-e fokotsa lifuse tsa bekapo

1000 kVA pad mount transformer-motlakase o bohlale bakeng sa litsi tsa khoebo, e nang le tshireletso-fuse tse pedi le phetoho e tshepahalang ya 13.8kV ho isa ho 460Y/266V
01 Kakaretso
1.1 Tlhaloso ea Morero
Ka Mmesa 2025, e mong oa bareki ba rona ba nako e telele-a Guyana o ile a etsa odara ea li-transformer tse peli: 1000kVA 13.8kV–460Y/266V-phase pad-mohau oa motlakase oa 400kVA 460–220/127VPI.omile{{0}mofuta oa transformer.
1000 kvapad mount transformere hahiloe ho latela maemo a IEEE Std C57.12.34-2022 'me e na le moralo oa loop feed o nang le tiisetso e sa sebetseng-ka pele-pele. E amohela pholiso ea ONAN (Oil Natural Air Natural) mme e kentsoe ka oli ea diminerale. Motlakase oa mantlha ke 13.8kV, 'me motlakase oa bobeli ke 460Y / 266V, o nang le sehlopha sa Dyn11 vector le 5.75% impedance.
Transformer e na le li-fuse tse tharo tsa Bayonet le li-fuse tse tharo tsa ELSP tsa hajoale-tse fokotsang li-backup fuse. Bayonet Fuse e fana ka tšireletso bakeng sa karolo e tlaase ea hona joale. ELSP Fuse e potlakisa ho tima hona joale mme e fokotsa matla a arc ha potoloho e khuts'oane e phahameng e etsahala. Ha e kopantsoe, e koahela letoto le feletseng la tšireletso ea phoso ho tloha tlaase ho ea ho ea holimo hona joale. E tsamaisana hantle le litlhoko tsa mokhoa o sireletsehileng, o tsitsitseng, ho hlokomeloa habonolo le -seseteme e sebetsang hantle ea ho aba motlakase.
1000 kVA three-phase pad mount transformer e loketse lisuphamakete le litsi tsa khoebo{2}}kV e hoketsoe ho netweke ea phepelo ea masepala, 'me 460V e sebelisoa bakeng sa li-air conditioner, mabone, lifti le lintho tse ling. Hobane mefuta e mengata e fapaneng ea lisebelisoa tsa khoebo e hloka matla a -mokhahlelo a mararo a tsitsitseng, motlakase oa 460Y/266V o lekane. Tšireletso ea li-fuse habeli e ntlafatsa boemo ba polokeho le ho fokotsa tahlehelo ea thepa e bakoang ke liphoso.
1.2 Tlhaloso ea Setsebi
1000kVA pad ea mekhahlelo e meraro e kentsoeng li-transformer le leqephe la data
|
E fetisetsoa ho
Guyana
|
|
Selemo
2025
|
|
Mofuta
Transformer ea mekhahlelo e meraro
|
|
Standard
IEEE Std C57.12.34-2022
|
|
Rated Power
1000 kVA
|
|
Khafetsa
60HZ
|
|
Fepa
Loop
|
|
Pele
E shoeleng
|
|
Mokhahlelo
Boraro
|
|
Mofuta oa ho Pholisa
ONA
|
|
Mokelikeli o thibelang metsi
Oli ea Liminerale
|
|
Voltage ea mantlha
13.8 kV
|
|
Motlakase oa bobeli
0.46 kV
|
|
Sehlopha sa Vector
Dyn11
|
|
Lintho Tse Hlahang
Koporo
|
|
Tšitiso
5.75%
|
|
Tlanya Changer
NLTC
|
|
Tlanya Range
±2*2.5%
|
|
Katleho
99.15%
|
|
Ha ho Tahlehelo ea Mojaro
1600 W
|
|
Ho Lahleheloa ke Moroalo
11800 W
|
|
Lisebelisoa
Tlhophiso e Tloaelehileng
|
1.3 Litšoantšo
1000kVA pad ea mekhahlelo e meraro e kentsoeng lebitso la transfoma le ho taka
![]() |
![]() |
02 Tlhahiso
2.1 Ntlha ea bohlokoa
Mehato e meraro-ea boraro-maoto a mantlha a sebelisa manonyeletso a koaletsoeng ka botlalo, a sebelisa lishiti tse batang-tse rolotsoeng{3}} tse tšehelitsoeng ke silicon ho fokotsa{4}}tahlehelo le ho matlafatsa matla a khoheli ka botlalo. Ka ho sebelisa manonyeletso a nang le li-mitered ka ho feletseng, matla a khoheli a lula a tsamaisana le tsela e pota-potileng ea tšepe, kahoo e fokotsa tahlehelo ea mantlha. Leha ho le joalo, ts'ebetso ena ea ho kopanya e rarahane haholoanyane, 'me botšepehi ba mochine oa mantlha bo ka fokotsoang.

2.2 Ho tsubella

Transformer e amohela foil ea motlakase e tlase le sebopeho sa terata e phahameng ea motlakase. Maqhubu a phahameng a motlakase a amohela mokhanni oa koporo oa 1.5 × 4 mm khutlonnetsepa. Motsoako ona o fana ka ts'ebetso e ntle ea mocheso, sebopeho sa compact le litšobotsi tse tšepahalang tsa motlakase.
2.3 Tanka
Transformer e na le tanka e koetsoeng e nang le sekoaelo sa bolt, se entsoeng ka tšepe e bobebe ea boleng bo holimo{{0}. Li-radiator li cheselitsoe ka mahlakoreng ka bobeli le ka morao ho tanka ho ntlafatsa phallo ea mocheso. Moralo oa tanka o tiisa matla a matla le ho tsidifala ha mokelikeli-ka metsi. Ho etsa bonnete ba hore e tšepahala, tanka e lekoa ka -ka 50 kPa ka lihora tse 24 ntle le ho lutla kapa ho senyeha.


Ea ronatse tharo-pase ea mekhahlelo-e kentsoeng ka transformere sebelisa Eaton's ELSP ea hajoale-e fokotsang fuse ea ho boloka, e tsamaisanang le Bay-O{2}}Fuse ea Net ho etsa tsamaiso e habeli ea tšireletso. Fuse ena e na le-sebete se fokotsang tšebetso ea hajoale, e fokotsang matla a maqhubu a sesebediswa, mme e loketse ho sebediswa ho oli ya diminerale ya transformer.
1. Kopano ea Core le Maqhubu
Kopanya karolo e sebetsang (ea mantlha le e matsoelintsoeke). Lieta tse bontšitsoeng setšoantšong li lokiselitsoe ho cheselletsa.
2. Ho kenngoa ha Tanka e ka Sehloohong
3. Ho kenya lisebelisoa
Transformer ena ea 1000 kva pad mount e sebelisa motsoako oa Bay-O-Net fuse le ELSP current-limiting backup fuse, e leng mokhoa o tloaelehileng oa tšireletso bakeng sa{4}}liphetoho tse qoelisoang tsa ho tsamaisa oli Amerika Leboea.
4. Ho Tlatsa Oli le Ho Tiisa
Tlatsa transformer ka oli e sireletsang 'me u tiise tanka.
5. Likhokelo tsa Motlakase le Tlhahlobo
6. Ponahalo ea ho Qetela le Tlhahlobo ea ho Ngola

03 Teko


Teko e Tloaelehileng le Tekanyetso ea Teko
1. Tekanyo ea ho Resistance ea Winding: Ho latela IEEE C57.12.90-2021 Clause 5
2. Tekanyo ea Karohano ea Voltage: Ho latela IEEE C57.12.90-2021 Clause 7
3. Teko ea Phallo ea Phase: Ho latela IEEE C57.12.90-2021 Clause 6
4. Che-Tahlehelo ea Mojaro le Che{2}}Tekanyo ea Hona Joale ea Mojaro: Ho latela IEEE C57.12.90-2021 Clause 8
5. Ho Lahleheloa ke Meroalo, Matla a Matla, le Tekanyo ea Tšebetso: Ho latela IEEE C57.12.90-2021 Clause 9 le CSA-C802.1-13 Clause 6
6. Applied Voltage Test: Ho latela IEEE C57.12.90-2021 Clause 10.6
7. Induced Voltage Withstand Test: Ho latela IEEE C57.12.90-2021 Clause 10.5.1
8. Teko ea ho Dutla ka Khatello ea Mokelikeli-Li-Immersed Transformers: Teko e lutlang ka 50KPa e tla etsoa lihora tse 24 ntle le ho lutla. Ha ho deformation e sa feleng.
9. Tekanyo ea ho hanyetsa Insulation
10. Teko ea Matla a Dielectric ea Oli ea Transformer
Liphetho tsa liteko
|
Che. |
Ntho ea Teko |
Yuniti |
Melao ea ho Amohela |
Litekanyetso Tse Lekanyelitsoeng |
Qetello |
|
1 |
Litekanyo tsa ho hanyetsa |
% |
Sekhahla se phahameng sa ho hanyetsa ho se leka-lekane Ka tlase kapa ho lekana le 5% |
1.68 |
Feta |
|
2 |
Liteko tsa Karolelano |
% |
Phapang ea karo-karolelano ea motlakase ho theipi ea mantlha: Ka tlase ho kapa ho lekana le 0.5% Letšoao la khokahano: Dyn11 |
-0.09%~-0.08% |
Feta |
|
3 |
diteko- tsa dikamano |
/ |
Dyn11 |
Dyn11 |
Feta |
|
4 |
Ha ho{{0}tahlehelo ea thepa le thabo ea hona joale |
/ |
I0 :: fana ka boleng bo lekantsoeng |
0.77% |
Feta |
|
P0: fana ka boleng bo lekantsoeng(t:20 degree) |
1.465kW |
||||
|
mamello ea ho se lahleheloe ke moroalo ke +10% |
/ |
||||
|
5 |
Litahlehelo tsa tahlehelo ea matla a motlakase le katleho |
/ |
T:85 likhato mamello bakeng sa impedance ke ± 7.5% mamello ea tahlehelo ea boima kaofela ke +6% |
/ |
Feta |
|
Z%: boleng bo lekantsoeng |
5.62% |
||||
|
Pk: boleng bo lekantsoeng |
11.085kW |
||||
|
Pt: boleng bo lekantsoeng |
12.550 kW |
||||
|
Katleho e seng ka tlase ho 99.15% |
99.21% |
||||
|
6 |
Teko ea Voltage e sebelisitsoeng |
kV |
HV: 34kV 60s LV: 10kV 60s |
Ha ho ho putlama ha motlakase oa liteko |
Feta |
|
7 |
Teko ea ho mamella Voltage e kentsoeng |
kV |
Matla a sebelisoang (KV): 2Ur |
Ha ho ho putlama ha motlakase oa liteko |
Feta |
|
Matla a susumetsoang (KV): 27.6 |
|||||
|
Nako:48 |
|||||
|
Hangata (HZ): 150 |
|||||
|
8 |
Leakage Test |
kPa |
Khatello e sebelisitsoeng: 50kPA |
Ha ho na leakage le che Tšenyo |
Feta |
|
Nako: 24h |
|||||
|
9 |
Tekanyo ea ho hanyetsa Insulation |
GΩ |
HV{{0}LV ho ea fatše : |
48.4 |
/ |
|
LV-HV ho ea fatše: |
65.5 |
||||
|
HV&LV ho ea fatše: |
51.9 |
||||
|
10 |
Teko ea Dielectric ea Oli |
kV |
E kholo ho feta kapa e lekana le 45 |
56.5 |
Feta |
04 Sebaka le Kakaretso

SCOTECHe fana ka li-transformer tse fetang 12,000,000 tsa kVA lefatšeng ka bophara selemo se seng le se seng, e matlafatsa malapa le likhoebo tse ngata. Re na le boiphihlelo bo bongata ba ho rala le ho hlahisa li-transformer tse kentsoeng ka mekhahlelo e meraro. Ebang ke CSA Standard kapa IEEE Standard, re na le linyeoe tse ngata. Matla a lekantsoeng ho tloha ho 100 kVA ho isa ho 5000 KVA. Re etsa bonnete ba hore karolo e 'ngoe le e 'ngoe e etsa liteko tse matla tsa ho amoheloa. Tšepo ea ho fumana tšepo ea hau.
Hot Tags: 1000 kva pad mount transformer, moetsi, mofani oa thepa, theko, litšenyehelo
You Might Also Like
75 kVA 3 Phase Distribution Transformer-13.8/0.208 k...
300 kVA Oli e Tlatsang Transformer-13.2 / 0.48 kV|Gu...
750 kVA Pad Mounted Transformer-13.2/0.48 kV|Sebelis...
1000 kVA Dead Front Transformer-24/0.48 kV|Sebelisa ...
1250 kVA Pad Mounted Transformer-12.47/0.6 kV|Sebe...
500 kVA Pad Mounted Transformer-13.2/0.48 kV|USA 2025
Romela Inquiry