800kVA cast coil dry type transformer e ile ea isoa Afrika Boroa ka 2025. Matla a lekantsoeng a transformer ke 800 kVA e nang le pholiso ea KNAN/KNAF. Motlakase o ka sehloohong ke 6.6 kV o nang le ± 2 * 2.5% tapping range (NLTC), motlakase oa bobeli ke 0.55 kV, ba thehile sehlopha sa vector sa Dyn11.
Lefatšeng la kajeno, moo tsoelo-pele ea khoebo, polokeho, le ts'ebeliso e ntle ea matla e leng tsona tsa bohlokoa, mochini o bitsoang cast coil dry{0}} o eme e le motheo oa mokhoa oa sejoale-joale oa ho tsamaisa motlakase. E etselitsoe ho ts'epahala ho fetisisa, li-transformer tsena li fana ka khotso ea kelello e ke keng ea lekanngoa. Lelakabe la tsona-moetso oa epoxy-o kentsoeng ka thata{4}} o felisa likotsi tsa mollo, e leng se lumellang hore ho kenngoe ka mokhoa o sireletsehileng haufi le thepa ea hau e boima, e bolokang sebaka sa bohlokoa le ho fokotsa litšenyehelo tsa ho instola.
Re tsepamisitse maikutlo tabeng ea ho tšoarella le litšenyehelo tse tlase kaofela tsa thepa, li-cast coil transformer li na le meralo e phahameng-e fokotsang tahlehelo ea matla, e leng se lebisang ho bolokeheng ha ts'ebetso. Ha li hloke ho hlokomeloa 'me li hahiloe ho mamella maemo a thata ka ho fetisisa a indasteri, ho netefatsa hore ho na le motlakase o sa sitisoeng bakeng sa ts'ebetso ea hau ea bohlokoa-ho tloha ho lifeme tsa tlhahiso le merero ea matla a ka nchafatsoang ho ea litsing tsa khoebo le lisebelisoa tsa sechaba. Khetha theknoloji ea li-coil bakeng sa tharollo ea motlakase e bohlale, e sireletsehileng le e tšoarellang.
1.2 Tlhaloso ea Setsebi
Tlhaloso ea 800 kVA e lahlileng coil e omileng ea mofuta oa transformer le leqephe la data
|
E fetisetsoa ho
Afrika Boroa
|
|
Selemo
2025
|
|
Mofuta
mofuta o omileng oa transformer
|
|
Boitsebiso ba mantlha
Letlapa la tšepe la silicon le entsoeng ka lijo-thollo
|
|
Standard
IEC60076
|
|
Rated Power
800kVA
|
|
Khafetsa
50HZ
|
|
Sehlopha sa Vector
Dyn11
|
|
Mokhahlelo
3
|
|
Mofuta oa ho Pholisa
ONAN/ONAF
|
|
Voltage ea mantlha
6.6kV
|
|
Motlakase oa bobeli
0.55kV
|
|
Lintho Tse Hlahang
Koporo
|
|
Tšitiso
6%
|
|
Tlanya Changer
NLTC
|
|
Tlanya Range
±2*2.5%@lehlakoreng la mathomo
|
|
Ha ho Tahlehelo ea Mojaro
1.52KW
|
|
Ho Lahleheloa ke Moroalo
6.96KW
|
|
Mabone a mantlha a mamellang voltage primary side (BIL)
60kV
|
|
Maqhubu a Matla a mamellang -karolo ea mantlha
20kV
|
|
Power Frequency e mamella voltage{0}}ka lehlakoreng la bobeli
3kV
|
|
Mocheso o matla oa moea o nyoloha@ boemo ba tšebeletso bo lekantsoeng
100K
|
|
Boemo ba insulation
F
|
1.3 Litšoantšo
800 kVA e entsoeng ka resin e omileng ea mofuta oa setšoantšo sa setšoantšo le boholo.
![]() |
![]() |
02 Tlhahiso
2.1 Ntlha ea bohlokoa

Iron core e entsoe ka boqhetseke hore e sebetse maemong a tlase, e fokotsang{0}tahlehelo haholo le ho netefatsa ts'ebetso e khutsitseng. Ho thibela litsela tsa hona joale tsa eddy, li-laminations tse tšesaane li koahetsoe ka bonngoe ka lera la insulating. Ka mor'a ho bokellana, core e tlamahanngoa ka mokhoa o sireletsehileng 'me e thehiloe sebakeng se le seng, ho felisa kotsi ea ho potoloha ha maqhubu le ho netefatsa ts'ebetso e bolokehileng, e ts'eptjoang le e sebetsang hantle{3}.
2.2 Ho tsubella
Bakeng sa li-winding tsa transformer tse entsoeng ka "cast coil dry type", li-conductors li hlophisoa ka mokhoa o hlophisehileng 'me li kenngoa ka lisebelisoa tsa khalase pele, 'me li lateloe ke vacuum pressure casting e nang le mocheso-resistant epoxy resin compound. Maqhubu a folisitsoeng a etsa mokhoa o tiileng oa ho kenya letsoho o nang le matla a phahameng a dielectric le mocheso oa mocheso bakeng sa ho qhala mocheso hantle, empa hape o na le matla a matla a thibelang-tšilafalo le{3}}a thibela ho bola, a loketseng lisebelisoa tse fapaneng tsa ka hare le tsa ka ntle.

2.3 Kopano ea ho Qetela

Bakeng sa kopano ea transformer ea coil e omeletseng, motheo oa tšepe o behiloe ka thata pele. Li-windling{{1}tse tlang pele li tla kopanngoa holim'a motheo ka likaroloana tse tiisang boemo ba tsona. Likamano tse etellang pele lipakeng tsa matsoelintsoeke le li-terminals tsa kantle li entsoe, 'me litsamaiso tsa ho pholisa (joalo ka li-axial fans) lia kopanngoa. Ka mor'a moo, sebaka seo sea khomareloa, 'me -litlhahlobo tsa poso-ho kenyeletsoa liteko tsa ho hanyetsa le ho feto-fetoha ha mocheso-li etsoa ho netefatsa bots'epehi le ts'ebetso ea yuniti.
03 Teko
Liteko tsa 800kVA-6.6/0.55kV cast coil dry type transformer li lumellana le IEC 60076-1, 60076-3 le 60076-11 maemo a, a koahelang lintho tse tloahelehileng: tekanyo ea winding resistance (unbalance rate (unbalance rate D) kapa tekanyo e lekanang le 2%) kapa tekano ea voltage. ho kheloha ± 1/10), ho sitisa potoloho e khuts'oane / tahlehelo ea mojaro le tahlehelo ea moroalo / liteko tsa hajoale, tlhahlobo ea motlakase e sebelisitsoeng (HV 20kV / 60s, LV 5kV / 60s), tlhahlobo ea matla a ho mamella mocheso (1.1kV, 150Hz, 40s), le teko ea ho tsoa ka mokhoa o sa fellang (max 1p) ho feta 1p); litekanyetso tsohle tse lekantsoeng li fihlela litlhoko, ka sephetho sa "Pass".
|
Che. |
Ntho ea Teko |
Yuniti |
Kamohelo Litekanyetso |
Litekanyetso Tse Lekanyelitsoeng |
Qetello |
|
|
1 |
Tekanyo ea ho hanyetsa matsoelintsoeke |
/ |
Sekhahla se phahameng sa ho hanyetsa ho se leka-lekane Khanyetso ea mela: e ka tlase ho kapa e lekana le 2% |
HV (mohala) |
LV (mohala) |
Feta |
|
0.04% |
1.56% |
|||||
|
2 |
Tekanyo ea karo-karolelano ea motlakase le ho hlahloba phallo ea mohato |
/ |
Mamello ea karo-karolelano ea motlakase ho theipi ea mantlha: ± 1/10 Letšoao la khokahano: Dyn11 |
-0.17% ~ 0.22% Dyn11 |
Feta |
|
|
3 |
Tekanyo ea -nako e Khutšoane ea Impedance le Loss Loss |
/ kW kW |
T:120 likhato Z%: boleng bo lekantsoeng Pk: boleng bo lekantsoeng Pt: boleng bo lekantsoeng |
5.93% 5.891 7.586 |
Feta |
|
|
4 |
Tekanyo ea Ha ho-Tahlehelo ea Mojaro le Hona Joale ho 90% le 110% ea matla a matla a motlakase |
/ kW |
I0 : fana ka boleng bo lekantsoeng P0: fana ka boleng bo lekantsoeng |
90% Ur |
0.22 1.059 |
Feta |
|
100% Ur |
0.41 1.415 |
|||||
|
110% Ur |
1.15 1.952 |
|||||
|
5 |
Teko ea Voltage e sebelisitsoeng |
/ |
HV: 20kV 60s LV: 5kV 60s |
Ha ho ho putlama ha motlakase oa liteko |
Feta |
|
|
6 |
Teko ea ho mamella Voltage e kentsoeng |
/ |
Matla a sebelisoang (KV): 2 Ur Matla a hlahisoang ke matla (KV): 1.1 Nako:40 Hangata (HZ): 150 |
Ha ho ho putlama ha motlakase oa liteko |
Feta |
|
|
7 |
Teko ea Phallo e sa Feleng |
pC |
Boemo bo phahameng ba ho tsoa ha karolo e itseng e tla ba 10 pC |
<10 |
Feta |
|


04 Ho paka le ho Romela
4.1 Ho paka

Bakeng sa li-transformer tsa mofuta o omeletseng oa li-coil, liphutheloana tsa mabokose a lepolanka li na le likhutlo tse matlafalitsoeng le likhoele tsa tšepe ka ntle ho crate. Ka hare, litšehetso tsa lehong li sebelisoa ho ikamahanya le motheo oa transformer, li-buffers tsa foam li tlatsa likheo lipakeng tsa 'mele le kreiti, 'me ho kentsoe lerōle le tiisitsoeng-le loketseng ho sireletsa yuniti nakong ea{3}}ea sebaka se selelele kapa{4}karollo e boima{4}.
4.2 Ho tsamaisa thepa
Bakeng sa transformer ea mofuta o omileng oa coil, lipalangoang li hlophisitsoe tlas'a maemo a CIF ho ea boema-kepeng ba Durban. Thepa ea lehong-e paketetsoeng ea transformer e kenngoa ka har'a lik'hontheinara tse romelloang; morekisi o jara thepa ea leoatleng 'me o fumana inshorense ea thepa ea metsing e koahelang likotsi tsa mantlha. E tla tsamaisoa ka mokhoa o sireletsehileng ho ea boema-kepeng ba Durban, 'me morekisi a phethahatsa boitlamo ba ho tlisa thepa ha a kenya thepa sekepeng.

05 Sebaka le Kakaretso
Ha re kopanya tekhenoloji e tsoetseng pele ea li-coil le polokeho ea tlhaho ea-mofuta oa mofuta o omileng, transformer ea rona ea cast coil dry type e sebetsana le tlhokahalo e matla ea kabo ea motlakase e tsitsitseng, e tlase{1}}e leng kotsi e tlase. E nepahetse bakeng sa tikoloho eo ho eona{3}}liyuniti tse tlatsitsoeng oli li sa sebetseng, e sebetsa hantle maemong a thata kapa a hlokolosi ha e ntse e kopana le litekanyetso tsa tšebetso ea lefats'e. Ho feta karolo e 'ngoe, ke mokokotlo o tsitsitseng oa lisebelisoa tsa hau tsa motlakase{{5}tse tšehetsoang ke boleng ho matlafatsa ts'ebetso ea hau ea nako e telele{6}.

Hot Tags: low voltage omileng mofuta oa transformer, moetsi, mofani oa thepa, theko, litšenyehelo
You Might Also Like
3 MVA Mofuta o omileng oa Transformers-13.8 / 0.48 k...
500 kVA Dry Resin Transformer-13.8 / 0.46 kV|Afrika ...
2500 kVA Dry Transformer-10/0.4 kV|Georgia 2025
1.25 MVA Cast Resin Mofuta oa Transformer-0.415 / 3....
12 kVA Dry Distribution Transformer-11/0.22 kV|Unite...
1500 KVA Medium Voltage Dry Type Transformers-15/0.5...
Romela Inquiry