1500 kVA Mount Transformer-22.86 / 0.208 kV|USA 2024

1500 kVA Mount Transformer-22.86 / 0.208 kV|USA 2024

Naha: Amerika 2024
Matla: 1500kVA
Matla: 22.86/0.208kV
Feature: e nang le surge arrester
Romela Inquiry

 

 

1500 kVA mount transformer

Matla a tsitsitseng, ts'ehetso e ts'epahalang-Liphetoho tse kentsoeng- tsa mekhahlelo e meraro{2}, tse matlafatsang motsotso o mong le o mong!

 

01 Kakaretso

1.1 Semelo sa Morero

1500 kVA pad mounted transformer e ile ea isoa Amerika ka 2024. Matla a lekantsoeng a transformer ke 1500 kVA e nang le pholiso ea ONAN. Motlakase oa mantlha ke 22.86kV o nang le ± 2 * 2.5% tapping range (NLTC), motlakase oa bobeli ke 0.208kV, ba thehile sehlopha sa vector sa YNyn0, 'me ke sesebelisoa sa loop le transformer e ka pele e shoeleng. Pad mounted transformer ke compact,{10}e kentsoeng pele{10}sesebediswa sa motlakase sa kantle, se sebediswang haholo dinetwekeng tsa ho aba. E kopanya li-switches tse phahameng-li-voltage, li-transformer le{13}}lisebelisoa tse fetisoang ka matla a tlase ka har'a lebokose, le leng le lenyenyane ka boholo 'me le nka sebaka se fokolang, 'me le loketse libaka tse nang le sebaka se fokolang. pad mounted transformer ke{15}}e kentsoeng, e hloka feela ho ba bonolo ho{16}}khokahanyo ea sebaka sa marang-rang, nako ea ho kenya le ho sebetsa e khutšoane, ho bonolo ho e tsamaisa le ho holisa. Ka moralo o tiisitsoeng ka ho feletseng, o sirelelitsoeng ka ho feletseng, lebokose le na le tšebetso e ntle e thibelang{18}}ho bola, e sa keneleng metsi, e lerōle{19}, e loketseng maemo a fapaneng a thata. Moralo o kopanetsweng o fokotsa ditjeho mme o loketse diphaka tsa diindaseteri, dibaka tsa bodulo le phetolo ya keriti ya motlakase ya mahaeng.

Our three-phase pad-mounted transformers are engineered to address critical grid challenges in demanding environments like the U.S. Gulf Coast, where units must withstand Category 4 hurricane winds and salt-rich atmospheres while fitting within 2.5-meter urban footprints. Constructed with 304 stainless steel tanks, hybrid foil-wire windings, and IP68 sealing, these transformers achieve >99% e sebetsang hantle, e fokotsa tahlehelo ea mojaro ka 20%, le ho fana ka maemo a sa fellang a ho tsoa ka tlase ho 5 pC. E kopantsoe le-ka lisensara tsa nako ea nnete, li thusa ho lokisoa le ho fokotsa nako ea karabo ea ho tima ka 40%, ho fana ka lisebelisoa tse nang le-lisebelisoa tse tšoarellang tse eketsang bophelo ba ts'ebeletso ho fihlela lilemo tse 35 le ho theola kakaretso ea litšenyehelo tsa ho ba beng libakeng tse thata tsa lebopo kapa{8}likopo tse ngata tsa litoropo.

 

 

1.2 Tlhaloso ea Setsebi

1500 kVA lintlha tsa mofuta oa li-transformer le leqephe la data

E fetisetsoa ho
Amerika
Selemo
2024
Mofuta
Transformer e kentsoeng ka pampiri
Standard
IEEE C57.12.00
Fepa
Loop
Pele
E shoeleng
Rated Power
1500kVA
Khafetsa
60 HZ
Mokhahlelo
3
Mofuta oa ho Pholisa
ONA
Voltage ea mantlha
22.86 kV
Motlakase oa bobeli
0.208 kV
Lintho Tse Hlahang
Aluminium
Angular displacement
YNyn0
Tšitiso
5.75%
Tlanya Changer
NLTC
Tlanya Range
±2*2.5%
Ha ho Tahlehelo ea Mojaro
1.545kW
Ho Lahleheloa ke Moroalo
10.535kW
Lisebelisoa
Tlhophiso e Tloaelehileng

 

1.3 Litšoantšo

1500 kVA pad mounted transformer diagram to the size and size.

1500 kVA pad mounted transformer drawing 1500 kVA mount transformer nameplate

 

 

02 Tlhahiso

2.1 Konokono

Meralo e mehlano-e eketsa tse peli tse thusang-maoto a khutlisetsang ho tiisetso e tloaelehileng ea mohato oa boraro-, e nolofalletsang ho sebetsana le ho se leka-lekane ha makenete lits'ebetsong tsa grid. Ka ho fana ka litsela tse laoloang bakeng sa phallo e feteletseng, e thibela ho tlala hohle tlas'a meroalo e sa leka-lekaneng{4}}e tloaelehileng marang-rang a hlahisang matla a letsatsi kapa a liindasteri-ho fokotsa tahlehelo ka 25% le ho boloka ts'ebetso e sebetsang nakong ea 130% ea maemo a mangata. Sena se fella ka bophelo bo bolelele ba ho kenya letsoho, litšenyehelo tse fokotsehileng tsa ts'ebetso, le botsitso bo matlafalitsoeng ba grid bakeng sa lits'ebeletso tse tsamaisang lifaele tse rarahaneng tsa mojaro.

five-column iron core

 

2.2 Ho tsubella

YNyn0 1500 kVA mount transformer winding

Ho tsoelipana ha transformer ho amohela sehlopha sa khokahanyo ea YNyn0, 'me mahlakore ka bobeli a matla a phahameng (YN) le lehlakore le tlaase la motlakase (yn) a thehiloe ka ntlha e sa nke lehlakore, e leng se loketseng ho ntlafatsa botsitso ba motlakase oa tsamaiso. Ha karolo e meraro-moroalo o sa leka-lekanngoa, ntlha e sa nke lehlakore ea transformer e ka fana ka tsela bakeng sa tatellano ea lefela hona joale ho fokotsa tšusumetso ho motlakase oa tsamaiso. Ha u sa nke lehlakore, ho fetoha ha motlakase o sa nke lehlakore kapa hona joale ho ka sebelisoa ho bona liphoso kapele, joalo ka{4}}mohato o le mong.

 

2.3 Tanka

Transformer ea tanka ea Amerika e nka moralo o kopaneng, boholo bo kopaneng, sebaka se senyenyane, se loketseng tikoloho ea litoropo, kabo ea matla a sechaba le liketsahalo tse ling tse hlokang ho boloka sebaka. Hangata tanka e sebelisa-mekhoa e nepahetseng ea ho tjheseletsa le sebopeho sa ho tiisa ho thibela ka nepo ho dutla ha oli ea transformer kapa ho kena ha moea le metsi kantle. E na le valve ea ho imolla khatello le sesebediswa se thibelang ho phatloha-ho netefatsa tshebetso e bolokehileng. Tanka e entsoe ka tšepe ea boleng bo holimo 'me e alafshoa ka ts'ireletso ea ho senya (mohlala, hot dip galvanizing, spray kapa epoxy coating). E na le khanyetso e ntle ea kutu le khanyetso ea khoholeho ea tikoloho, e loketseng mongobo, sefafatsi sa letsoai, tšilafalo ea indasteri le libaka tse ling tse thata. Tanka e entsoe ka lipampiri tse entsoeng ka masenke ho fana ka elasticity e lekaneng ea mochini ho monya katoloso ea molumo kapa ho fokotseha ha oli ea transformer ka lebaka la liphetoho tsa mocheso, ntle le tlhoko ea mosamo o ikemetseng oa oli.

1500 kVA mount transformer oil tank

 

2.4 Kopano ea ho Qetela

1500 kVA mount transformer assembly

Mohato oa ho qetela oa khomishene o qala ka ho nepahala-mahokelo a motlakase a torque a netefalitsoeng ka liteko tse nyane- tsa ohm ho netefatsa<5% phase imbalance, followed by a vacuum-assisted oil filling process that achieves <0.5% gas content in the insulating fluid. The cooling system undergoes cyclic pressure testing at 1.5× operating pressure with thermal imaging confirming ±2°C temperature uniformity across radiators. Insulation resistance testing at 5kV DC validates >1000 MΩ polarization index, e fetang litlhokahalo tsa IEEE C57.12.00, athe IP68-e nang le likhase tse peli tsa EPDM e phethela tiiso ea hermetic-e nolofalletsang ho sebetsa lihora tse 8{6}}matla le ho felisa mathata a amanang le mongobo lebopong la leoatle.

 

 

03 Teko

Che.

Ntho ea Teko

Yuniti

Kamohelo

Litekanyetso

Litekanyetso Tse Lekanyelitsoeng

Qetello

1

Litekanyo tsa ho hanyetsa

%

/

6.67

Feta

2

Liteko tsa karo-karolelano

%

Phapang ea karo-karolelano ea motlakase ho theipi ea mantlha: Ka tlase ho kapa ho lekana le 0.5%

-0.07~-0.04

Feta

3

diteko- tsa dikamano

/

YNyn0

YNyn0

Feta

4

Ha ho{{0}tahlehelo ea thepa le thabo ea hona joale

/

I0:: fana ka boleng bo lekantsoeng

0.18%

Feta

P0: fana ka boleng bo lekantsoeng

(t:20 likhato)

1.500kW

Mamello ea ho se lahleheloe ke moroalo ke +10%

/

5

Litahlehelo tsa tahlehelo ea matla a motlakase le katleho

/

T:85 likhato

Mamello ea impedance ke ± 7.5%

Mamello ea tahlehelo ea boima kaofela ke +6%

/

Feta

Z%: boleng bo lekantsoeng

5.77%

Pk: boleng bo lekantsoeng

10.494kW

Pt: boleng bo lekantsoeng

11.994kW

Katleho e seng ka tlase ho 99.48%

99.48%

6

Teko ea Voltage e sebelisitsoeng

kV

HV&LV ho ea fatše: 10kV 60s

Ha ho ho putlama ha motlakase oa liteko

Feta

7

Teko ea ho mamella Voltage e kentsoeng

kV

Matla a sebelisoang (KV):

2 Ur

Ha ho ho putlama ha motlakase oa liteko

Feta

Nako:48

Hangata (HZ): 150

8

Leakage Test

kPa

Khatello e sebelisitsoeng: 20kPA

Nako:12h

Ha ho na leakage le che

Tšenyo

Feta

9

Tekanyo ea ho hanyetsa Insulation

GΩ

HV&LV ho ea fatše

11.6

/

10

Tlhahlobo ea oli

/

Matla a Dielectric

54.2 kv

Feta

Mongobo

9.9 mg / kg

Ntho ea ho senya

0.00356%

Furan Analysis

0.03 mg/kg

Tlhahlobo ea Khase ea Chromatography

/

 

1500 kVA mount transformer testing
1500 kVA mount transformer routine test

 

04 Ho paka le ho Romela

1500 kVA mount transformer  wooden packing
1500 kVA mount transformer shipping

05 Sebaka le Kakaretso

-mohato oa rona oa mekhahlelo e meraro-transformer e kentsoeng tšebetsong e sebetsa hantle ka 99.7% ka mokhoa oa eona oa hybrid foil{{3}moetso oa mapheo le IP68-e tiisitsoeng ka tanka ea tšepe e sa hloekang ea 304, e fanang ka lisebelisoa tse nang le kutu{8}}tharollo e sa senyeheng e netefalitsoeng bakeng sa lilemo tse 35 le lits'ebeletso tse kholo{1}mabopong{1}{1} tikoloho. Bophahamo bo hokahaneng (ka tlase ho bophara ba 2.5m) bo thusa ho kenya ka kotloloho sebakeng{18}liteishene tse fokolang, ha lisensara tse kopaneng tsa IoT li fokotsa nako ea karabo ea ho tima ka 40% ka ho lekola mojaro o itseng. E etselitsoe ho kopana le litekanyetso tsa IEEE C57.12.00 tse nang le 65 kA nako e khuts'oane ea ho mamella matla, e fokotsa litšenyehelo tsa tlhokomelo ea bophelo bohle ka 30% - lisebelisoa tse nolofalletsang ho finyella lipakane tsa sejoale-joale tsa marang-rang le ts'ebetso e tsitsitseng ea ho batla marang-rang a kabo.

1500 kVA pad mounted transformer

 