3 MVA Mofuta o omileng oa Transformers-13.8 / 0.48 kV|Jamaica 2025
Matla: 2400/3000kVA
Matla: 13.8/0.48kV
Tšobotsi: e nang le fan e pholileng

Resin casting tiisetso, ho sireletsa mantlha ea motlakase, khetho e sireletsehileng le e sebetsang ea li-transformer!
01 Kakaretso
1.1 Tlhaloso ea Morero
Matla a 2400/3000 kVAli-transformer tsa mofuta o omilengli ile tsa isoa Jamaica ka 2025, matla a lekantsoeng a transformer ke 2400/3000 kVA. Matla a phahameng a motlakase oa mofuta ona o omileng ke 13.8kV, matla a tlaase ke 0.48kV. Transformer ena ea mofuta o omileng oa motlakase o phahameng o na le mochine o sa fetoleng mojaro oa pompo, sebaka sa ho thepha ke ± 2 * 2.5% ka lehlakoreng la mantlha, pholileng ke ONAN/ONAF.
Sena ke 2400/3000kVAlahla coil omileng mofuta oa transformere etselitsoe litsamaiso tsa sejoale-joale tsa matla, tse kopanyang ts'ebetso e phahameng, polokeho, le likarolo tse bohlale tsa taolo. E sebelisa-moetso o thusang oa ho pholisa 'me e tla e na le mabili a tenyetsehang, e netefatsang hore e tsamaisoa ka potlako le ho kengoa ha e ntse e ikamahanya le maemo a fapaneng a lits'ebetso. Fene e sebetsa ka matla a matla a 220V, a kopantsoeng le matla a matla a ho laola mocheso a 125V, a fana ka ts'ebetso e tšepahalang le ho ntlafatsa matla a matla.
Bakeng sa ho ngola motlakase, sehlahisoa se sebelisa li-tubing tse fokotsang mocheso le li-tag tsa tatellano ea likarolo tse nang le likhoutu tsa mebala: bofubelu bakeng sa karolo ea A, bosehla bakeng sa mohato oa B, boputsoa bakeng sa mohato oa C, le botšo bakeng sa ho se nke lehlakore. Sena se tiisa ts'ebetso e bonolo ea pono le ts'ireletso e ntlafalitsoeng ea sistimi nakong ea ts'ebeliso.
Ho feta moo, transformer e na le selaoli se phahameng sa-se sebetsang hantle se laolang mocheso ka linako tsohle, se fana ka tšireletso e bohlale khahlanong le mocheso o feteletseng le ho lelefatsa nako ea bophelo ea sesebelisoa ka nepo. Karolo ena e netefatsa botsitso bo ikhethang- libakeng tse phahameng tsa ts'ebetso le tsa bohlokoa.
Ebang ke bakeng sa lifeme tsa liindasteri, lits'ebeletso tsa khoebo, litsi tsa boitsebiso, kapa maemo a mang-a mahlahahlaha a matla, transformer ena ea 2400/3000kVA{3}}e fana ka tharollo e sebetsang hantle, e tšepahalang, le{4}e bonolo ho basebelisi, e fana ka taolo e sireletsehileng le e bohlale ho feta ea matla.
1.2 Tlhaloso ea Setsebi
Tlhaloso ea 2400/3000 kVA ea mofuta o omileng oa li-transformer le leqephe la data
|
E fetisetsoa ho
Jamaica
|
|
Selemo
2025
|
|
Mofuta
Resin cast omileng mofuta oa transformer
|
|
Boitsebiso ba mantlha
Letlapa la tšepe la silicon le entsoeng ka lijo-thollo
|
|
Standard
IEC60076
|
|
Rated Power
2400/3000kVA
|
|
Khafetsa
50HZ
|
|
Sehlopha sa Vector
Dyn1
|
|
Mokhahlelo
3
|
|
Mofuta oa ho Pholisa
ONAN/ONAF
|
|
Voltage ea mantlha
13.8 kV
|
|
Motlakase oa bobeli
0.48 kV
|
|
Lintho Tse Hlahang
Aluminium
|
|
Tšitiso
6.04(±10%)%
|
|
Tlanya Changer
NLTC
|
|
Tlanya Range
± 2*2.5% @ motlakase oa mantlha
|
|
Ha ho Tahlehelo ea Mojaro
3.5 kW
|
|
Ho Lahleheloa ke Moroalo
17.17 kW
|
|
Boemo ba insulation
F
|
1.3 Litšoantšo
2400/3000 kVA resin e entseng setšoantšo sa li-transformer tsa mofuta o omileng le boholo.

02 Tlhahiso
2.1 Ntlha ea bohlokoa
Mokotla oa tšepe oa li-transformer tsa mofuta o omileng oa resin o entsoe ka mohatsela o matla oa makenete-lithollo tse kolokisitsoeng{1}}ka maqephe a tšepe a silicon, a sebetsoa ka mokhoa oa ho itšeha kapa ka mokhoa o nepahetseng oa setempe, 'me o sebelisa sebopeho sa laminated ho fokotsa tahlehelo ea hona joale ea eddy. Bokaholimo ba mantlha bo apesitsoe ka lera le khethehileng la insulating ho matlafatsa ho hanyetsa mongobo le ts'ebetso ea ho kenella. E na le kopano e kopaneng le e nepahetseng, e nang le-matla a makenete a sebelisetsoang ho lokisa ho fokotsa lerata le khatello ea maikutlo. Sebopeho sa kakaretso se hatisa ts'ebetso e phahameng, tahlehelo e tlaase, le ho senya mocheso o motle, ho etsa hore e be karolo ea bohlokoa bakeng sa ts'ebetso e tsitsitseng ea transformer.

2.2 Ho tsubella

Coil ea li-transformer tsa mofuta o omileng oa resin e entsoe ka mapheo a aluminium a phahameng a conductivity, a tiisitsoeng ka botlalo ka resin ea epoxy bakeng sa insulation e ntle haholo, ho hanyetsa mocheso le ts'ireletso ea mongobo, ho thibela ka katleho lipotoloho tse khutšoane le ho tsoa ka mokhoa o itseng. Coil e na le mohaho o kopanetsoeng o nang le matla a phahameng a mochine, 'me moralo o ntlafetseng oa ho senya mocheso o tiisa taolo ea mocheso le ts'ebetso e tsitsitseng. Ts'ebetso ea ho lahla resin e boetse e na le litšobotsi tsa tikoloho, e fokotsang ho thothomela le lerata, e lumellang coil ho boloka ts'epo e phahameng le botsitso bo phahameng ba ts'ebetso libakeng tse rarahaneng.
2.3 Kopano ea ho Qetela
Ho kenya likhoele: Kenya likhoele tsa resin tse seng li tšolotsoe holim'a mokokotlo oa tšepe. Ho ea ka litlhoko tsa litšoantšo tsa moralo, etsa bonnete ba hore khoele e 'ngoe le e' ngoe e hlophisitsoe hantle ebile e tsitsitse. Likarolo tsa ho koala pakeng tsa likhoele le lipakeng tsa likhoele le mantlha li lokela ho ba tse tiileng ho thibela li-circuits tse khutšoane.
Theminale ea khokahanyo: Hokela ntlha e ka pele-ea ka ntle ea khoele ho theminale ea transformer. Netefatsa hore khokahano e tsitsitse mme o etsa kalafo e hlokahalang ho thibela ho lutla le potoloho e khuts'oane.
Ho kenngoa ha sistimi e pholileng: Kenya fan ho latela litlhoko tsa moralo ho netefatsa hore transformer e khona ho qhala mocheso hantle nakong ea ts'ebetso le ho boloka mocheso o tloaelehileng oa ho sebetsa.

03 Teko
|
Che. |
Ntho ea Teko |
Yuniti |
Melao ea ho Amohela |
Litekanyetso Tse Lekanyelitsoeng |
Qetello |
||||
|
1 |
Tekanyo ea ho hanyetsa matsoelintsoeke |
/ |
Sekhahla se phahameng sa ho hanyetsa ho se leka-lekane Khanyetso ea mela: e ka tlase ho kapa e lekana le 4% |
HV (mohala) |
LV (mohala) |
Feta |
|||
|
0.09% |
0.9% |
||||||||
|
2 |
Tekanyo ea ho hanyetsa Insulation |
MΩ |
HV{{0}LV & E |
R15 |
R60 |
/ |
|||
|
2500 |
2500 |
||||||||
|
LV-HV &E |
R15 |
R60 |
|||||||
|
2500 |
2500 |
||||||||
|
Ea mantlha-E |
R15 |
R60 |
|||||||
|
2500 |
2500 |
||||||||
|
3 |
Tekanyo ea karo-karolelano ea motlakase le ho hlahloba phallo ea mohato |
/ |
Mamello ea karo-karolelano ea motlakase ho theipi ea mantlha: ± 1/10 Letšoao la khokahano: Dyn1 |
-0.08% ~ 0.07% Dyn1 |
Feta |
||||
|
4 |
Tekanyo ea Che{0} ea Tahlehelo ea Mojaro le ea Hona Joale ho 90%, 100% le 110% ea matla a matla a motlakase. |
/ kW |
I0 :: fana ka boleng bo lekantsoeng P0: fana ka boleng bo lekantsoeng |
90%Ur |
100%Ur |
110%Ur |
Feta |
||
|
0.27% 2.684 |
0.30% 2.983 |
0.33% 3.281 |
|||||||
|
5 |
Litahlehelo tsa Meroalo, Impedans Voltage |
/ kW kW |
T:120 likhato Z%: boleng bo lekantsoeng Pk: boleng bo lekantsoeng Pt: boleng bo lekantsoeng |
2400kVA |
3000kVA |
Feta |
|||
|
6.18% 13.555 17.219 |
7.73% 21.370 27.285 |
||||||||
|
6 |
Teko ea Voltage e sebelisitsoeng |
/ |
HV: 38kV 60s LV: 3kV 60s |
Ha ho ho putlama ha motlakase oa liteko |
Feta |
||||
|
7 |
Teko ea ho mamella Voltage e kentsoeng |
/ |
Matla a sebelisoang (kV): 2 Ur Matla a susumetsoang (kV): 0.96 Nako:40 Hangata (HZ): 150 |
Ha ho ho putlama ha motlakase oa liteko |
Feta |
||||
|
8 |
Teko ea Phallo e sa Feleng |
pC |
Boemo bo phahameng ba ho tsoa ha karolo e itseng e tla ba 10 pC |
<10 |
Feta |
||||
|
9 |
Mocheso Ho phahama |
/ |
Mocheso oa moea oa moea o nyoloha Ka tlase ho kapa ho lekana le 100K |
Ho ruruha ha HV |
LV ho potoloha |
Feta |
|||
|
88 |
92 |
||||||||


04 Ho paka le ho Romela
4.1 Ho paka
Sefetoleli sa mofuta oa cast coil dry{0} se pakiloe ka har'a kreiti ea lepolanka, e koahetsoeng ka{1}}mokotlana oa foil oa aluminium o thibelang mongobo ho sireletsa lerōle le mongobo nakong ea lipalangoang le polokelo. Kereiti e matla ea lepolanka e kenyelletsa ho ts'oara ka hare ho thibela ts'abo le ts'enyehelo ea ho sisinyeha.

4.2 Ho tsamaisa thepa

Ho tsamaisoa ha transformer ho sebelisa nomoro ea setshelo CSNU7745546 ho ea boema-kepeng ba Kingston ho kenyelletsa ho tiisa ka mokhoa o sireletsehileng transformer ka har'a sets'oants'o. Ka mor'a ho laela, setshelo se tla isoa boema-kepe 'me se kenngoe sekepeng ka mokhoa o sireletsehileng. Nakong ea lipalangoang tsa leoatle, boemo ba thepa bo tla beoa leihlo ho netefatsa polokeho ea setshelo. Ha o fihla Kingston, setshelo se tla theoloa ho sebelisoa lisebelisoa tsa ho phahamisa, 'me se lateloe ke tlhahlobo. Ka mor'a moo, tumello ea lekhetho e tla phethoa pele ho tsamaisoa transformer ho ea moo e eang teng. Nakong eohle ea ts'ebetso, ho tlameha ho lebisoa tlhokomelo ho polokeho ea lipalangoang, 'me inshorense e lokela ho rekoa bakeng sa lisebelisoa ho fokotsa likotsi tsa lipalangoang.
05 Sebaka le Kakaretso
Qetellong, li-transformer tsa mofuta oa resin cast li emela tsoelo-pele e kholo ho theknoloji ea transformer, e fanang ka polokeho e ntlafalitsoeng, ts'epahalo le tšebelisano ea tikoloho. Mohaho oa bona o ikhethang o sebelisang epoxy resin ha o fane feela ka mokhoa o babatsehang oa ho kenya letsoho le ho hanyetsa mongobo empa hape o lumella moralo o kopanetsoeng o loketseng maemo a fapaneng a ho kenya. Ka litlhoko tse fokolang tsa tlhokomelo le nako e telele ea nako e telele, li-transformer tsena ke khetho e nepahetseng bakeng sa lits'ebetso makaleng a khoebo, a indasteri le a ka nchafatsoang. Ha liindasteri li ntse li tsoela pele ho beha ts'ebetso le ts'ebetso e tlang pele, li-transformer tsa mofuta oa resin cast ha ho pelaelo hore li tla bapala karolo ea bohlokoa lits'ebetsong tsa sejoale-joale tsa phepelo ea motlakase, ho kenya letsoho bokamosong bo botala le bo ts'epahalang haholoanyane.

Hot Tags: li-transformer tsa mofuta o omileng, moetsi, mofani oa thepa, theko, litšenyehelo
You Might Also Like
500 kVA Dry Resin Transformer-13.8 / 0.46 kV|Afrika ...
400 kVA Mofuta o omileng oa Motlakase Transformers-0...
250 kVA Dry Cast Resin Transformers-10/0.4 kV|Georgi...
160 kVA Indoor Dry Type Transformer-10/0.4 kV|Georgi...
630 kVA Three Phase Dry Type Transformer-10/0.4 kV|G...
630 kVA 3 Phase Dry Type Transformer-6.6/0.55 kV|Afr...
Romela Inquiry