500 kVA Pad Mount Transformer-24 * 13.8 * 12 / 0.416 * 0.24 kV|Jamaica 2025
Matla: 500kVA
Matla: 24GrdY/13.8*13.8D*12GrdY/6.9-0.416Y/0.24*0.24/0.12kV
Feature: e nang le switch ea li-voltage tse peli

Ho Tloha ho Likaroloana ho ea ho Smart Cities – Pad-Mounted Transformers E Boloka Matla a Phaphallang.
01 Kakaretso
1.1 Tlhaloso ea Morero
500 kVA pad mounted transformer e ile ea isoa Jamaica ka 2025. Matla a lekantsoeng a transformer ke 500 kVA e nang le pholiso ea ONAN. Motlakase oa mantlha ke 24/13.8 * 13.8D * 12/6.9 kV e nang le ± 2 * 2.5% tapping range (NLTC), motlakase oa bobeli ke 0.416 / 0.24 * 0.24D / 0.12 kV, ba thehile lihlopha tsa vector tsa YNyn0 le YNd11.
The pad-mounted transformer ke tharollo e kopanetsoeng, e kentsoeng ka botlalo ea kabo ea motlakase e etselitsoeng ho ts'epahala, polokeho, le ts'ebetso e ntle libakeng tsa litoropo le indasteri. E etselitsoe hore e kopanngoe ka mokhoa o sa tsitsang ho li-grid tsa sejoale-joale, e na le-circuit changer le dual voltage switch bakeng sa ts'ebetso e feto-fetohang, e lumellang ho lokisoa ha motlakase habonolo ntle le ho sitisa litšebeletso.
Bakeng sa tshireletso e matlafaditsweng, yuniti e kenyeletsa dintho tse thibelang sekgono le -lihokelo tsa ho robeha elbow, tse netefatsang ho kgaolwa ho bolokehile le kgatello ya surge. Phepelo-ka ho kenya e thusa ho laola likhebula hantle, ha tlhahlobo e tsoetseng pele e fanoa ka themometara ea oli, mokelikeli oa boemo ba mokelikeli, le vacuum gauge bakeng sa tlhahlobo ea nako ea sebele-.
Polokeho e etelletsoa pele ka Bay-O-Fuse ea Net le li-fuse tsa hona joale- tse fokotsang ho thibela ho tlala, hammoho le switch break break bakeng sa ho itšehla thajana nakong ea tlhokomelo. E hahiloe hore e sebetsane le maemo a thata, transformer ena e fana ka ts'ebetso e tšepahalang ka tlhokomelo e fokolang-e loketseng lits'ebeletso, lits'ebetso tsa khoebo, le lisebelisoa tsa motlakase tse ka nchafalitsoeng.
1.2 Tlhaloso ea Setsebi
500 kVA substation transformer specifications type le data sheet
|
E fetisetsoa ho
Amerika
|
|
Selemo
2025
|
|
Mofuta
Substation ea motlakase
|
|
Standard
IEEE Std C57.12.34-2022
|
|
Rated Power
500 kVA
|
|
Khafetsa
50HZ
|
|
Mokhahlelo
3
|
|
Mofuta oa ho Pholisa
ONA
|
|
Voltage ea mantlha
24/13.8*13.8D*12/6.9 kV
|
|
Motlakase oa bobeli
0.416/0.24 * 0.24D/0.12 kV
|
|
Lintho Tse Hlahang
Koporo
|
|
Angular displacement
YNyn0, YNd11
|
|
Tšitiso
5%
|
|
Tlanya Changer
NLTC
|
|
Tlanya Range
±2*2.5%
|
|
Ha ho Tahlehelo ea Mojaro
Ka tlase ho kapa ho lekana le 0.767kW
|
|
Ho Lahleheloa ke Moroalo
Ka tlase ho kapa ho lekana le 7.2kW
|
1.3 Litšoantšo
500 kVA sets'oants'o sa sets'oants'o sa sets'oants'o se senyane sa 500 kVA le boholo.
![]() |
![]() |
02 Tlhahiso
2.1 Ntlha ea bohlokoa
Transformer e na le-mokotla oa tšepe o koaletsoeng ka bokhabane o phahameng o entsoeng ka lijo-thollo tse phahameng- tse entsoeng ka silicon steel laminations. Lamination e 'ngoe le e 'ngoe e entsoe ka leseare-e khaotsoe ka mohato o hokahaneng-manonyello a lirope ho fokotsa ho lutla ha makenete le ho fokotsa{5}tahlehelo ea thepa. Bohareng bo koahetsoe ka insulating oxide layer ho thibela maqhubu a metsi, ha moralo oa eona o kopaneng o matlafatsa botsitso ba mochini le ho theola lerata le utloang{7}haholo bakeng sa ho kenya litoropong. E khabisitsoe ka thata bakeng sa ho kenella ka matla ha makenete, konokono ena e netefatsa phetisetso ea matla e thellang ho li-setting tse peli tsa motlakase, e boloka ts'ebetso e ntle leha e le tlas'a meroalo e feto-fetohang.

2.2 Ho tsubella

Mokokotlo oa LV o sebelisa mohala oa koporo, o netefatsa hore o ajoa ka mokhoa o ts'oanang, o monyane-oa ho thibela potoloho, le mokhoa o matla oa ho qhala mocheso. Ho sa le joalo, matsoelintsoeke a HV layer a amohela li-conductors tsa koporo tse sirelelitsoeng ka har'a li-dielectric discs, tse nang le pampiri ea kraft e kentsoeng bakeng sa matla a matla a dielectric. Mekhoa ea phetoho e sebelisoa ho fokotsa tahlehelo ea li-eddy, ha li-axial le radial cooling ducts li ntlafatsa tsamaiso ea mocheso.
2.3 Tanka
Tanka ea transfoma ke sebaka se thata, se sa jeng{0}}se nang le mabota a masenke a 3D bakeng sa katoloso ea oli le mapheoana a ho pholisa a kopantsoeng bakeng sa ho qhala mocheso. Ka moaho o kentsoeng ka litšepe, o lekotsoeng ka radiographical, o kenyelletsa -li-cable ports tse entsoeng pele tse nang le li-grounding bosss, 'me tse hahelletsoeng-in lifting/forklift points. Ka hare ho na le li-baffle plates bakeng sa phallo e nepahetseng ea oli, athe UV-pente e sa khoneng ea epoxy e tiisa hore e tšoarella nako e telele libakeng tse kantle.

2.4 Kopano ea ho Qetela

Kopano ea ho qetela ea pad-transformer e kentsoeng e kopanya core-coil assembly, tanki, le lisebelisoa hore e be sistimi e kopaneng. The dry core-uniting winding unit e theoleloa ka hloko ka har'a tanka ea tšepe e sa jeng{4}, 'me e lateloe ke ho kenya lihlahla, mapheoana a pholisang le likarolo tsa ho laola. Mehato ea bohlokoa e kenyelletsa:
• Ho tlatsoa ha oli ka tlas'a vacuum bakeng sa ho kenngoa ka ho feletseng
• Ho tsamaisana le metjhini ea li-switches tsa khefu ea mojaro le likhokahanyo tsa thapo
• Tekolo ea ts'ebetso ea lisebelisoa tsohle tsa ho beha leihlo (li-gauge, lialamo)
03 Teko
|
Che. |
Ntho ea Teko |
Yuniti |
Melao ea ho Amohela |
Litekanyetso Tse Lekanyelitsoeng |
Qetello |
|
1 |
Litekanyo tsa ho hanyetsa |
% |
Sekhahla se phahameng sa ho hanyetsa ho se leka-lekane |
0.76 |
Feta |
|
2 |
Liteko tsa karo-karolelano |
% |
Phapang ea karo-karolelano ea motlakase ho theipi ea mantlha: Ka tlase ho kapa ho lekana le ± 0.5% Letšoao la khokahanyo: YNyn0/YNd11 |
0.14% ~ 0.15% |
Feta |
|
3 |
Liteko tsa likamano tsa mohato- |
/ |
YNyn0/YNd11 |
YNyn0/YNd11 |
Feta |
|
4 |
Ha ho{{0}tahlehelo ea thepa le thabo ea hona joale |
% kW |
I0 :: fana ka boleng bo lekantsoeng P0: fana ka boleng bo lekantsoeng mamello ea ho se lahleheloe ke moroalo ke +0% |
0.59% 0.7535 |
Feta |
|
5 |
Litahlehelo tsa tahlehelo ea matla a motlakase le katleho |
% kW kW |
T:85 likhato mamello bakeng sa impedance ke ± 7.5% mamello ea tahlehelo ea boima kaofela ke +0% |
/ |
Feta |
|
Z%: boleng bo lekantsoeng |
5.02% |
||||
|
Pk: boleng bo lekantsoeng |
6.649kW |
||||
|
Pt: boleng bo lekantsoeng |
7.4025kW |
||||
|
Katleho e seng ka tlase ho 99.05% |
99.10% |
||||
|
6 |
Teko ea Voltage e sebelisitsoeng |
kV |
HV: 40kV 60s LV: 10kV 60s |
Ha ho ho putlama ha motlakase oa liteko |
Feta |
|
7 |
Teko ea ho mamella Voltage e kentsoeng |
kV |
Matla a sebelisoang (KV): 2Ur |
Ha ho ho putlama ha motlakase oa liteko |
Feta |
|
Nako:40 |
|||||
|
Hangata (HZ): 150 |
|||||
|
8 |
Leakage Test |
kPa |
Khatello e sebelisitsoeng: 20kPA Nako: 12h |
Ha ho na leakage le che Tšenyo |
Feta |
|
9 |
Tekanyo ea ho hanyetsa Insulation |
GΩ |
HV{{0}LV ho ea fatše : |
11.0 |
/ |
|
LV-HV ho ea fatše: |
9.51 |
||||
|
HV&LV ho ea fatše: |
20.1 |
||||
|
10 |
Teko ea Dielectric ea Oli |
kV |
E kholo ho feta kapa e lekana le 45 |
58.6 |
Feta |


04 Ho paka le ho Romela
4.1 Ho paka
Transformer ena e kentsoeng ka holim'a lepheo e kenngoa ka ho qala ka ho beha mokoloko oa mokotla oa tin foil holim'a terei ea transformer le ho koahela transformer ka mokotla oa tin foil. Ha ho tiisa mokotla oa tin foil, ho lokela ho siuoa ho buleha, moo ho sebelisoang mochine o hloekisang ho ntša khase, ebe monyetla o koaloa ka mochine o tiisang. Ho sa le joalo, desiccant e kenngoa ka har'a sephutheloana ho thibela mafome. Ka mor'a ho hloekisa, litšireletseho tsa sekhutlo tse entsoeng ka foam, polasetiki, kapa karete (basireletsi ba khethehileng ba k'honeng ba hatelitsoeng ka khateboto) ba kenngoa ho pota-pota transformer, e ntan'o phutheloa ka filimi e sireletsang. Qetellong, e kenngoa ka lebokoseng la lepolanka, leo ho lona ho lokelang ho fafatsoa matšoao a forklift le setsi sa matla a khoheli.

4.2 Ho tsamaisa thepa

Phedi ena-e tla romelwa ho ya ka dipehelo tsa FOB (Free On Board), mme morekisi o na le boikarabelo ba ho isa thepa Boemakepeng ba Yiwu le ho qeta ho kenya thepa sekepeng. Beng le ho fetisetsa kotsi ho moreki hang ha thepa e feta seporo sa sekepe ho Yiwu Port. Thepa e latelang ea leoatle le thomello ea ho qetela ho ea Jamaica e tla hlophisoa ke moreki. Nakong ea lipalangoang, thepa e tlameha ho tlamelloa ka mokhoa o sireletsehileng ho thibela ho sisinyeha le mongobo, ka lethathamo le felletseng la liphutheloana le litokomane tse tsoang kantle ho naha tse fanoeng bakeng sa tumello ea lekhetho.
05 Sebaka le Kakaretso
Ka bokhabane bo holimo, moralo o kopaneng, le ho tšoarella ka nako e telele, Pad ena-Mounted Transformer ke khetho e nepahetseng bakeng sa litsamaiso tsa motlakase tsa indasteri, tsa khoebo le tsa sechaba. E entsoe ka tumellano e tiileng le litekanyetso tsa machaba, setsi se seng le se seng se tiisa ts'ebetso e phahameng le polokeho. Hore na o hloka kabo ea motlakase e tšepahalang kapa tharollo e ikhethileng bakeng sa maemo a thata, sehlopha sa rona se ikemiselitse ho fana ka tšehetso ea litsebi. Ikopanye le rona kajeno bakeng sa lintlha tse qaqileng kapa litšebeletso tse lokiselitsoeng{4}re ikemiselitse ho fana ka litharollo tsa motlakase tse tsitsitseng le tse sebetsang hantle bakeng sa litlhoko tsa hau!

Hot Tags: 500 kva pad mount transformer, moetsi, mofani oa thepa, theko, litšenyehelo
You Might Also Like
300 kVA Oli e Tlatsang Transformer-13.2 / 0.48 kV|Gu...
500 kVA Pad Mounted Transformer Theko-22.86/0.208 kV...
1500 kVA Pad Mounted Transformer-34.5/0.48 kV|Sebeli...
1000 kVA Pad Mounted Transformer List-13.8/0.415 kV|...
1500 kVA Pad Mounted Transformer Price-23.9/0.416 Kv...
500 kVA Three Phase Distribution Transformer-4.16/0....
Romela Inquiry