500 KVA Radial Feed Transformer-12.47 * 4.16/0.6 KV|Canada 2024

500 KVA Radial Feed Transformer-12.47 * 4.16/0.6 KV|Canada 2024

Naha ea thomello: Canada 2024
Matla: 500kVA
Matla: 12.47Grdy/7.2 X 4.16Grdy/2.4-0.6y/0.347 kV
Tšobotsi: Ka IFD
Romela Inquiry

 

500 kVA Radial Feed Transformer

{{0}e sebetsang hantle haholo 500 kVA Radial Feed Transformer bakeng sa kabo ea motlakase e tšepahalang le e kopaneng

 

 

01 Kakaretso

1.1 Tlhaloso ea Morero

Ka 2024, moreki oa Canada o ile a fumana 500 kVA{2}}phase three phase-mounted transformer ho tsoa Scotech. Transformer e entsoe le ho etsoa ho latela CSA Standard C227.4:21. Sehlopha ke sa ho kenya ka ntle holim'a letlapa la konkreite. E fana ka tharollo e kopanetsoeng le e bolokehileng bakeng sa kabo ea matla a bolulo le khoebo.

Sena ke 500 kVAradial feed transformer e sebelisa pholiso ea ONAN le oli ea diminerale bakeng sa ho kenya letsoho. Maqhubu a aluminium a fana ka tekanyo e ntle ea ts'ebetso, boima le litšenyehelo. E na le 500 kVA, 60 Hz, e nang le motlakase oa mantlha oa 12.47 / 4.16 kV le motlakase oa bobeli oa 0.6 kV, o hlophisitsoeng ka sehlopha sa YNyn0 vector.

Yuniti e etselitsoe marang-rang a phepelo ea radial, a fanang ka matla ka tsela e le 'ngoe ho tloha seteisheneng ho ea ho moreki. Lisebelisoa tsa mahlaseli li bonolo, -li sebetsa hantle, 'me li loketse libaka tseo botšepehi bo ka laoloang ka li-switches tsa ho arola likarolo.

Ho lumella taolo ea motlakase e feto-fetohang, transformer e na le-load tap changer (NLTC), e fanang ka sebaka sa ±2×2.5%. E fihlela katleho ea 99.05%, e se nang-tahlehelo ea mojaro Ka tlase kapa ho lekana le 1090 W le tahlehelo ea thepa Ka tlase kapa ho lekana le 5800 W. E hahiloe hore e tšoarelle nako e telele, e tla le lisebelisoa tse lumellanang le CSA{9}}me e emela tharollo e tšepahalang bakeng sa marang-rang a phano ea Canada.

 

 

 

1.2 Tlhaloso ea Setsebi

Tlhaloso ea 500 kVA radial feed transformer le leqephe la data

E fetisetsoa ho
Canada
Selemo
2024
Mofuta
Transformer ea mekhahlelo e meraro
Standard
CSA C227.4:21
Rated Power
500KVA
Khafetsa
60HZ
Fepa
Radial
Pele
E shoeleng
Mokhahlelo
tharo
Mofuta oa ho Pholisa
ONA
Mokelikeli o thibelang metsi
Oli ea Liminerale
Voltage ea mantlha
12.47(4.16) kV
Motlakase oa bobeli
0.6 kV
Sehlopha sa Vector
YNyn0
Lintho Tse Hlahang
Aluminium
Tšitiso
5 %
Katleho
99.05%
Tlanya Changer
NLTC
Tlanya Range
±2*2.5%
Ha ho Tahlehelo ea Mojaro
Ka tlase ho kapa ho lekana le 1090 W
Ho Lahleheloa ke Moroalo
Ka tlase ho kapa ho lekana le 5800 W
Lisebelisoa
Tlhophiso e Tloaelehileng

 

1.3 Litšoantšo

500 kVA radial feed transformer e taka le nameplate

500 kVA Radial Feed Transformer drawing 500 kVA Radial Feed Transformer nameplate

 

 

02 Tlhahiso

2.1 Ntlha ea bohlokoa

Maoto a mahlano-a boloka matla a khoheli a leka-lekana ka mekhahlelo eohle e meraro. Moqapi ona o fokotsa phallo e khelohileng le tahlehelo. Konokono e sebelisa lishiti tsa tšepe tsa silicon tse 0.30-0.35 mm tse nang le matla a matla a khoheli le khanyetso e tlase. Sephetho ke ts'ebetso e ntle le lerata le tlase nakong ea ts'ebetso.

 

2.2 Ho tsubella

Transformer ena e na le lifensetere tsa aluminium. Likhoele li entsoe ka foil bakeng sa motlakase o tlase le terata bakeng sa motlakase o phahameng. Moralo ona o netefatsa phano e ts'oanang ea hajoale, e matla{2}}e thibelang potoloho ea potoloho, le ho pholisa hantle. Ka 5% impedance le 99.05% e sebetsang hantle, transformer ena e fana ka ts'ebetso e tsitsitseng le e sebetsang tlas'a maemo a sa tšoaneng a mojaro.

 

2.3 Tanka

500 kVA Radial Feed Transformer oil tank

Tanka ea tšepe e tiisitsoeng e bobebe-e nang le sekhurumetso sa bolt e sebelisoa bakeng sa 500 kVA radial feed transformer. E khona ho mamella khatello ea ka hare ea 50 kPa ntle le ho lutla kapa ho khopama ho fetang 0.25% ea boholo ba diagonal. Khabinete e hahiloe molemong oa ts'ebeliso ea kantle, e thibang-e hanana le maemo a leholimo{7}}e hanana le boemo ba leholimo, 'me e sirelelitsoe ka liboutu tsa pentahead joalo ka ha ho bonts'itsoe ho CSA C227.4.

 

2.4 Kopano ea ho Qetela

Re na le sehlopha sa kopano se koetlisitsoeng ka botsebi le se hlahlobiloeng ka thata, se tsoelang pele ho fetisa phihlelo ea bohlokoa ka-seseteme ea boithuto. Sebakeng sa tlhahiso, re kenya ts'ebetsong taolo ea ts'ebetso, ho netefatsa hore ts'ebetso e 'ngoe le e' ngoe ea kopano ea transformer e tlas'a taolotlhahlobo e akaretsang ea bolengle ho rekota lintlha tsa bohlokoa. Motsoako oa tlhaho oa ts'ebetso ea sehlopha sa litsebi le taolo ea taolo e tlase e netefatsa boleng bo ikhethang.

 

 

03 Ho etsa liteko

Teko ea Teko le Teko e Tloaelehileng

CSA C227.4-21

Mekhahlelo e meraro{0},pad-li-transformer tse phahamisitsoeng e nang le lihokelo tsa motlakase tse ka arohang{0}} tse phahameng

CSA-C802.1-13 (R2022)

Maemo a Tlatsi a Sebetsang bakeng sa Mokelikeli{{0}O Tlatsitse Li-Transformer tsa Phano

 

1. Litekanyo tsa ho hanyetsa
2. Karo-karolelano Liteko
3. Teko ea Kamano ea Phase
4. Ha ho Tahlehelo ea Mojaro 'me Ha ho na Mojaro Hona Joale
5. Litahlehelo tsa Load Impedans Voltage le Katleho
6. Teko ea Voltage e sebelisitsoeng
7. Induced Voltage E mamella Teko
8. Teko ea ho Lutla ka Khatello ea Li-transformers tse qoelitsoeng ka Metsi
9. Tekanyo ea ho hanyetsa Insulation
10. Teko ea Dielectric ea Oli
 

500 kVA Radial Feed Transformer testing
500 kVA Radial Feed Transformer Test

Liphetho tsa liteko

Che.

Ntho ea Teko

Yuniti

Kamohelo

Litekanyetso

Litekanyetso Tse Lekanyelitsoeng

Qetello

1

Litekanyo tsa ho hanyetsa

%

Sekhahla se phahameng sa ho hanyetsa ho se leka-lekane

1.17

Feta

2

Liteko tsa karo-karolelano

%

Phapang ea karo-karolelano ea motlakase ho theipi ea mantlha: Ka tlase ho kapa ho lekana le 0.5%

-0.03-0.10

Feta

3

diteko- tsa dikamano

/

YNyn0

YNyn0

Feta

4

Ha ho{{0}tahlehelo ea thepa le thabo ea hona joale

/

I0 :: fana ka boleng bo lekantsoeng

0.39%

Feta

P0: fana ka boleng bo lekantsoeng

0.7455kW

mamello ea ho se lahleheloe ke moroalo ke +10%

/

5

Litahlehelo tsa tahlehelo ea matla a motlakase le katleho

/

T:85 likhato

mamello bakeng sa impedance ke ± 7.5%

mamello ea tahlehelo ea boima kaofela ke +6%

/

Feta

Z%: boleng bo lekantsoeng

5.36%

Pk: boleng bo lekantsoeng

4.534kW

Pt: boleng bo lekantsoeng

5.312kW

Katleho e seng ka tlase ho 99.05%

99.28%

6

Teko ea Voltage e sebelisitsoeng

kV

LV: 10kV 60s

Ha ho ho putlama ha motlakase oa liteko

Feta

7

Teko ea ho mamella Voltage e kentsoeng

kV

Matla a sebelisoang (KV):

2 Ur

Ha ho ho putlama ha motlakase oa liteko

Feta

Nako:30

Hangata (HZ): 240

8

Leakage Test

kPa

Khatello e sebelisitsoeng: 20kPA

Nako: 12h

Ha ho na leakage le che

Tšenyo

Feta

9

Tekanyo ea ho hanyetsa Insulation

LV-HV ho ea fatše

6.3

/

HV&LV ho ea fatše

9.5

10

Tlhahlobo ea oli

/

Matla a Dielectric;

56.2 kv

Feta

Mongobo

11.9 mg / kg

Ntho ea ho senya

0.00342%

Furan Analysis

Ka tlase ho kapa ho lekana le 0.1

Tlhahlobo ea Khase ea Chromatography

/

 

 

04 Ho paka le ho Romela

500 kVA Radial Feed Transformer packing
500 kva radial feed transformer-export-packing
500 kVA Radial Feed Transformer shipping

 

05 Sebaka le Kakaretso

500 kva radial feed transformer-back-view

Transformer ena ea 500 kVA{1}}phase three-e hahiloeng bakeng sa Canada. E latela CSA C227.4:21 'me e etselitsoe kabo e sireletsehileng, e sebetsang hantle ea kantle ea motlakase. E na le compact pad{7}}moralo o kentsoeng 'me e sebetsa hantle libakeng tsa bolulo le tsa khoebo. Meetso ea-tlhano ea mantlha e boloka botsitso ba makenete le ho fokotsa lerata. Tanka ea tšepe e tiisitsoeng e matla, e mamella boemo ba leholimo, 'me ha e kenelle. Transformer e 'ngoe le e' ngoe e etsoa ke basebetsi ba nang le boiphihlelo tlas'a taolo e tiileng ea boleng. E sebetsa ka katleho ea 99.05%, tahlehelo e tlase, le motlakase o tsitsitseng. Ke khetho e tšoarellang le e tšepahalang bakeng sa litsamaiso tsa motlakase tsa Canada.

 

Hot Tags: Radial Feed Transformer, moetsi, mofani oa thepa, theko, litšenyehelo