75 kVA Pole Mounted Transformer-7.97/0.12/0.24 kV|Canada 2024

75 kVA Pole Mounted Transformer-7.97/0.12/0.24 kV|Canada 2024

Naha ea thomello: Canada 2024
Matla: 75kVA
Matla: 7.97/13.8Y-0.12(0.24)kV
Tšobotsi: ntle le ;changer ea theipi ea load
Romela Inquiry

 

 

75 kva pole mounted transformer-front-view

Scotech 75 kVA pole mounted transformer - matla a sebetsang hantle, a sebetsang hantle, le a tshepehang bakeng sa marangrang a sejoale-joale a phanoang.

 

01 Kakaretso

1.1 Tlhaloso ea Morero

Li-transformer tsena tsa 75 kVA -tse phahamisitsoeng ka lipalo tse entsoeng ke Scotech.Li-transformer{{0}tse palamisitsoeng ka polatheola{{0}motlakase o matla oa motlakase ho ea maemong a loketseng malapa le likhoebo tse nyane, ho netefatsa phepelo e tsitsitseng ea motlakase litoropong le mahaeng. Li-transformer tsena li romelloa Canada, li lumellana ka botlalo le litekanyetso tsa IEEE C57.12.20 le ho finyella litlhoko tsa morao-rao tsa tšebeliso ea matla a matla.

Taelo e kenyelletsa likarolo tse 8 tsa transformer ea 75 kVA. Yuniti ka 'ngoe e etselitsoe motlakase o phahameng oa 7.97/13.8Y kV le motlakase o tlase oa 120/240 V mokhahlelo{7}. E na le lihlahla tse peli tse phahameng tsa motlakase le lihlahla tse tharo tse tlase tsa motlakase, transformer e netefatsa ts'ebeletso e tšepahalang bakeng sa lits'ebetso tsa khoebo tsa bolulo le tse bobebe.

Transformer e fana ka libaka tse 'ne tsa ho penya ka lehlakoreng le phahameng la voltage e nang le mefuta e mengata ea ± 2 × 2.5%, e fanang ka lisebelisoa tse bonolo ho fetola motlakase ho latela maemo a mohala.

Ka tekanyo ea ho se sebetse hantle ea 2.1%, -tahlehelo e se nang moroalo oa 0.148 kW, le tahlehelo ea boima ba 0.675 kW, e bonts'a ts'ebetso e phahameng ea ts'ebetso le tahlehelo e tlase ea ts'ebetso. E sebelisa ONAN cooling, aluminium windings, le additive polarity, e etselitsoeng boholo bo kopanetsoeng le ho kenya poleiti e bonolo{5}}.

Transformer e boetse e na le mookameli oa surge arrester, e lumellang ho kopanngoa ha lisebelisoa tse sireletsang bakeng sa ts'ireletso e ntlafetseng le ho tšepahala ho marang-rang a kabo.

 

 

1.2 Tlhaloso ea Setsebi

Tlhaloso ea 75kVA pole mounted transformer le data sheet

E fetisetsoa ho
Canada
Selemo
2024
Mofuta
Single phase pole mounted transformer
Standard
IEEE C57.12.20
Rated Power
75 kVA
Khafetsa
60HZ
Polarity
Keketso
Sehlopha sa Vector
Ii6
Voltage ea mantlha
7.97/13.8Y kV
Motlakase oa bobeli
120/240V
Lintho Tse Hlahang
Aluminium
Tšitiso
2.1%
Mokhoa oa ho Pholisa
ONA
Tlanya Changer
NLTC
Tlanya Range
±2X2.5%
Ha ho Tahlehelo ea Mojaro
0.148 kW
Ho Lahleheloa ke Moroalo
0.675 kW
Lisebelisoa
Mookameli oa surge arrester

 

1.3 Litšoantšo

75kVA poleiti e pentiloeng ka transformer le lebitsoplate

75 kva pole mounted transformer-outline-drawing 75 kva pole mounted transformer-nameplate

 

 

02 Tlhahiso

2.1 Ntlha ea bohlokoa

75 kVA -phase pole{2}} li-transformer tse kentsoengsebelisa{0}lisebelisoa tsa tšepe tsa silicon tsa boleng bo holimo. Silicon steel ke lisebelisoa tse atileng haholo bakeng sa li-cores tsa transformer. E na le thepa ea makenete, ho kenyeletsoa ho kenella haholo le tahlehelo ea mantlha e tlase. Ha ho bapisoa le li-cores tse tloaelehileng tsa laminated, li-cores tsa maqeba li bobebe, tse nolofalletsang ho hahoa ha li-transformer tse nyenyane le tse bobebe.

75 kva pole mounted transformer-amorphous-core

 

2.2 Ho tsubella

75 kva pole mounted transformer-coils

Maqhubu a transformer a entsoe ka bokhabane ke basebetsi ba khale ba nang le boiphihlelo ba lilemo tse fetang leshome. Matsoelo a tlase{{1}ke leqeba-'me sebaka se phahameng-ke maqeba a motlakase ke terata{4}}, 'me ho na le taolo e nepahetseng ho thibela ho phahama ha foil. Inter-mokoloko oa ho thinya le{7}}mokhoa oa ho thinya le ka har'a{7}}li sebelisoa ka hloko ho qoba ho tsoa ka mokhoa o itseng.

 

2.3 Tanka

Tanka ea mafura a cylindrical e entsoe ka tšepe e bonolo. Theknoloji e tšesaane- ea ho otlolla maqephe e etsa hore sekoahelo le tlase li be bobebe 'me li be matla. Tanka e tiisitsoe ka ho feletseng. Moqapi ona o etsa hore e ikamahanye le tikoloho le ho tšepahala ho sebelisoa. E sebetsa hantle bakeng sa phepelo ea motlakase ea kantle e sa sitisoeng.

75 kva pole mounted transformer mild steel cylindrical fuel tank

 

2.4 Kopano ea ho Qetela

75 kva pole mounted transformer-activepart

Mokhoa oa ho kenya khoele le mokokotlo oa maqeba: Qala ka ho rala C-ea pele ea mantlha (e bulang e shebile holimo joalo ka "U"). Nka coil 'me u phunye ka botlalo lesoba la eona le bohareng holim'a leoto le le leng la mantlha, u le sutumelletse tlase ho ea tlase. Nka C{3}}konokono ea bobeli, u tsamaise sehiloeng sa eona hantle le sehiloeng sa mantlha sa mantlha. E koala ka bonolo ho fihlela likarolo tse peli li kopana ka botlalo. Kenya lipoleiti tsa clamping tse ka holimo le ka tlase, kenya li-screws tse telele.

 

 

03 Ho etsa liteko

Teko e Tloaelehileng

1. Litekanyo tsa ho hanyetsa

2. Karo-karolelano Liteko

3. Teko ea kamano ea Mokhahlelo-

4. Ha ho Tahlehelo ea Mojaro 'me Ha ho na Mojaro Hona Joale

5. Litahlehelo tsa Meroalo, Matla a Matla a Impedance le Katleho

6. Teko ea Voltage e sebelisitsoeng

7. Induced Voltage E mamella Teko

8. Teko ea ho Lutla ka Khatello ea Li-transformers tse qoelitsoeng ka Metsi

9. Tekanyo ea ho hanyetsa Insulation

10. Teko ea Dielectric ea Oli

11. Lehalima Impulse Test

 

75 kva pole mounted transformer-electrical-test
75 kva pole mounted transformer-performance-test

 

Liphetho tsa liteko

Che.

Ntho ea Teko

Yuniti

Melao ea ho Amohela

Litekanyetso Tse Lekanyelitsoeng

Qetello

1

Litekanyo tsa ho hanyetsa

%

/

/

Feta

2

Liteko tsa karo-karolelano

%

Phapang ea karo-karolelano ea motlakase ho theipi ea mantlha: Ka tlase ho kapa ho lekana le 0.5%

Letšoao la khokahano: Ii6

-0.03

Feta

3

diteko- tsa dikamano

/

Keketso

Keketso

Feta

4

Ha ho{{0}tahlehelo ea thepa le thabo ea hona joale

%

kW

T:85 likhato

I0 :: fana ka boleng bo lekantsoeng

P0: fana ka boleng bo lekantsoeng

mamello ea ho se lahleheloe ke moroalo ke +10%

0.24(100%)

0.46(105%)

0.144(100%)

0.167(105%)

Feta

5

Litahlehelo tsa tahlehelo ea matla a motlakase le katleho

%

kW

kW

T:85 likhato

Z%: boleng bo lekantsoeng

Pk: boleng bo lekantsoeng

Pt: boleng bo lekantsoeng

mamello ea impedance ke ± 10%

mamello ea tahlehelo ea boima kaofela ke +6%

2.19

0.688

0.838

99.19

Feta

6

Teko ea Voltage e sebelisitsoeng

kV

HV: 34kV 60s

LV: 10kV 60s

Ha ho ho putlama ha motlakase oa liteko

Feta

7

Teko ea ho mamella Voltage e kentsoeng

kV

Matla a sebelisoang (KV):

15.94

Nako:40

Hangata (HZ): 150

Ha ho ho putlama ha motlakase oa liteko

Feta

8

Leakage Test

kPa

Khatello e sebelisitsoeng: 20kPA

Nako: 12h

Ha ho na leakage le che

Tšenyo

Feta

9

Tekanyo ea ho hanyetsa Insulation

HV&LV ho ea fatše:

97.1

/

HV{{0}LV ho ea fatše

36.1

LV-HV ho ea fatše

45.5

10

Teko ea Dielectric ea Oli

kV

E kholo ho feta kapa e lekana le 45

55.50

Feta

11

Teko ea matla a matla

kV

leqhubu le tletseng, Half wave

Ha ho ho putlama ha motlakase oa liteko

Feta

 

 

04 Ho paka le ho Romela

75 kva pole mounted transformer-packaging
 
75 kva pole mounted transformer-wooden crate packaging
 

05 Sebaka le Kakaretso

The 75 kVA single{1}}phase pole mounted transformer e etselitsoe Canada ka 2024. E latela IEEE C57.12.20. E sebetsa ho 13.8 kV grounded-wye system 'me e fana ka 120/240 V split{8}}mohato oa tlhahiso bakeng sa matlo le likhoebo tse nyenyane.

Transformer e na le-moko oa tšepe oa silicon oa boleng bo holimo. Ha e boloke -tahlehelo ea mojaro ho 0.148 kW le tahlehelo ea mojaro ho 0.675 kW. E sebetsa ka katleho e phahameng le litšenyehelo tse tlase tsa ts'ebetso. Maqhubu ke aluminiamo, a nang le foil-likhoele tsa LV tse nang le maqeba le lithapo{8}} tsa HV tse nang le maqeba. Mosebetsi oa matsoelintsoeke o etsoa ke basebetsi ba nang le litsebo, ho netefatsa hore ho kenella ka matla le ts'ebetso e sireletsehileng.

Tanka e entsoe ka tšepe e bonolo. E tiisitsoe ka botlalo, e bobebe ebile e matla. E fana ka tšireletso e ntle ka ntle 'me e sebetsa hantle-litšebeletso tsa nako e telele. Sehlopha sena se boetse se na le mookameli oa surge arrester, e leng se etsang hore ho be bonolo ho eketsa tšireletso.

Li-transformer tsa SCOTECH li hahiloe ho latela maemo a machaba. Lihlahisoa tsa rona li boloka matla, li fokotsa tahlehelo, 'me li fana ka matla a tsitsitseng. Re fana ka litharollo tse sireletsehileng le tse netefalitsoeng tse ntlafatsang ts'ebetso ea grid letsatsi le letsatsi.

75 kva pole mounted transformer-left-view

Hot Tags: li-transformer tse kentsoeng ka palo, moetsi, mofani oa thepa, theko, litšenyehelo