100 kVA Pole Mount Transformer-24.94/0.347 kV|Canada 2024
Matla: 100 kVA
Matla: 24.94GrdY/14.4-0.347 kV
Sebopeho: ka IFD

Boemo bo Nyenyane, Botšepehi bo Phahameng - Li-Pole Mounted Transformers bakeng sa Phano e Ntle ea Matla.
01 Kakaretso
1.1 Tlhaloso ea Morero
100 kVA single phase pole mounted transformer e ile ea isoa Canada ka 2025. Matla a lekantsoeng a transformer ke 100 kVA e nang le pholiso ea ONAN. Motlakase o ka sehloohong ke 24.94GrdY / 14.4 kV e nang le ± 2 * 2.5% tapping range (NLTC), motlakase oa bobeli ke 0.347 kV, ba thehile sehlopha sa vector sa Ii6.
Transformer ena ea 100 kVA pole{1}}e entsoe bakeng sa-ho sebetsa hantle haholo ka har'a marang-rang a motlakase, e kopanyang ts'epahalo, polokeho, le ho ikamahanya le maemo bakeng sa lits'ebetso tsa mahaeng le litoropong. E etselitsoe ho mamella maemo a thata a tikoloho le a ts'ebetso, e kenyelletsa likarolo tsa bohlokoa tsa ts'ireletso le ts'ebetso ho netefatsa ts'ebeletso e sa sitisoeng le bophelo bo atolositsoeng ba ts'ebetso.
Likarolo tsa bohlokoa li kenyelletsa sesebelisoa sa ho imolla khatello ho ntša khatello e feteletseng ka mokhoa o sireletsehileng haeba ho na le liphoso tse ka hare, ho fokotsa kotsi ea ho phatloha ha tanka. Ts'ehetso e kopaneng ea ho ts'oara e fana ka ts'ebetso e sireletsehileng bakeng sa li-surge arresters, e matlafatsang tšireletso khahlanong le ho otla ha lehalima le transients ea motlakase. Bakeng sa ho lemoha liphoso tse tsoetseng pele, transformer e na le Internal Fault Detector (IFD), e nolofalletsang ho lemoha lintho tse sa tloaelehang ho thibela ho hlōleha ha koluoa. Ho feta moo, mochine o timang-o lumella ho feto-fetoha ha motlakase o feto-fetohang (ha{4}}o matlafalitsoe), ho netefatsa hore o sebetsa hantle tlas'a maemo a sa tšoaneng.
E hahiloe bakeng sa ho tšoarella le boiketlo ba tlhokomelo, transformer ena e fana ka kabo e nepahetseng ea matla ha e ntse e etelletsa pele polokeho le botsitso ba ts'ebetso, e etsa hore e be tharollo e nepahetseng bakeng sa meaho ea motlakase ea sejoale-joale.
1.2 Tlhaloso ea Setsebi
167 kVA pole mounted transformer specifications type le data sheet
|
E fetisetsoa ho
Canada
|
|
Selemo
2025
|
|
Mofuta
Pole mounted transformer
|
|
Standard
CSA C2.2-06
|
|
Rated Power
100 kVA
|
|
Khafetsa
60HZ
|
|
Mokhahlelo
1
|
|
Polarity
Kekeletso
|
|
Mofuta oa ho Pholisa
ONA
|
|
Voltage ea mantlha
24.94GrdY/14.4 kV
|
|
Motlakase oa bobeli
0.347 kV
|
|
Lintho Tse Hlahang
Aluminium
|
|
Angular displacement
Ii6
|
|
Tšitiso
3%
|
|
Tlanya Changer
NLTC
|
|
Tlanya Range
±2*2.5%
|
|
Ha ho Tahlehelo ea Mojaro
0.195 kW
|
|
Ho Lahleheloa ke Moroalo
1.52 kW
|
|
Lisebelisoa
Tlhophiso e Tloaelehileng
|
1.3 Litšoantšo
167 kVA poling mounted transformer diagram to the size and size.
![]() |
![]() |
02 Tlhahiso
2.1 Konokono
Thepa ea tšepe ea silicon e ntse e tsoela pele ho sebelisoa mochini o nepahetseng, e leng ho etsang hore ho be le motsoako- o sa lefelloeng o nang le tsela e ts'oanang ea makenete, 'me o fokotsa tahlehelo ea hysteresis le lerata. Moralo o sa tsitsang o fokotsa ho sisinyeha ha magnetostriction{2}}e bakang lerata le tlase ka 5-10 dB ho feta li-cores tsa laminated. Tsela ea symmetrical magnetic e matlafatsa ho hanyetsa leeme la DC, e etsa hore e tšoanelehe bakeng sa marang-rang a kabo a nang le liphetoho tse kholo tsa motlakase. Bokhoni bo phahameng ba sebaka sa maqeba bo lumellana le litlhoko tsa boholo ba compact tsa pole{7}}li-transformer tse kanngoeng, tse tsamaisanang le tlhophiso ea likhetla-le mefuta ea mantlha.

2.2 Ho tsubella

Pole-li-transformer tse kentsoeng li sebelisa moralo o ntlafalitsoeng oa aluminium oa LV + terata ea koporo ea HV: Lehlakore la LV le sebelisa foil ea aluminium e nang le maqeba a hlabang (0.2–1.0mm) bakeng sa ho pholisa hantle, ho sebetsa hantle ka litšenyehelo, 'me ho se hokae{4}}mohaho oa potoloho, ha lehlakore la HV le sebelisa leqeba la koporo windings bakeng sa conductivity e phahameng ea 5k le V7. Sethibelo sa "insulating pressboard" le "vacuum impregnation" se matlafatsa matla a dielectric. Sebaka se seholo sa foil se ntlafatsa ho qhala ha mocheso, 'me ho teteana ha koporo ho etsa bonnete ba ho kopana. Tharollo ena e nyalisitsoeng e leka-lekanya moruo (Al) le ho tšepahala (Cu), e fokotsa-tahlehelo ea thepa ka 15-25%, e leng se etsang hore e be se loketseng bakeng sa marang-rang a phano.
2.3 Tanka
Lihlahisoa tsa rona li latela sehlopha sa C4 corrosion resistance. Lintlafatso tse latelang tsa tekheniki li netefatsa ts'ebetso e holimo:
1- Matlafatso ea Taolo ea Ts'ebetso
Mekhoa e ntlafalitsoeng ea ho alafa bokaholimo e amoheloa, ka ho hloekisoa ka thata le ts'ebetso ea kalafo ea lik'hemik'hale ho felisa ka botlalo tšilafalo ea substrate ha e ntse e netefatsa ho latela ka botlalo lintlha tsa botenya.
2- Ntlafatso ea Sebopeho
Theknoloji e felletseng-ea seam sealing e sebelisoa ho li-welds tsa bohlokoa, ho thibela ka nepo ho kenella ha mongobo ka har'a li-transformer tse ka hare le ho ntlafatsa haholo{1}}botšepehi ba ts'ebetso ea nako e telele.

2.4 Kopano ea ho Qetela

1. Ho Kenngwa ha Maqhubu:Tsamaisa mapheo a phahameng-le a tlase-ea matla a motlakase holim'a konokono ea laminated, ho netefatsa hore ho tsepamisoa hantle le ho lokisa ka mokhoa o sireletsehileng.
2. Lihokelo tsa Motlakase:Connect winding e lebisa ho chencheng ea pompo, lihlahla le likarolo tse ling, ebe u netefatsa khanyetso ea ho ikopanya.
3. Ho Omisa Likhoele:{1}}Beha karolo e sebetsang e kopaneng (core + windings) ka har'a ontong ea ho omisa bakeng sa ho futhumatsa vacuum ho tlosa mongobo le ho netefatsa boits'oaro ba ho kenya letsoho.
4. Ho Beha Tanka:Kenya karolo e omisitsoeng e sebetsang ka har'a tanka 'me u e sireletse ka liboutu.
5. Kenyelletso ea lisebelisoa:Mount bushings, IFD, valve ea liphallelo, le lisebelisoa tse ling, ho tiisa manonyeletso ohle.
6. Ho Tlatsa le ho Tiisa Oli:Vacuum-tlatsa oli e sireletsang hore e fihle boemong bo itseng, ebe u leka boleng ba oli le ho tiea ha tanka ka mor'a hore e be teng.
03 Teko
|
Che. |
Ntho ea Teko |
Yuniti |
Melao ea ho Amohela |
Litekanyetso Tse Lekanyelitsoeng |
Qetello |
|
1 |
Litekanyo tsa ho hanyetsa |
/ |
/ |
/ |
Feta |
|
2 |
Liteko tsa Karolelano |
/ |
Phapang ea karo-karolelano ea motlakase ho theipi ea mantlha: Ka tlase ho kapa ho lekana le 0.5% Letšoao la khokahano: Ii6 |
-0.04 |
Feta |
|
3 |
Liteko tsa polarity |
/ |
Kekeletso |
Kekeletso |
Feta |
|
4 |
Ha ho{{0}tahlehelo ea thepa le thabo ea hona joale |
% |
I0 :: fana ka boleng bo lekantsoeng(100%) |
0.17 |
Feta |
|
kW |
P0: fana ka boleng bo lekantsoeng(100%) |
0.161 |
|||
|
% |
I0 :: fana ka boleng bo lekantsoeng(105%) |
0.33 |
|||
|
kW |
P0: fana ka boleng bo lekantsoeng(105%) |
0.204 |
|||
|
/ |
mamello ea ho se lahleheloe ke moroalo ke +15% |
/ |
|||
|
5 |
Litahlehelo tsa meroalo, motlakase oa impedance, tahlehelo e felletseng le katleho |
/ |
T:85 likhato mamello bakeng sa impedance ke ± 7.5% mamello ea tahlehelo ea boima kaofela ke +8% |
/ |
Feta |
|
% |
Z%: boleng bo lekantsoeng |
3.16 |
|||
|
kW |
Pk: boleng bo lekantsoeng |
1.377 |
|||
|
kW |
Pt: boleng bo lekantsoeng |
1.538 |
|||
|
% |
Katleho e seng ka tlase ho 98.94% |
99.07 |
|||
|
6 |
Teko ea Voltage e sebelisitsoeng |
/ |
LV: 10kV 60s |
Ha ho ho putlama ha motlakase oa liteko |
Feta |
|
7 |
Teko ea ho mamella Voltage e kentsoeng |
/ |
Matla a sebelisoang (KV): 2Ur |
Ha ho ho putlama ha motlakase oa liteko |
Feta |
|
Nako:48 |
|||||
|
Hangata (HZ): 150 |
|||||
|
8 |
Tekanyo ea ho hanyetsa Insulation |
GΩ |
LV-HV ho ea fatše |
43.3 |
Feta |
|
9 |
Leakage Test |
/ |
Khatello e sebelisitsoeng: 20kPA |
Ha ho na leakage le che Tšenyo |
Feta |
|
Nako:12h |
|||||
|
10 |
Tlhahlobo ea oli |
kV |
Matla a Dielectric |
57.4 |
Feta |
|
mg/kg |
Mongobo |
9.3 |
|||
|
% |
Ntho ea ho senya |
0.00254 |
|||
|
mg/kg |
Furan Analysis |
0.03 |
|||
|
/ |
Tlhahlobo ea Khase ea Chromatography |
/ |


04 Ho paka le ho Romela
4.1 Ho paka
The single{0}phase pole-transformer mounted e pakiloe ka har'a kreiti ea lepolanka e thibelang ho bola{2}, e sirelelitsoeng ka hare e kentsoeng ka liboutu le -litlapa tsa rabara tse monyang, 'me likarolo tse robehang li sirelelitsoe ka foam. Kreiti e phuthetsoe ka lesela le thibelang pula ea UV-, le tlanngoe ka likhoele tsa nylon, 'me meroko ea koaloa. Likoti tsa moea li kenyelelitsoe holimo. Sephutheloana se na le matšoao a ho phahamisa, li-desiccants, le mokotla oa litokomane tse sa keneleng metsi, tse netefatsang hore li loketse lipalangoang tsa leoatle le kantle.

4.2 Ho tsamaisa thepa

Ho ea ka melao ea CIF, morekisi o tsamaisa{0}li-transformer ka sekepe ho ea Montreal Port, Canada, ho lefella litšenyehelo, inshorense ea metsing le thepa. Li-transformer li kentsoe ka mokhoa o sireletsehileng (liforeimi tsa lehong/tšepe) 'me li romelloa ka thepa ea leoatleng (sekontiri kapa breakbulk), ka inshorense ea All Risks. Ha a fihla, moreki o sebetsana le tumello ea lekhetho le thepa ea ho qetela ea literaka. Litokomane tsa bohlokoa li kenyelletsa B / L, invoice ea khoebo, lenane la ho paka, le setifikeiti sa inshorense. Mathata a kenyeletsa tšireletso ea leholimo ea mariha le tieho ea meetlo.
05 Sebaka le Kakaretso
Pole{{0}motlakase oa li-transformer o fana ka tharollo e kopanetsoeng,{1}}e sebetsang hantle, le e tšepahalang bakeng sa kabo ea motlakase libakeng tsa litoropo le tsa mahaeng. E etselitsoe ho tšoarella le ho kenya habonolo, li netefatsa phetoho e sebetsang ea motlakase ka tlhokomelo e fokolang. Ebang ke lits'ebeletso, lits'ebetso tsa indasteri, kapa ho kopanya matla a ka nchafatsoang, li-transformer tsa rona li fihlella maemo a machaba (IEEE, IEC, CSA) 'me li hahiloe tikolohong e thata. Ikopanye le rona kajeno bakeng sa litharollo tse ikhethileng tse lumellanang le litlhoko tsa gridi ea hau.

Hot Tags: pole mount transformer, moetsi, mofani oa thepa, theko, litšenyehelo
You Might Also Like
150 kVA Pmt Transformer-19.92 / 0.24 * 0.12 kV|Canad...
500 kVA Pole Transformer-4.16 / 0.6 kV|Canada 2024
50 kVA Transformer On Power Pole-7.97/0.12/0.24 kV|C...
50 kVA Transformer On Power Line-7.97/0.277 kV|Canad...
100 kVA Pole ea Transformer Mounted-13.8 / 0.24 kV|G...
50 kVA Single Phase Pole Mounted Distribution Transf...
Romela Inquiry