1500 KVA Dry{1}}mofuta oa Transformers-6.6/0.55 KV|Afrika Boroa 2025

1500 KVA Dry{1}}mofuta oa Transformers-6.6/0.55 KV|Afrika Boroa 2025

Naha: Afrika Boroa 2025
Matla: 1500 kVA
Matla: 6.6/0.55 kV
Sebopeho: le balateli
Romela Inquiry

Jiangshan Scotech Electrical Co., Ltd ke e mong oa baetsi le barekisi ba tšepahalang ba 1500 kva dry{2}}mofuta oa li-transformer{7}}6.6/0.55 kv|Afrika Boroa 2025 Chaena. Ka kopo, ikutloe u lokolohile ho reka lihlahisoa tse baballang litšenyehelo tse rekisoang mona le ho fumana litšoantšo ho tsoa femeng ea rona. Ikopanye le rona bakeng sa lintlha tse ling.

 

dry-type transformers

Smart Distribution, Worry-Free Operation - Tšepa Cast Coil Dry Type Transformer ho lisebelisoa tsa morao-rao tsa motlakase.

 

 

01 Kakaretso

1.1 Tlhaloso ea Morero

1500kVA cast coil dry-type transformer e ile ea isoa Afrika Boroa ka 2025. Matla a lekantsoeng a transformer ke 1500 kVA e nang le AN/AF cooling. Motlakase oa mantlha ke 6.6 kV e nang le ± 2 * 2.5% tapping range (NLTC), motlakase oa bobeli ke 0.55 kV, ba thehile sehlopha sa vector sa Dyn11.

Li-transformer tsa rona tsa Cast Coil dry{0}} li emela sehlohlolo sa polokeho, ts'epahalo, le bokhoni ba kabo ea motlakase ea sejoale-joale. E entsoe ka epoxy resin-e kentsoeng ka li-coil tse phahameng-ea motlakase, ha e na oli{4}}ka ho feletseng, e etsa hore e be khetho e nepahetseng, ea tlhokomelo{5}} bakeng sa ho kenya ka tlung moo polokeho ea mollo le tšireletso ea tikoloho e leng tsona tsa bohlokoa.

Karolo e ka sehloohong ea transformer ena ke mokhoa oa eona oa ho futhumatsa oa fan ea bohlale (WTB). Seseteme ena e beha leihlo mocheso oa ts'ebetso 'me ka bo eona e kenya tšebetsong{1}} li-fan axial tse sebetsang hantle ha ho hlokahala. Pholiso ena e qobelletsoeng{{3}ea moea o pholileng e matlafatsa matla a mocheso oa transformer haholo 'me e eketsa bokhoni ba eona ba nako e khutšoanyane- ea ho tlala ho tlōla, ho netefatsa hore ts'ebetso e tsitsitse le e tsoelang pele le tlas'a maemo a boima kapa a feto-fetohang.

E etselitsoe lits'ebetso tse fapaneng tsa lefats'e, yuniti ena e sebetsa ka motlakase o tloaelehileng oa 220V. Kaho ea eona e kopaneng le e matla, e kopantsoeng le theknoloji ea coil ea cast resin, e fana ka khanyetso e ikhethang ho mongobo, lerōle le tikoloho e senyang. Sena se etsa hore e be e loketseng hantle bakeng sa mefuta e mengata ea maemo a bohlokoa, ho kenyelletsa:

  • Mehaho ea Khoebo le ea Sechaba:Litsi tsa mabenkele, lipetlele, boemafofane, le{0}libaka tse phahameng haholo.
  • Lisebelisoa tsa Indasteri:Limela tsa tlhahiso, mehala ea tlhahiso, le likarolo tsa ts'ebetso ea lik'hemik'hale.
  • Meralo le Merero e Ikhethileng:Sistimi ea metro, lithanele, likepe, le sethala sa kantle ho naha.
  • Kopanyo ea Matla a Tsosolositsoeng:Mekhoa ea ho fehla matla a moea le letsatsi.

 

 

 

1.2 Tlhaloso ea Setsebi

1500 kVA cast coil dry-tlhahiso ea li-transformer le leqephe la data

E fetisetsoa ho
Afrika Boroa
Selemo
2025
Mofuta
mofuta o omileng oa transformer
Lintho tsa mantlha
Letlapa la tšepe la silicon le entsoeng ka lijo-thollo
Standard
IEC60076
Rated Power
1500kVA
Khafetsa
50HZ
Sehlopha sa Vector
Dyn11
Mokhahlelo
3
Mofuta oa ho Pholisa
AN/AF
Voltage ea mantlha
6.6kV
Motlakase oa bobeli
0.55kV
Lintho Tse Hlahang
Koporo
Tšitiso
6%
Tlanya Changer
NLTC
Tlanya Range
±2*2.5%@lehlakoreng la mathomo
Ha ho Tahlehelo ea Mojaro
2.45KW
Ho Lahleheloa ke Moroalo
11.73KW
Mabone a mantlha a mamellang voltage primary side (BIL)
60kV
Maqhubu a Matla a mamellang -karolo ea mantlha
20kV
Power Frequency e mamella voltage{0}}ka lehlakoreng la bobeli
3kV
Mocheso o tsoileng matsoho o nyoloha@ boemo ba tšebeletso bo lekantsoeng
100K
Boemo ba insulation
F

 

1.3 Litšoantšo

1500 kVA cast resin dry-mofuta oa sethalo sa setaele sa li-transformer le boholo.

dry-type transformers diagram

 

 

02 Tlhahiso

2.1 Ho tsubella

dry-type transformers winding

Bohareng ba "cast coil dry"-mofuta oa li-transformer ke mochini oa eona o entsoeng ka bokhabane, o sebelisa mapheo a koporo a phahameng- a koaletsoeng ka botlalo ka mokhoa oa "vacuum casting" o nang le premium{2}grade epoxy resin. Encapsulation ena e tsoetseng pele e theha 'mele o se nang moroallo, o tiileng o pota-potileng li-conductors tsa koporo, o theha sebopeho se le seng, se matla, le se se nang letho{4}}. Epoxy resin ha e fane feela ka matla a ikhethang a dielectric le ho hanyetsa ho tsoa ka mokhoa o sa fellang empa e boetse e tiisa hore ho na le conductivity e phahameng ea mocheso, ka katleho e ntša mocheso ho tloha mapheong. Mohaho ona o fella ka khoele e hanyetsanang haholo le mongobo, lerole, lik'hemik'hale le maemo a thata a tikoloho, e netefatsang{7}}botsitso, polokeho le tlhokomelo{8}ntle le ts'ebetso ea nako e telele.

 

2.2 Selaoli sa Mocheso

Selaola mocheso bakeng sa li-transformer tsa mofuta oa cast coil dry type tse hahiloeng-ka PT100 probes ka mekhahlelo e meraro-ea matsoelineng a mekhahlelo e meraro ho hlokomela{3}}nako ea sebele ea mocheso le ho li hlahisa skrineng sa dijithale. E fana ka mokhoa oa ho itlhahloba le-ho itlhahloba ka lialamo, le -mehato e meraro ea likarabo tsa mocheso: ho ikemela ka mokhoa o itekanetseng oa ho fehla moea mohatong oa pele, alamo{7}}ea mocheso o phahameng lekhetlong la bobeli, le leeto la boraro. Mesebetsi e meng e kenyelletsa taolo ea matsoho / koloi ea fan, ho qala / ho emisa fan ka nako, ho rengoa ha data ea nalane le tlhahiso, 'me e sebetsa ho matla a 220V.

Temperature Controller

 

2.3 Fans

fans

Li-fan tse pholileng bakeng sa transformer ea mofuta o omileng oa coil li behiloe ka tlase ho yuniti. Nako ea ho qala kapa ea ho emisa e laolloa ka bo eona ke selaoli sa mocheso oa transformer, se se sebelisang ho ipapisitse le-data ea 'nete ea nako e etsang hore mocheso o fetele pele ho matlafatsa phallo ea mocheso. E sebetsa ka motlakase oa 220V mme e fanoe e le lotho e le 'ngoe e feletseng, libapali tsena li phetha karolo ea bohlokoa ho boloka maemo a matle a mocheso, ho thibela ho futhumala, le ho netefatsa ts'ebetso e tsitsitseng, e tsoelang pele ea transformer.

 

2.4 Letlapa la mabitso

Letlapa la lebitso la transformer le fana ka boitsebiso ba bohlokoa ba botekgeniki. E bonts'a ka ho sa feleng moetsi, mohlala, nomoro ea serial, le lintlha tsa kVA, hammoho le lintlha tsa mantlha tsa motlakase joalo ka voltages, frequency, vector group, le impedance. Litemoso tse hlokehang tsa polokeho le matšoao a setifikeiti (mohlala, IEC) le tsona li kenyelelitsoe, li sebetsa e le tšupiso ea bohlokoa bakeng sa ho kenya, ho sebetsa, le ho latela bophelo bohle ba eona ba ts'ebeletso.

dry type transformer nameplate

 

 

03 Ho etsa liteko

Tekanyo ea Nako e Khutšoane-Ho Sefuba ha Potoloho le Ho Lahleheloa ke Moroalo ke teko ea bohlokoahali e etsoang ka nako e khuts'oane-ho potoloha mapheo a bobeli le ho sebelisa motlakase o fokotsehileng ka lebelo le rehelletsoeng ho ea pele. Teko ena e fana ka khetho e nepahetseng ea phepelo e lekanang ea transformer, paramente ea bohlokoa bakeng sa ho bala taolo ea motlakase le maqhubu a ka bang teng a fosahetseng. Ka nako e ts'oanang, e lekanya kakaretso ea tahlehelo ea mojaro (haholo-holo tahlehelo ea koporo ka lebaka la ho hanyetsa mapheo), e leng ntho ea bohlokoa bakeng sa ho netefatsa katleho ea moralo, ho etsa bonnete ba ho lumellana le litlhaloso, le ho bolela esale pele ts'ebetso ea ts'ebetso le ho phahama ha mocheso tlas'a mojaro.

 Measurement of Short-Circuit Impedance
Short-Circuit Impedance test

 

 

04 Ho paka le ho Romela

4.1 Ho paka

packaging of cast coil dry type transformers

Sephutheloana sa li-transformer tsa mofuta oa cast coil dry dry li sebelisa mongobo{{0}ho phuthela filimi e kopantseng le liphalete tsa lepolanka kapa likhese tsa lehong tse tiisitsoeng, tse nang le ts'oenyeho e kahare-e monyang litšepe ho fokotsa mathata a lipalangoang. Matshwao a hlakileng a thomello, ditemoso tsa ho sebetsa, le ditlhahiso tsa sehlahiswa di ngodilwe ka ntle. Sephutheloana sena se latela litekanyetso tsa lipalangoang tsa machabeng, ho netefatsa hore transformer e lula e sirelelitsoe ebile e tiile nakong ea likepe tsa naha kapa tsa leoatle.

 

4.2 Ho tsamaisa thepa

Transformer ea mofuta oa cast coil dry dry e tsamaisoa ka thepa ea leoatleng tlas'a maemo a CIF (Litšenyehelo, Inshorense le Thepa) ho ea Boema-kepeng ba Durban, moo morekisi a jarang boikarabelo ba ho lefella thepa ea maoatle, inshorense ea thepa, le litšenyehelo tsa thomello boema-kepeng boo u eang ho bona. E sirelelitsoe ka har'a mongobo{{1}sephutheloana, sephutheloana se sa tsitsang{2}}ho lumellana le maemo a machaba a maoatle, transformer e sirelelitsoe khahlanong le mongobo, tšusumetso le tšenyo ea lipalangoang, ho netefatsa hore e fihla e ntse e le 'me e loketse ho sebelisoa ha e fihla boema-kepeng ba Durban.

sea freight under CIF terms

 

 

05 Sebaka le Kakaretso

SCOTECH li-transformer tsa mofuta oa coil dry dry li na le mosireletsi, polokeho le tlhokomelo{{0}ts'ebetso ea mahala, e loketseng maemo a indasteri, a khoebo le a macha a tšehetsang matla. E entsoe ka ho latela melao ea IEC, e fana ka ts'ebetso e tsitsitseng le e ts'epahalang bakeng sa ho tšoenyeha-phepelo ea motlakase mahala. Re labalabela ho sebelisana le uena bakeng sa tharollo e sebetsang ea kabo ea motlakase.

IEC standards dry transformer

 

Hot Tags: omile{{0}mofuta oa li-transformer, moetsi, morekisi, theko, litšenyehelo