2000 KVA Power Transformer Box-12.47/0.48 KV|USA 2025
Matla: 2000 kVA
Matla: 12.47/0.48 kV
Tšobotsi: ka Oli ea FR3
Jiangshan Scotech Electrical Co., Ltd ke e 'ngoe ea baetsi le barekisi ba tšepahalang ba 2000 kva power transformer box-12.47/0.48 kv|USA 2025 naheng ea China. Ka kopo, ikutloe u lokolohile ho reka lihlahisoa tse baballang litšenyehelo tse rekisoang mona le ho fumana litšoantšo ho tsoa femeng ea rona. Ikopanye le rona bakeng sa lintlha tse ling.

Ho Tšepahala ka Sekhukhu, Ka Holimo-Ho Finyelleha ka Motheo. Pad-Mounted Transformers.
01 Kakaretso
1.1 Tlhaloso ea Morero
2000 kVA tse tharo phase pad mounted transformer e ile ea isoa USA ka 2025. Matla a lekantsoeng a transformer ke 2000 kVA le KNAN cooling. Matla a phahameng ke 12.47GrdY/7.2 kV e nang le ± 2 * 2.5% tapping range (NLTC), motlakase o tlaase ke 0.48Y / 0.277 kV, ba thehile sehlopha sa vector sa YNyn0.
Joalo ka karolo ea bohlokoa marang-rang a sejoale-joale a kabo ea motlakase, pad mounted transformer e etselitsoe ho fana ka phetoho e tšepahalang ea motlakase le phepelo ea motlakase bakeng sa lits'ebetso tsa bolulo, tsa khoebo le tsa indasteri. Transformer ena e hlahelletse ka boqapi ba eona e baballang tikoloho le e bolokehileng, e nang le oli ea FR3 ea tlhaho ea ester insulation-e leng tharollo e ka nchafatsoang habonolo, e felisang likotsi tsa tikoloho tse amanang le oli ea setso ea liminerale. Oli ea FR3 ha e ithorise feela ka polokeho ea mollo e ikhethang (e nang le flash le lintlha tsa mollo habeli tsa oli ea minerale) empa hape e eketsa nako ea bophelo ba pampiri e kenang ka makhetlo a robeli, e netefatsa hore ts'ebetso ea nako e telele-e tsitsisa. E tsamaellana le litekanyetso tse tiileng tsa matla a matla a DOE, e fokotsa tahlehelo ea matla le ho fokotsa litšenyehelo tsa ts'ebetso haholo. E na le-mohatlalatsi o hahelletsoeng, e sireletsa hantle khahlano le ho phahama ha motlakase le ho fetella ha nakoana, ha static shield e kopaneng e ntlafatsa ts'ebetso ea ho koala le ho fokotsa likotsi tse itseng tsa ho tsoa. The side{10}lebokose la gauge e phahamisitsoeng le fana ka tlhahlobo e bonolo ea nako{11}}ea maemo a bohlokoa a ts'ebetso, ho netefatsa tlhokomelo ka nako le ho lemoha liphoso. E qetiloe ka{13}}pente e soeufalitsoeng (RAL 9003) e phofshoana, transformer e fana ka tšireletso e ntle ea boemo ba leholimo le ts'ireletso ea kutu, e etsa hore e tšoanelehe libakeng tse fapaneng tsa kantle. Transformer ena ea pad mounted ke khetho e nepahetseng bakeng sa basebelisi ba etelletsang pele ho boloka tikoloho, polokeho ea ts'ebetso, le ho ts'epahala ha nako e telele{16}.
1.2 Tlhaloso ea Setsebi
2000 kVA pad mounted transformer specifications type le data sheet
|
E fetisetsoa ho
usa
|
|
Selemo
2025
|
|
Mofuta
Transformer e kentsoeng ka pampiri
|
|
Standard
IEEE Std C57.12.34-2022
|
|
Rated Power
2000 kVA
|
|
Khafetsa
60HZ
|
|
Mokhahlelo
3
|
|
Fepa
Loop
|
|
Pele
E shoeleng
|
|
Mofuta oa ho Pholisa
KNAN
|
|
Voltage ea mantlha
12.47GrdY/7.2 kV
|
|
Motlakase oa bobeli
0.48Y/0,277 kV
|
|
Lintho Tse Hlahang
Aluminium
|
|
Sehlopha sa Vector
YNyn0
|
|
Tšitiso
5.75%
|
|
Katleho
99.51%
|
|
Tlanya Changer
NLTC
|
|
Tlanya Range
±2*2.5%
|
|
Ha ho Tahlehelo ea Mojaro
1.95 kW
|
|
Ho Lahleheloa ke Moroalo
13.15 kW
|
1.3 Litšoantšo
2000 kVA pad mounted transformer diagram to the size and size.
![]() |
![]() |
02 Tlhahiso
2.1 HV Neutral (H0)

Sebaka se phahameng{{0}tlase sa "voltage neutral point" sa transfoma ena e phahamisitsoeng se hlahisoa e le H0 bushing e arohaneng, moralo o entsoeng ka boomo o nolofatsang{2}}ts'ebetso le tlhokomelo ea sebaka sa marang-rang, le ho ntlafatsa ts'ireletseho ea ts'ebetso. Tokisetso ena e lumella hore ho be le taolo e nepahetseng holim'a monyetla oa ho se nke lehlakore, ka katleho e hatella likotsi tse feteletseng, 'me e lumellana ka mokhoa o sa tsitsang litlhoko tse fapaneng tsa marang-rang a matla (joalo ka mekhoa ea TN, TT), e leng se etsang hore transformer e ikamahanye le mefuta e mengata ea kabo ea litoropo, serapa sa boikhathollo sa indasteri le lits'ebetso tsa meaho ea khoebo.
2.2 LV Neutral Bushing (X0)
Karolo e tlase{{0}ea "voltage neutral" ea "pad mounted" e entsoe ka lihlahla tse peli tse ikhethileng bakeng sa ts'ebetso e ikhethileng: sehlahla se le seng se holisa thebe e tsitsitseng ka ntle ho tanka, 'me e theiloe ka mokhoa o sireletsehileng ka har'a komporo ea LV, e fokotsang kotsi ea ho tsoa le ho ntlafatsa ts'ebetso ea mochini oa transfoma; bushing e 'ngoe e sebelisoa feela bakeng sa ho etella pele sebaka sa ho se nke lehlakore sa LV, se nolofalletsang tlhophiso ea khokahano ea ntlha e sa nke lehlakore ho fihlela litlhoko tsa motheo tsa litsamaiso tse fapaneng tsa kabo.

2.3 Four Position Loadbreak Switch

The four-position loadbreak switcher of pad mounted transformer ke ea bohlokoa{1}}karolong ea ho chencha thepa e kopantsoeng le maemo a mane a ts'ebetso a seng a setiloe, a etselitsoeng ho nolofalletsa ts'ebetso e bolokehileng le e ts'epahalang ea ho switjha (joalo ka taolo ea motlakase, taolo ea ho tima kapa ho tima, kapa ts'ireletso ea fatše) tlasa maemo a laetseng ntle le ho sitisa phepelo ea motlakase ka kakaretso. E etselitsoe ho ts'oana le litšoaneleho tsa ts'ebetso ea li-transformer tse kentsoeng marang-rang marang-rang a kabo ea litoropo, lirapeng tsa boikhathollo tsa indasteri le lits'ebeletso tsa khoebo, sesebelisoa sena se na le sebopeho se matla, ts'ebetso e phahameng ea insulation, le indexing ea boemo bo nepahetseng, ho netefatsa ho ikopanya ho tsitsitseng le khanyetso e tlase ea ho ikopanya nakong ea lits'ebetso. 4 Ntle le moo, e lumellana le litlhoko tsa polokeho le tikoloho ea tikoloho ea kantle kapa e kentsoeng, e fana ka tharollo e tšoarellang le e sebetsang ea phetisetso bakeng sa litsamaiso tsa li-transformer tse kentsoeng ka pad.
2.4 Busbar ea Koporo e Tlisang fatše
The ground busbar copper -pad mounted transformer ke conductor e tiileng ea koporo e kentsoeng ka har'a sebaka se kampetsoeng ho fana ka sebaka se tšoanang sa motheo. E hokela tanka ea transfoma,- le libaka tsa ho theola motlakase tse phahameng-le tlase{3}, li-cable shields, le lisebelisoa tsa ts'ireletso ea surge, ho netefatsa hore ho na le tsela e tlase-e thibelang lefatše. Sebaka sena sa busbar se ntlafatsa ts'ireletso ea basebetsi le ts'ireletso ea lisebelisoa ka ho felisa matla le lehalima.

2.5 1''drain valve e nang le sampuli ea 3/8''

Transformer e na le valve e matla ea 1-ea inch drainage e nang le boema-kepe bo kopaneng ba 3/8-inch, bo etselitsoeng ho thusa tlhahlobo le tlhokomelo ea mokelikeli oa dielectric; valve ea 1-inch e lumella ho tlosoa ka mokhoa o nepahetseng ha sediment kapa seretse se bokelitsoeng ho tloha tlaase ho tanka, ha sampuli ea 3/8-inch e fana ka khokahanyo e inehetseng, e nyenyane ea ho ntša lisampole tsa oli ntle le ho ntša yuniti, ho netefatsa botšepehi ba ts'ebetso le ho lumellana le liprothokholo tsa tlhahlobo ea tlhahlobo.
03 Ho etsa liteko

04 Ho paka le ho Romela


05 Sebaka le Kakaretso
Ha e le hantle, li-transformer tsa SCOTECH's - li eme e le sesupo sa ho tšepahala, ho sebetsa hantle, le ho tšoarella ha marang-rang a sejoale-joale a kabo ea motlakase-ekaba a kopantsoe le marang-rang a literopo, meaho ea khoebo, kapa lisebelisoa tse nchafalitsoeng tsa matla a letsatsi le polokelo ea matla a letsatsi. E etselitsoe ho kopana le litekanyetso tse thata tsa machaba ho kenyeletsoa IEEE C57 le CSA C227.4:21, li-transformer tsena li fana ka ts'ebetso e ts'oanang libakeng tse thata tsa kantle, li fokotsa nako ea ho lokisoa, le ho netefatsa phepelo ea motlakase e bolokehileng, e tsitsitseng ka lilemo tse mashome. Ka tšehetso ea lilemo tse mashome tsa SCOTECH - tsa boitseanape bo bolelele ba ho etsa li-transformer, karolo e 'ngoe le e 'ngoe ke bopaki ba boitlamo ba rona ba boleng le khotsofalo ea bareki. Khetha SCOTECH pad - li-transformer tse kentsoeng, 'me u sebelisane le mofani oa litšebeletso tseo u li tšepang ho matlafatsa merero ea hau ka kholiseho le khotso ea kelello.

Hot Tags: lebokose la motlakase oa motlakase, moetsi, mofani oa thepa, theko, litšenyehelo
You Might Also Like
112.5 kVA Pad Mounted Transformer-34.5/0.208 kV|USA ...
300 kVA Pad-mounter-34.5/0.208 kV|USA 2024
300 kVA Green Box Transformer-12/0.12 * 0.24 kV|Jama...
1000 kVA Oli e Tlatsang Pad Mounted Transformer-13.8...
400 kVA Padmount Transformer-23 / 0.4 kV|Chile 2024
225 kVA Pad Mounted Transformer-34.5/19.92 kV|USA 2024
Romela Inquiry