300 kVA Pad Mount Transformer-12.47/0.48 kV|USA 2024

300 kVA Pad Mount Transformer-12.47/0.48 kV|USA 2024

Naha: Amerika 2024
Matla: 300kVA
Matla: 12.47/0.48kV
Sebopeho: tanka ea tšepe e sa hloekang
Romela Inquiry

 

 

300 kva pad mount transformer

Litlhahiso tse tala, -mohloli oa ho boloka matla-Liphetoho tse - tse tharo tsa mekhahlelo- tse holimo, tse etellang pele mehleng ea matla a tsitsitseng!

 

01 Kakaretso

1.1 Semelo sa Morero

300 kVA pad mounted transformer e ile ea isoa Amerika ka 2024. Matla a lekantsoeng a transformer ke 300 kVA e nang le pholiso ea ONAN. Motlakase oa mantlha ke 12.47GrdY/7.2 kV e nang le ± 2 * 2.5% tapping range (NLTC), motlakase oa bobeli ke 0.48 / 0.277 kV, ba thehile sehlopha sa vector sa YNyn0, Melemo ke boleng bo phahameng ba motlakase, ntlha e sa nke lehlakore ha e hoholehe, lebokose ha le chese, lerata le tlaase, tšireletso e ntle ea lehalima. Ke phepelo ea loop le transformer e ka pele e shoeleng. pad mounted transformer e ka sebelisoa ka tlung kapa ka ntle, e sebelisoa haholo lirapeng tsa boikhathollo tsa indasteri, libakeng tsa bolulo, litsi tsa khoebo le{13}meaho e phahameng le libakeng tse ling.

Ho bohlokoa ho bolela hore pholiso ea dielectric ho transformer e sebelisa mofuta o hloekisitsoeng haholo oa Mofuta oa II o thibetse oli e ncha ea liminerale. Bayonet e nang le li-fuse tse fokotsang hona joale. Sekeme sa ho sireletsa{2}voltage overcurrent overcurrent se fanweng le transformer ke sebaka se ka ntshuwang ka ntle sa ho robeha ha morwalo{3}O-Khokahano ya Net fuse e nang le valve ya flapper ho fokotsa ho qhalana ha oli. Li-fuse tsa bayonet li hlophisitsoe ka ELSP ka tlas'a-karolo ea oli{7}}moeli o fokolang oa morao-rao{8}}ka li-fuse tse sitisang 50,000 RMS symmetrical ampere tse sitisang bonyane ba hona joale ba ho qhibiliha hoo e ka bang 200% ea lintlha tsa transformer nameplate.

 

 

1.2 Tlhaloso ea Setsebi

Litlhaloso tsa mofuta oa 300 kVA le pampiri ea data

E fetisetsoa ho
Amerika
Selemo
2024
Mofuta
Transformer e kentsoeng ka pampiri
Standard
IEEE Std C57.12.34-2022
Rated Power
300KVA
Khafetsa
60 HZ
Mokhahlelo
3
Fepa
Loop
Pele
E shoeleng
Mofuta oa ho Pholisa
ONA
Voltage ea mantlha
12.47GRDY/7.2 KV
Motlakase oa bobeli
0.48/0,277 KV
Lintho Tse Hlahang
Aluminium
Angular displacement
YNyn0
Tšitiso
4%
Tlanya Changer
NLTC
Tlanya Range
±2*2.5%
Ha ho Tahlehelo ea Mojaro
0.45KW
Ho Lahleheloa ke Moroalo
2.925KW
Lisebelisoa
Tlhophiso e Tloaelehileng

 

1.3 Litšoantšo

300 kVA pad mounted transformer diagram to the size and size.

300 kva pad mount transformer diagram 300 kva pad mount transformer nameplate

 

 

02 Tlhahiso

2.1 Konokono

Melemo ea Boraro{{0}Mokhahlelo oa Bohlano-Limb Core

High Magnetic Circuit Symmetry:E matlafatsa-mohato oa boraro.

Tshebetso e Kgutshwane-ya Potoloho e Kgutshwane:Ho hanyetsa ka matla ho lipotoloho tse khutšoanyane tse nang le saturation e tlaase ea magnetic.

Sebopeho se Matla sa Mechini:Motsoako oa li-tie plate le lisebelisoa tsa ho koala li tiisa{0}}ts'ebetso ea nako e telele.

Mosebetsi oa Lisebelisoa tsa Clamping: Sireletsa konokono le ho thibela lishiti tsa tšepe tsa silicon hore li se ke tsa theoha; tshehetsa boima ba mantlha le mapheo.

Mosebetsi oa Lipoleiti tsa Tlama: Fana ka lisebelisoa tse ka holimo le tse tlase tsa clamping u sebelisa liboutu, u fane ka khatello ea lateral, 'me u thibele mantlha ho thella.

Excellent Short-Circuit Performance

 

2.2 Ho tsubella

vacuum process

Coil e sirelelitsoe ka B-mohato, epoxy coated, diamond pattern, insulating paper, e phekolehang ka mocheso tlas'a khatello ho netefatsa hore ho tlamahanngoa hantle ha conductor le pampiri. Coil e se e sebelitsoe ka vacuum ho etsa bonnete ba ho kenella ka bongata ha mokelikeli o thibelang metsi ka har'a sistimi ea ho kenya li-coil. Motsoako oa -oa matsoelintsoeke a foil a tlase le -oa matsoelintsoeke a motlakase o phahameng o etsa hore motho a lahleheloe ke thepa e tlase 'me a khone ho tsamaea ka nako e khutšoanyane-, 'me a finyella litlhoko tse fapaneng tsa mojaro. E netefatsa hore motlakase o arohantsoe lipakeng tsa-maemelo a phahameng a motlakase le a tlase{8}}e matlafatsang tšireletso. Ho tsitsa ha mochini oa foil winding le ho ts'epahala ho ts'epahala ha mapheo a terata ho ntlafatsa bophelo ba ts'ebetso ea transformer. Ho hanyetsa ka matla ho lipotoloho tse khutšoane le ho sisinyeha ho etsa hore e tšoanelehe bakeng sa maemo a thata a ts'ebetso.

 

2.3 Tanka

Tanka ea transformer e entsoe ka tšepe e sa hloekang ea 304, Setsi sa tanka se etselitsoe ho lumella ho thella kapa ho thella ka tsela efe kapa efe. Litokisetso tsa ho phahamisa li na le mekotla e mene ea ho phahamisa e cheselitsoeng tanka. Transformer e amohela kaho ea tanka e tiisitsoeng ea matla a lekaneng ho mamella khatello ea 7 psig ntle le ho sotha ka ho sa feleng, le 15 psig ntle le ho phatloha kapa ho ama ts'ireletso ea khabinete.

Tanka e kenyelletsa sesebelisoa sa khatello ea khatello e le mokhoa oa ho imolla khatello e feteletseng ea khatello e bakoang ke ts'ebetso e tloaelehileng. Litšobotsi tsa ho kenya moea le ho tiisa e tla ba tse latelang:

a. Khatello ea ho senya: 10psig ± 2psig.

b. Khatello ea ho tiisa: bonyane ba 6psig.

c. Ho lutla ha Zero ho tloha khatellong ea seal ho ea ho -8psig.

d. Phallang ka 15 psig: 35 SCFM bonyane.

304 stainless steel

 

2.4 Kopano ea ho Qetela

transformer accessory installation

Ho kenngwa ha Core Component:

Lokisa lithapo le lithapo ka tankeng ea oli, hokela li-lead tse phahameng- le tse tlase{1}}'me u kenye lisebelisoa tse sireletsang le tse sireletsang ho netefatsa likhokahano tse tšepahalang tsa motlakase.

Kenyelletso ea lisebelisoa:

Kenya lisebelisoa tse kang tekanyo ea boemo ba oli, tekanyo ea mocheso, le mapheoana a pholiso. Hokela lebokose la li-terminal le likarolo tsa taolo, ho phethela ho kenya lisebelisoa tse sireletsang.

Kakaretso le ho Tiisa:

Beha sebaka sa tšepe ho tiisa tanka ea oli, hlahloba le ho tiisa manonyeletso ho netefatsa hore mongobo o hana ho lutla.

Teko le Ho Tlatsa Oli:

Etsa liteko tsa tšebetso ea motlakase le ea mochini, tlatsa tanka ea oli ka oli e sireletsang, u tlose lipululo, 'me u lekole-teko ea ho tiisa ha khase.

 

 

03 Ho etsa liteko

Che.

Ntho ea Teko

Yuniti

Kamohelo

Litekanyetso

Litekanyetso Tse Lekanyelitsoeng

Qetello

1

Litekanyo tsa ho hanyetsa

%

Sekhahla se phahameng sa ho hanyetsa ho se leka-lekane

0.37

Feta

2

Liteko tsa Karolelano

%

Phapang ea karo-karolelano ea motlakase ho theipi ea mantlha: Ka tlase ho kapa ho lekana le 0.5%

-0.05

Feta

3

Liteko tsa likamano tsa mohato-

/

YNyn0

YNyn0

Feta

4

Ha ho{{0}tahlehelo ea thepa le thabo ea hona joale

%

I0 :: fana ka boleng bo lekantsoeng

0.28

Feta

kW

P0: fana ka boleng bo lekantsoeng (ka likhato tse 20)

0.412

/

mamello ea ho se lahleheloe ke moroalo ke ± 10%

/

5

Litahlehelo tsa meroalo, motlakase oa impedance, tahlehelo e felletseng le katleho

/

T:85 likhato

mamello bakeng sa impedance ke ± 7.5%

mamello ea tahlehelo ea mojaro o felletseng ke ± 6%

/

Feta

%

Z%: boleng bo lekantsoeng

3.86

kW

Pk: boleng bo lekantsoeng

2.822

kW

Pt: boleng bo lekantsoeng

3.234

%

Katleho e seng ka tlase ho 99.27%

99.30

6

Teko ea Voltage e sebelisitsoeng

/

HV: 34kV 60s

LV: 10kV 60s

Ha ho ho putlama ha motlakase oa liteko

Feta

7

Teko ea ho mamella Voltage e kentsoeng

/

Matla a sebelisoang (KV): 0.96

Ha ho ho putlama ha motlakase oa liteko

Feta

Nako:48

Hangata (HZ): 150

8

Tekanyo ea ho hanyetsa Insulation

HV{{0}LV ho ea fatše:

85.3

/

LV-HV ho ea fatše:

95.2

HV&LV ho ea fatše:

90.1

9

Leakage Test

/

Khatello e sebelisitsoeng: 20kPA

Ha ho na leakage le che

Tšenyo

Feta

Nako:12h

10

Tlhahlobo ea oli

kV

Matla a Dielectric

56.9

Feta

mg/kg

Mongobo

9.9

%

Ntho ea ho senya

0.0274

mg/kg

Furan Analysis

/

/

Tlhahlobo ea Khase ea Chromatography

/

 

300 kva pad mount transformer test
300 kva transformer routine test

 

 

04 Ho paka le ho Romela

channel steel
300kva transformer shipping
 
 

 

05 Sebaka le Kakaretso

Indastering ea motlakase ea kajeno e ntseng e tsoela pele ka potlako, transfoma e phahamisitsoeng ka mekhahlelo e meraro e fetohile karolo ea bohlokoahali ea litsamaiso tsa kabo ea motlakase ka lebaka la ts'ebetso ea eona e ntle le ts'epahalo. Ebang ke lits'ebetsong tsa bolulo, tsa khoebo, kapa tsa indasteri, moralo oa eona o kopaneng, ho lokisoa habonolo, le matla a matle a tikoloho li etsa hore e khone ho fihlela litlhoko tse fapaneng tse rarahaneng tsa motlakase. Ho khetha transfoma e kentsoeng ka mekhahlelo e meraro ha se khetho feela bakeng sa tharollo e sebetsang ea matla empa hape ke boitlamo ba polokeho le botsitso. Re ikemiselitse ho fa bareki ba rona lihlahisoa le lits'ebeletso tse ikhethang, ho u thusa ho fumana melemo e mengata lits'ebetsong tsa sejoale-joale tsa motlakase.

300kva transformer outstanding performance

 

Hot Tags: 300 kva pad mount transformer, moetsi, mofani oa thepa, theko, litšenyehelo