Ka ntshetsopele e potlakileng ya dithekenoloji tse kang UHV le kgokelo ya keriti e ntjha ya eneji, di-transformer-sesebediswa sa mantlha bakeng sa phetiso ya motlakase le phetoho ya motlakase{1}}di bohlokwa ho tshepeheng ya digridi tsa motlakase le boleng ba phepelo ya motlakase. Leha ho le joalo, hangata li-transformer li tobana le tšokelo ea overvoltage nakong ea ts'ebetso: ha motlakase oa ts'ebetso o feta matla a mangata a amohelehang a sebetsang, ho etsahala ntho e fetang ea overvoltage. Ts'ebetso ena ea nakoana ea voltage anomaly ha e potlakise botsofali ba motlakase oa motlakase feela, empa hape e ka baka karohano ea insulation ka kotloloho, e lebisang ho hloleheng ha lisebelisoa kapa likotsi tsa grid. Tlhahlobo e phethahetseng ea mekhoa ea ho hlahisa overvoltage le ts'ebetsong ea mehato e lebisitsoeng ea tšireletso e bohlokoa ho netefatsa ts'ebetso e bolokehileng ea li-transformer.
1. Sehlopha le Likotsi tsa ho Fetela ho Fetisisa
Overvoltage tsamaisong ea matla e arotsoe ka mefuta e meraro ea mantlha ho latela nako le sesosa:overvoltage ya nakoana, ho fetoha ho feteletseng, lesepakapaka (atmospheric overvoltage), e 'ngoe le e 'ngoe e na le maemo a fapaneng a susumetsang le litšobotsi tsa kotsi.
(1) Ho Fetola Ha Matla ka Nakoana
Overvoltage ea nakoana e bakoa haholo-holo ke {{0}litšitiso tsa boemo bo itseng tse kang-fase ground faults le grid resonance,' me li kenyeletsa power{2}}frequency overvoltage, resonance overvoltage, le arc grounding overvoltage.
- Resonance overvoltageho etsahala ha motlakase (mohlala, likhoele tsa transfoma, li-arc suppression) le matla (mohlala, mohala-ho{5}ho -bohato ba fatše, matla a thapo) ho grid ho etsa sedikadikwe sa resonant ka lebaka la liphoso kapa ts'ebetso ea khafetsa, e tsosang phetolo ea phetolo ea motlakase le matla a khoheli tlas'a maemo a itseng. Ferromagnetic resonance, e bakoang ke litšoaneleho tse sa tsitsang tsa motlakase oa transfoma, e kotsi ka ho khetheha, ka amplitudes ea motlakase e ka fetang makhetlo a 2-3 ho feta boleng bo lekantsoeng.
- Arc grounding overvoltagee hlaha ka lebaka la ho timela ha nako le nako ha arc e fela ka nako e itseng ka nako ea{0}}mehato e le 'ngoe ea litsamaiso tse se nang motheo kapa tsa arc suppression{1}}grounded coil. Sena se etsa hore ho be le oscillation ea motlakase, 'me maqhubu a overvoltage a fihla ho makhetlo a 2.5-3 ho matla a lekantsoeng le ho nka metsotsoana e mengata ho isa ho metsotsoana e mashome, ho baka tšenyo ea mokhathala habonolo.
(2) Ho Fetola Ho Fetisisa
Ho feto-fetoha ha matla ho feta tekano ho bakoa ke ho fetoha ha grid state ka tšohanyetso, joalo ka ho chencha-sesebelisoa se seholo, ho sa bule/ho koala lithapo tsa motlakase kapa li-transformer, kapa liphoso tsa ts'ebetso tse etsang hore motlakase o lokolloe ka potlako, tse lebisang phetohong ea tšohanyetso ea matla a makenete a motlakase le ho phahama ha motlakase. Ka tloaelo makhetlo a 3.0–4.5 a matla a motlakase a lekantsoeng, li-overvoltage tsena li sebetsa feela -mehato e fokolang ea matla empa li potlakisa mokhathala oa ho kenya letsoho ka ho pepeseha khafetsa ho marang-rang a sebelisoang khafetsa.
(3) Atmospheric Overvoltage (Lightning Overvoltage)
Atmospheric overvoltage e bakoa ke ho phatloha ha leru la lehalima, le arotsoe ka ho fetella ha lehalima le ho feteletsoa ha lehalima:
- Ho fetella ha lehalima ka ho otlolohaliphetho tsa lehalima le otlang lisebelisoa kapa li-conductors, 'me sena se hlahisa-amplitude pulse voltages.
- Lehalima le matlafalitsoeng ke matla a mangatae susumetsoa ke liphetoho tse potlakileng masimong a motlakase nakong ea ha lehalima le tsoa.
Naheng ea lehalima-ka boroa ho Chaena, ho feta 15% ea ho hlōleha ha li-transformer selemo le selemo ho bakoa ke ho tlala ha lehalima. Maqhubu a lehalima a na le maqhubu a phahameng haholo (1–4 μs) le maqhubu a phahameng (ka holimo ho 100 kHz), a nang le maqhubu a fihlang makhetlo a 8–12 ho feta boleng bo reriloeng{8}}esita le makhetlo a 50–200 ho feta boleng bo reriloeng maemong a feteletseng. Ha li-windings li hlasela, kabo e sa lekanang ea capacitance e etsa hore ho be le li-gradients tse feteletseng tsa voltage ho li-terminals tse kenang, tse sokelang ka ho toba interturn le main insulation.
Bongata ba tšenyo ea motlakase ho li-transformer bo ipapisitse le sebopeho sa maqhubu, bophahamo le nako: maqhubu a lehalima a makhutšoane-ka pele, li-voltage li telele-li-pulse tse ka pele, 'me maqhubu a matla a nakoana a tlase{2}}maqhubu a maqhubu a motlakase. Insulation ea lisebelisoa e tlameha ho lekoa khahlano le mefuta ena ea maqhubu. Lehalima le feteletseng le baka kotsi e kholo ka ho fetisisa ea ho robeha ha motlakase: ha maqhubu a lehalima a ata ho li-transformer, litšepe tsa melapo li qala ho tsoa, 'me maqhubu a setseng a feta ka har'a transformer ho ea fatše. Haeba ho na le sebaka sa motlakase pakeng tsa transformer le arrester, residual voltage oscillates 'me e phahama haufi le conductor, e ka' nang ea feta matla a setseng a sebatli. Ka hona, litšepe li lokela ho kenngoa haufi le li-transformer ka hohle kamoo ho ka khonehang. Ho feta moo, li-resonance le switching overvoltages, leha li le tlase ka amplitude, li na le nako e telele hape li ka baka ho senyeha.Phetoho e feteletsengha e bonolo haholo: ha lehlakore le phahameng{{0}li-voltage le otloang ke lehalima, "residual voltage" ea sebono e sebetsa ka lebelo le phahameng-le matsoelintsoeke a motlakase. Ho theoha ha matla a motlakase ho fetela sebakeng se tlase-motsokong oa motlakase ka mothapo o sa nke lehlakore, le ho phalla ho tloha tlase{4}}matlamang a motlakase a tlase a etsa hore ho be le matla a fetang makhetlo a mashome ho feta a setseng ha{5}}motsamao oa motlakase o phahameng, o baka ho senyeha habonolo.

2. Meloko ea Mechanism ea Overvoltage
(1) Switching Overvoltage: Transient Oscillation of Electromagnetic Energy
(2) Atmospheric Overvoltage: Tlhaselo e Moepa ea Maqhubu a Lehalima
(3) Tekanyo e Feteletseng ea Nako ea Nako: Kokello ea Matla le Ho Oscillation Tlas'a Tsitsitseng-Litšitiso tsa Naha
(1) Switching Overvoltage: Transient Oscillation of Electromagnetic Energy
Ha u sa nke-moroalo oa ho fetola{{1}sefetoleli se tlase{2}}e leng boemo bo atileng haholo ho li-grid tsa motlakase-e le mohlala, karolo ea bobeli-ka matla a lehlakore e na le tšusumetso e fokolang haholo lehlakoreng la mantlha ha e fetoloa, kahoo e ka hlokomolohuoa. Maqhubu a mantlhamola-ho{1}}bokhoni ba fatše (
)leinterturn capacitance (
)e be li-parameter tsa bohlokoa. Ho tloha
ho li-transformer tsa matla, phello ea bokhoni ba interturn e ka nolofalloa le ho feta bakeng sa tlhahlobo ea boleng.
Ha no-load transformer e tingoa, haeba che-load current e se{2}}zero, matla a khoheli a bolokiloeng ho "primary inductance"
(
) le matla a motlakase a bolokiloeng ho
(
) oscillate potolohong e bapileng e entsoeng ke
le
. Oscillation ena, e nang le maqhubu a Hz a makholo a 'maloa ho isa ho likete tse' maloa 'me e tšoarella feela matla a -khafetsa, e fetolela matla a matla a khoheli ho ea ho matla a motlakase ha hona joale a fihla ho zero, ho phahamisa capacitor voltage ho ea holimo le ho etsa hore ho fetoloe matla a mangata. Maqhubu a phahameng a matsoelintsoeke le mothapo o tlase-ho-ho eketsa matla a lefatše ho eketsa bophahamo ba motlakase, e hlalosang hore na ke hobane'ng ha li-switching overvoltage hangata li sa fete makhetlo a 4.5 ho feta matla a rekiloeng.
(2) Atmospheric Overvoltage: Tlhaselo e Moepa ea Maqhubu a Lehalima
Maqhubu a lehalima a na le maqhubu a moepa (1–4 μs) le maqhubu a phahameng (ka holimo ho 100 kHz), a nang le moepa o fihlang ho 500 kV/μs. Motlakase ona o fetohang ka potlako o etsa hore ho be le phallo e kholo ho li-winding. Ha maqhubu a lehalima a namela ho li-transformerterminals, a sebetsa joalo ka matshwao a phahameng-a maqhubu a phahameng,{7}}e phahameng. Ka maqhubu a phahameng, matsoelintsoeke a inductive reactance
e eketseha haholo, ha capacitive reactance
e fokotseha haholo, kahoo e phalla haholo-holo ka har'a khefutso le mothapo{0}ho ea ho{1}matla a fatše.
Kaha sebaka sa -voltage winding se haufi le konokono, tsela ea eona e kholo-ho{2}}ground capacitance e batla e lekana le potoloho e khuts'oane, e etsa hore e theohe hantle. Kabo ea motlakase ea maqhubu a lehalima hammoho le matsoelintsoeke e khethoa ke karo-karolelano ea
ho
: li-interturn capacitances tse haufi le theminale e kenang li nka nako e eketsehileng ka lebaka la ho tima, 'me li theha likhahla tse fetelletseng tsa motlakase moo thinyeho e 'maloa ea pele e ka bang le voltages makhetlo a makholo ho feta boleng bo reriloeng. Kabo ena ea motlakase e sa lekaneng ke sesosa sa mantlha sa ho putlama ha interturn insulation.
(3) Tekanyo e Feteletseng ea Nako ea Nako: Kokello ea Matla le Ho Oscillation Tlas'a Tsitsitseng-Litšitiso tsa Naha
Litšitiso tse fetelletseng tsa nakoana li hlaha ka lebaka la litšitiso tse - tse sa fetoheng, tse nang le maemo a mararo a tloaelehileng:
- Matla-a maqhubu a overvoltage: E bakoa ke-mohato o le mong o fosahetseng, ho hana thepa, kapa ho tjhaja mohala. Lisesetemeng tse theiloeng hantle, li-voltage tse phetseng hantle li nyolohela ho maemo a motlakase nakong ea{2}}mohato o le mong; Ho hana mojaro ka tšohanyetso ho eketsa lebelo la jenereithara le ho hlasimoloha ho sa fetoheng, ho phahamisa maqhubu a libese ho makhetlo a 1.5-1.8 ho boleng bo lekantsoeng ka metsotsoana e mengata.
- Resonance overvoltage: E etsahala ha inductance le capacitance li theha lipotoloho tse resontang ka lebaka la liphoso kapa ts'ebetso, e bakang phetoho ea motlakase-ea makenete. Ferromagnetic resonance, e tsamaisoang ke nonlinear transformer inductance, e baka maqhubu a maqhubu le amplitudes ea voltage ho fihlela makhetlo a 2-3 ho feta boleng bo lekantsoeng.
- Arc grounding overvoltage: E susumetsoa ke ho timela ha nako e itseng ha arc/ho rena ka nako e itseng-e nang le liphoso tsa mokhahlelo o le mong, e bakang ho sisinyeha ha motlakase. Arc extinction e lokolla matla a capacitive ho inductance, ha puso e eketsa pokello ea matla, e lebisang ho overvoltage makhetlo a 2.5-3 ho feta voltage e lekantsoeng.
3. Mehato ea Tšireletso ea Overvoltage
Sistimi ea ts'ireletso e holileng e ntlafalitsoe ho sebetsana le likotsi le mekhoa ea ho phatloha ho feteletseng, ho kopanya tšireletso ea lehalima e otlolohileng ka ntle, ts'ireletso ea mapheo a ka hare, le mehato e khethehileng ea tlatsetso ho netefatsa polokeho ea transformer.

(1) Tšireletso e Otlolohileng ea Lehalima ea Kantle
Boemong ba seteishene, tšireletso e tobileng ea lehalima ke mokhoa oa pele oa tšireletso:
- Melamu ea lehalima: Phapamisa maqhubu a lehalima fatše, ka tšireletso e laetsoeng ke bolelele le palo ea melamu. Melamu e mengata e eketsa tšireletso. Ho thibela li-counterattacks, li-grids tsa fatše li tlameha ho finyella litlhoko tsa ho hanyetsa le ho boloka libaka tse sireletsehileng ho tloha ho li-transformer le li-circuit breakers.
- Lithapo tsa lehalima: E kentsoe kaholimo ho mela e kenang haufi le liteishene, e fokotsa monyetla oa ho kenella ha maqhubu a lehalima. Ha lehalima le otla ka ntle ho mohala o sirelelitsoeng, tšitiso ea mohala e fokotsa sekhahla sa sebatli, 'me moea o kenang ho li-conductors o fokotsa lebelo le bophahamo ba maqhubu, o theola matla a masala a sebono bakeng sa khokahano e betere ea insulation.
(2) Tšireletso ea Motšoaroa: Mekhoa ea Tšireletso ea Core
Li-grid arresters ke tsona tse ka sehloohongGapless metal oxide arresters (MOA)leli-valve tse nang le lekhalo{0}lithiba tsa mefuta, e nang le molao-motheo oa khetho e arolelanoang: motlakase o lekanyelitsoeng oa " arrester rated voltage" ha oa lokela ho ba ka tlaase ho matla a phahameng a nakoana sebakeng sa ho kenya, 'me motlakase o sa nke lehlakore-point arrester rated ha oa lokela ho ba ka tlaase ho matla a phahameng a motlakase a transformer.
- Haeba motlakase o rekiloeng o le tlase haholo: Lithako tse khaohileng li ka 'na tsa hlōleha ho tima li-arcs nakong ea-mohato o le mong, o bakang ho phatloha; Li-MOA li theoloa ke ho monya matla ho feteletseng.
- Haeba motlakase o lekantsoeng o le holimo haholo: matla a ho ntša motlakase le masala a eketseha, a fokotsa ts'ireletso ea ts'ireletso.
Li-valve tse nang le lekhalo-li sebelisa li-valve discs tse se nang moeli tse bonts'ang molumo o phahameng ka tlas'a maqhubu a maholo a lehalima (ho boloka motlakase o tlase) le motlakase o tlase ka matla a tloaelehileng (matla a fokotsang{1}}maqhubu a latela a hona joale). Gapless MOAs, leveraging zinc oxide valve discs, suppress late current ntle le likheo, tse fanang ka karabelo e potlakileng, resadual voltage, le matla a holimo{3}e leng se etsang hore e be tsona khetho ea mantlha bakeng sa ts'ireletso ea transfoma.
Ho latela GB311.1-1997Insulation Coordination for High-Voltage Transmission and Distribution Equipment, li-transformer tsa 6kV li na le matla a ho mamella voltage ea 60kV, le li-transformer tsa 10kV 75kV. Bakeng sa litsamaiso tsa 6kV, YH5WS-10/30 MOA e na le matla a setseng Ka tlase ho kapa ho lekana le 30kV, e fanang ka ntlha ea khokahano ea ho kenella.
. Bakeng sa lisebelisoa tsa 10kV, YH5WS-17/50 MOA e fana ka lihlahisoa
, ho finyella litlhoko tsa ts'ireletso ea ts'ireletso.
Ka tloaelo E kholo ho feta kapa e lekana le 1.4 bakeng sa tšusumetso ea lehalima le E kholo ho feta kapa e lekana le 1.15 bakeng sa ho fetola maikutlo, ho nahanoa ka mofuta oa ho pata, kabo ea matla a mangata, le botsofali ba tikoloho.








(3) Insulation e Ntlafalitsoeng: Tšireletso ea Tlatsetso
Bakeng sa li-transformer tse mahareng le tse nyane (tse ka tlase ho kapa tse lekanang le 35kV), ho kenella ka matla ho matlafalitsoeng ke mokhoa oa bohlokoa oa tlatsetso: ho tiisa mapheo a phahameng-a matla le ho matlafatsa mohatsela ha li chenchana ho kena/terminal ho mamella likhahla tsa motlakase. Leha ho le joalo, mohatsela o motenya o sitisa ho qhalana ha mocheso 'me o fokotsa matla a ho phalla, e leng monyetla oa ho eketseha ha li-voltage -e leng se etsang hore sena se lokele feela bakeng sa maemo a tlase-ea motlakase, a theko{5}}a bobebe.
(4) Keketseho ea Boipheliso ba Matla: Phatlalatso ea Voltage e ntlafalitsoeng
Bophahamo bo phahameng ba interturn
e ntlafatsa ho tsamaisana ha motlakase: e kholoanyane
amanang le
e fokotsa li-voltage gradients le kotsi ea overvoltage. Mekhoa e joalo ka li-winding le li-capacitor screens li sebelisoa, haholo-holo libakeng tse nang le lehalima{1}}tse tloaelehileng joalo ka liteishene tsa lithaba kapa liteishene tsa wind farm{2}}up station.
(5) Tšireletso e sa nke lehlakore-Point Overvoltage Protection
Bakeng sa liteishene tsa lehalima-libakeng tse tloaelehileng tse nang le mehloli e le 'ngoe ea matla,-ho na le ho kenella ha leqhubu la lehalima ka mekhahlelo e meraro, 'me ho hloka tšireletso e tsepameng{2}}ea ntlha. Tharollo ea mantlha keho se nke lehlakore{{0}point MOAs, e sireletsang khahlanong le lehalima le ho fetola li-overvoltages ka karabelo e potlakileng, matla a tlase a setseng, le matla a phahameng a hona joale. Liprofinseng tse tloaelehileng-tse kang Guangdong le Guangxi, litekanyetso tsa ho kenya{2}}point MOA li feta 90%. E entsoe ka litekanyetso tse phahameng tsa motlakase, e lula e tšepahala nakong ea ho fetoha ha maemo a manyane-'me e mamella matla a 1x-mohato oa maqhubu a motlakase nakong ea-mohato o le mong.
Bakeng sa li-fift shifts tse feteletseng-( overvoltage E kholo ho feta kapa e lekana le 2x power-frequency phase voltage), ho sebelisoa "arrester + horizontal rod gap" scheme: ba ts'oarang ba sebetsana le lehalima/switching overvoltage, ha likheo li fokotsa matla a phahameng{4}}frequency power{5}frequency arrest.
(6) Tšireletso e Khethehileng bakeng sa-Li-Winding Transformers
Tse tharo-li- winding transformer (tse phahameng, tse mahareng, tse tlase) li tobana le likotsi tsa ho felloa ke matla ha electrostatic induction overvoltage, haholo ha li- windings tse tlase- li butse. Maqhubu a tlalima karolong e phahameng-ea fetisoang ka lehlakoreng la motlakase ho ea ho tse tlase-maemelong a maqhubu a motlakase ka ho kopana ha electrostatic coupling le electromagnetic induction, 'me matla a tlase a fatše a phahamisa motlakase oa electrostatic, ho ts'osetsa. Lits'oants'o tse nang le-voltage windings tse tlase li thibela ka kotloloho matla a fetang a matla.
Ho feta moo, zero-motlakase oa tatelano ho tloha ho asymmetric faults kapa breaker malfunctions o fetela ho tlase-voltage windings ka capacitive coupling. Ho fokotsa sena, ho sebelisoa li-breaker tse phahameng-synchronism breaker, 'me li-capacitor tse 3 tsa Y{5}connected capacitor li kentsoe marokhong a libese tse tlase{6}}ho eketsa bokhoni ba ho ea fatše, ho monya matla a mangata le ho fokotsa bophahamo/boemo.
7
Mehala e melelele ea {{0}voltage feeder feeder line' a ka hlaseloang habonolo ke lehalima. Ha e otloa, maqhubu a lehalima a susumetsaphetolo e fapaneng ya phetolomaqhubung a phahameng{{0}motlakase oa motlakase (makhetlo a 2-3) ka ho kenella ka motlakase, ho ts'osetsa. Low{{4}voltage side MOAs e hatella impulse flux -voltage windings e tlase, e thibela phetiso e fetang matla. Li-transformer tse nang le lihlopha tsa khokahanyo tsa Y/Zn11 ka tlhaho li hatella phetolo e feteletseng, li fana ka tšireletso e matlafalitsoeng ha li tsamaisana le{8}}li-voltage arrester.
(8) Mehato e meng e Khethehileng ea Tšireletso
Bakeng sa maemo a khethehileng a overvoltage, mehato ea tlatsetso e kenyelletsa:
1. Arc Suppression Coils: Ho hatella Arc Grounding Overvoltage
Ka li-coil tse sa thekeseleng kapa tse sa thekeseleng{0}}li-grounds tsa kabo ea li-coil, li-arc suppression coil li lefella capacitive current ka nako e le 'ngoe{1}}ea liphoso tsa mohato, ho fokotsa phoso le ho thibela ho busa ka linako tse ling. -likhoele tsa ho lokisa li latela{4}}liphetoho tsa nako ea 'nete, ho lekanyetsa ho overvoltage ea arc ho Tlas'a kapa ho lekana le 2x rated voltage.
2. Reactors: Limiting Switching le Power-Frequency Overvoltage
Series reactor: Thibela motlakase oa motlakase oa motlakase oa hona joale le oa ho fetola motlakase ka ho eketsa inductance ea potoloho ho fokotsa litekanyetso tsa hona joale tsa phetoho. Ka mohlala, li-reactors tse mahlakoreng a tlase-voltage ea li-transformer tse kholo li lekanyetsa inrush ea hona joale ho 2–3x rated current.
Shunt reactor: Nka matla a capacitive reactive lithapong tse telele tse telele- tsa motlakase, ho fokotsa matla a -khafetsa ho tsoa ho lithapo tsa ho tjhaja. Methapong ea 500kV, li-reactor tsa shunt li fokotsa matla a ho feta ho feta kapa a lekanang le matla a matla a 1.3x, a sireletsang li-transformer ka tsela e sa tobang.
3. Tlhōlisano ea Tsamaiso ea Grounding: Ho Fokotsa Phallo ea Motheo ea Motheo
Li-grid tse ntlafalitsoeng (mohlala, li-electrode tsa koporo-li-clad steel poles) li fokotsa khanyetso ea fatše ho Ka tlase ho kapa ho lekana le 0.5Ω, ho fokotsa ho phahama ho ka bang teng nakong ea lehalima le ho thibela litlhaselo. Libakeng tse tloaelehileng tsa lehalima-, "independent grounding + equipotential bonding" e fokotsa liphapano tse ka bang teng.
4. Varistors le Surge Protectors (SPD): Tlase-Tsireletso ea Matla a Felletseng
Li-Varistors (MOV) kapa li-SPD tse tlase-li-voltage feeder outlets li hatella lehalima le ho feto-fetoha ha matla, ho thibela phetolo e feteletseng. Lisebelisoa tsena li fana ka karabelo ea nanosecond le residual voltage e tlase, e loketseng bakeng sa ts'ireletso e tlase-ea motlakase oa phepelo ea motlakase.
Tšireletso ea SCOTECH Transformer Overvoltage: Lethathamo le Feletseng-Lethathamo la Tharollo ea Boemo
Lethathamo lena le sebetsana le litlhoko tsa ts'ireletso ea overvoltage ho pholletsa le maemo a motlakase le maemo, ho latela mohopolo oa mantlha oaTšireletso e tobileng ea lehalima + core voltage limiting + khatello e khethehileng + tsamaiso ea tsamaiso. E hokahana le likarolo tsa moralo oa SCOTECH, mehato ea ts'ireletso e ts'oanang le litharollo tse ikhethileng bakeng sa ts'ebeliso e tobileng moralong oa projeke, boitlamo ba bareki le khetho ea sehlahisoa.
|
Boemo ba Kopo |
Maemo a Ts'ebetso a mantlha |
Mehato ea Tšireletso ea mantlha |
SCOTECH e Ikamahanya le maemo |
|
Outdoor Substation/Wind Farm Step-Up Stations |
Kotsi e phahameng ea lehalima e tobileng; lehalima le kopantseng / switching overvoltage; ho se nke lehlakore{0}likotsi tse ka bang teng tsa ho fetoha |
1. Tšireletso e tobileng ea lehalima ka ntle |
1. Tloaeloli-winding/capacitor skriniliteisheneng tse kenang tsa li-transformer ho ntlafatsa kabo ea motlakase; |
|
Liteishene tsa Kabo ea Litoropo |
Ts'ebetso ea ho chencha khafetsa; phetoa khafetsa overvoltage; ha ho na lehalima le tobileng empa kotsi e bakoang ke lehalima; kotsi e tlase ea resonance |
1. High{1}}valve e nang le lekhalo le lehlakoreng{2}}ea mofuta/MOA |
1. Mohatla o motenya oa interturn/ground insulationho litheminale tse kenang tse kenang{{0}tse nang le maqhubu a phahameng a matla ho thibela mokhathala o feteletseng; |
|
Li-Transformer tsa Kabo ea Mahaeng |
Kotsi e phahameng e tobileng / e bakoang ke lehalima; matla a maholo a arc grounding overvoltage; mehala e melelele ea mahaeng, kotsi e phahameng ea phetoho e fetang matla |
1. |
1. PhahamisaLi-transformer tsa lihlopha tsa Y/Zn11ho hatella ka tlhaho ho feto-fetoha ho feteletseng; |
|
Industrial Plant inehetseng Transformers |
Multi{{0} winding electrostatic induction overvoltage; ho fetola overvoltage ho tloha ho fetola mojaro; kotsi-ea tatellano ea matla a khokahanyo; low{{2}voltage inverse transformation overvoltage |
1. Batšoantšisi ba ikemetseng bakeng sa leqhubu le leng le le leng |
1. Insulation e matlafalitsoeng e ikemetsengsebakeng se seng le se seng sa matsoelintsoeke: optimized capacitance distribution on high-mahlakoreng a feberu, a teteaneng a fatang fatše ka mahlakoreng a -tlase; |
|
-Li-Transformer tsa Khale ea Khale |
Matla-maqhubu a fetelletseng a ho tjhaja mohala; phetoho e kholo ea overvoltage ho tloha ho feto-fetoha ha mohala; leqhubu la leqhubu la lehalima le hlabang |
1. Li-MOA tsa{1}tse phahameng haholo mahlakoreng{2}a matla a phahameng |
1. Tloaelomatla a phahameng a mamella li-transformere ikamahantse le-moepa o molelele oa lehalima; |
|
Liteishene tsa Compact Substations/Seteishene sa Transformer se seng se entsoe |
Ha ho na tšireletso e tobileng ea lehalima e ikemetseng; ho kopanya lisebelisoa tse phahameng, libaka tse nyenyane tsa motlakase; lehalima le susumelitsoeng + ho feto-fetoha ha ka hare ho overvoltage |
1. Li-MOA tse kopantsoeng ka hare ho khabinete |
1. Maemo a kopantsoeng a ho ts'oarabakeng sa zero-distance transformer-kopano ea mots'oari; |
Tlatsetso Notes
- Litharollo tsohle li tšehetsaKhokahano e kopaneng ea li-transformer tsa SCOTECH le likarolo tsa ts'ireletso, ho fokotsa khetho ea bobeli ea bareki le litšenyehelo tsa ho kenya.
- Bakeng sa maemo a feteletseng (mohlala, libaka tse matla tsa lialuma, bophahamo bo phahameng, tšilafalo e matla), likhetho tse ntlafalitsoeng joalo katse thibelang-pollution insulation coatings,{1}lits'oants'o tse phahameng tsa hona joale, le litheminale tse ikemetsenglia fumaneha.
4. Qetello
Tšireletso ea overvoltage ea Transformer ke mosebetsi o hlophisitsoeng oa boenjiniere o leka-lekaneng bokhoni ba tekheniki le katleho ea moruo, ho nahanoa ka sebopeho sa grid, tikoloho ea ts'ebetso le litšobotsi tsa lisebelisoa. Ho tloha ka ntle ho tšireletso ea lehalima ho ea ho sebatli sa ka hare le ho matlafatsa ts'ebetso ea ho kenya letsoho, ho tlatsitsoe ke li-coil le li-reactors tsa khatello ea li-arc, ho thehoa marang-rang a tšireletso a pharaletseng. Tsoelo-pele ea nako e tlang ho mahlale a marang-rang a dijithale le litheknoloji tsa tlhahlobo ea marang-rang li tla tsamaisa kholo ea ts'ireletso ea transvoltage ho litsamaiso tse bohlale, tse sebetsang, tse ralang motheo o tiileng bakeng sa li-grid tsa motlakase tse tšepahalang haholoanyane.