Tataiso ea Ts'ebetso ea Compact Substation le Tataiso ea Ts'ebetso

May 11, 2026

Siea molaetsa

compact substation

 

 

 

 

1. Selelekela

 

 

Liteishene tse nyenyane (tse tsejoang hape e le li-package substations kapa transformer compact stations) ke litsi tse kopantseng tsa kabo ea motlakase tse kopanyang-voltage switchgear, distribuerar transfoma, low-li-voltage switchboards, likhokahano, le lisebelisoa tse thusang ka har'a kopano e le 'ngoe e kentsoeng. Femekeri ena{{3}e ahiloeng, ea mofuta oa{4}}liyuniti tse lekiloeng li fana ka tharollo ea ho theoha ha matla a mahareng-motlakase ho ea ho maemo a tlase-ea phepelo ea motlakase, e sebetsa e le khokahano ea bohlokoa lipakeng tsa mehloli ea mantlha ea motlakase le basebelisi ba ho qetela lits'ebetsong tsa matla a bolulo, tsa khoebo, tsa indasteri le tse ka nchafatsoang.

E etselitsoe hore ho kenngoe ka ntle libakeng tsa sechaba, liteishene tse nyenyane li fana ka melemo e mengata ho feta liteishene tsa khale tse hahiloeng--ka har'a libaka. Kaho ea bona ea-e entsoeng ka mokhoa o itekanetseng e fokotsa{4}}mesebetsi ea sechaba, e khutsufatsa nako ea ho kenya ho tloha libekeng ho isa ho matsatsi a seng makae, e fokotsa litšenyehelo tsa morero, 'me e fokotsa sebaka se hlokahalang bakeng sa thepa ea motheo ea kabo ea motlakase. Ho feta moo, liteishene tsa compact substation li lekoa ho latela maemo a machaba a kang IEC 62271-202, e netefatsang maemo a holimo a tšireletso bakeng sa basebetsi le lisebelisoa ka likarolo tse kenyeletsang likarolo tsa ka hare tsa arc le libaka tse notlehang ka botlalo, tse theiloeng fatše.

Sepheo sa tataiso ena ke ho fana ka litšupiso tse felletseng bakeng sa basebetsi ba nang le litsebo ba amehang ho kenngoeng, ho fana ka khomishene, ho sebetsa le ho hlokomela liteishene tse nyenyane tse kopanetsoeng. Lintlha tse hlahisitsoeng mona li kopanya mekhoa e metle ea indasteri, likhothaletso tsa moetsi oa lisebelisoa, le litekanyetso tse sebetsang tsa taolo hore e be moralo o kopaneng, o sebetsang.

 

 


 

 

2.Pele{1}}Tokisetso ea ho Kenya

High/low voltage preinstalled substation

2.1 Khetho ea Sebaka

Khetho ea sebaka se loketseng sa ho kenya e etsa motheo oa phepelo e atlehileng ea compact substation. Lintlha tse 'maloa tsa bohlokoa li tlameha ho hlahlojoa pele ho phethoa khetho ea sebaka.

  • Ho fihlella.Sebaka sa ho kenya se tlameha ho lula se fumaneha ka linako tsohle bakeng sa basebetsi ba tlhokomelo le likoloi tse arabelang tšohanyetso. Ho tlameha ho bolokoe litsi tse lekaneng ho pota-pota ka mahlakoreng 'ohle a seteishene ho lumella basebetsi ho sebetsa ka mokhoa o sireletsehileng le lisebelisoa hore li tsamaisoe le ho tsoa kamoo ho hlokahalang.
  • Maemo a fatše.Sebaka sena se tla ba sebakeng se phahameng, ho qoba libaka tse tlase-tse ka bang kotsing ea likhohola kapa ho bokellana ha metsi. Matla a ho beha mobu a tlameha ho lekana ho ts'ehetsa boima ba seteishene, se ka tlohang ho lithane tse ka bang 10 ho isa ho tse 17 tsa metric ho ipapisitse le tlhophiso le lisebelisoa tse kenyellelitsoeng. Libaka tse nang le mekhoabo e sa tsitsang, libaka tse atisang ho hoholeha ha mobu, le mobu o nang le matla a mangata a ho noa metsi li tla qojoa.
  • Mokelikeli oa metsi.Ho hlokahala drainage e lekaneng ea tlhaho kapa e entsoeng ka boenjineri ho thibela metsi ho kopana ho potoloha motheo oa seteishene. Metsi a emeng a ka senya ho kenella ha motlakase, a potlakisa ho bola ha likarolo tsa tšepe, 'me a baka likotsi tsa polokeho bakeng sa basebetsi. Sebaka sa ho kenya se lokela ho hlophisoa ho lebisa metsi a ka holim'a metsi ho tloha moeling oa seteishene.
  • Haufi le Mojaro le Khokahano ea Marang-rang.Seteishene se senyenyane se lokela ho behoa haufi le mojaro oo se o sebeletsang ho fokotsa tahlehelo ea motlakase le ho theoha ha motlakase haufi le li-feeders. Ka nako e ts'oanang, sebaka sena se tlameha ho nolofatsa phihlello e utloahalang bakeng sa khokahanyo ea thapo e mahareng- le marangrang a utility.
  • Ho Hlakola Likotsing.Seteishene se senyenyane se tlameha ho ba sebakeng se sireletsehileng ho tloha likotsing tsa mollo, tikolohong ea liqhomane, mehloli ea khoho ea lik'hemik'hale, le libaka tse thothomelang haholo. Ka tloaelo ho hlokahala tumello e fokolang ea 5,000 mm ho tloha linthong tse tukang. Sebaka se tla boela se boloke sebaka se lekaneng sa ho tsoa lifateng, meahong le litšitisong tse ling tse ka sitisang moea kapa tsa baka likotsi tse oelang.
  • Mehopolo ea Tikoloho.Maemo a tikoloho sebakeng sa ho kenya a tlameha ho oela ka har'a mekhahlelo ea ts'ebetso e boletsoeng bakeng sa lisebelisoa. Maemo a tloaelehileng a compact a etselitsoe hore a sebetse maemong a mocheso ho tloha ho −20 degrees ho ea ho +45℃, ka mongobo o itseng oa 15% ho isa ho 95% (o sa{5}}noa), le bophahamong bo sa feteng 1,000 metres ka holim'a bophahamo ba leoatle.

 

2.2 Litlhoko tsa Motheo

Hang ha setša se khethiloe, ho tlameha ho hahuoa motheo o loketseng ho tšehetsa setsi ka mokhoa o sireletsehileng le ka nako e telele. Moralo oa motheo o tlameha ho ikarabella bakeng sa lintlha tse latelang.

  • Load Bearing Capacity.Motheo o tla etsoa enjenere ho ts'ehetsa boima bo felletseng ba seteishene, ho kenyeletsoa likarolo tsohle tsa kahare joalo ka transfoma, switchgear, le lisebelisoa tse ling. Bokhoni ba ho jara ba motheo bo tlameha ho ba bonyane 1,000 Pa, le hoja litlhoko tse khethehileng li fapana ho latela maemo a mobu le boima ba setsi.
  • Maemo a Mobu.Mofuta le matla a ho jara a mobu sebakeng sa ho kenya li susumetsa ka ho toba moralo oa motheo. Libakeng tse nang le maemo a mobu a nang le bokhoni, bethe ea lehlohlojane kapa letlapa la konkreite le matlafalitsoeng le ka lekana. Moo ho nang le letsopa le atolositsoeng, lehlabathe le hlephileng, kapa maemo a thata a tekheniki, ho ka hlokahala metheo e tebileng joalo ka maballo a konkreite kapa metheo ea qubu. Libakeng tse thata, motheo o lokela ho behoa holim'a liqubu ho thibela ho rarolla phapang.
  • Botebo ba Serame.Motheo o tlameha ho hahuoa ka botebo bo lekaneng ho thibela ho phahama ha serame, se ka bakang sebaka se sa tsitsang sa bolulo, ho se lumellane ha mamati le khatello ea sebopeho. Likhoutu tsa meaho ea lehae hangata li hlakisa botebo bo hlokahalang ba serame sebakeng sa tikoloho.
  • Litokisetso tsa ho Kena ka Cable.Motheo ona o tla kenyelletsa{0}}mehaho e entsoeng esale pele, likotopo, kapa liforo tse kenyang likhoele tsa motlakase tse kenang le tse tsoang le lithapo tsa taolo. Menyako ena ea li-cable e lokela ho hlophisoa hore e ikamahanye le lintlha tsa keno tsa lithapo sebakeng se kampetsoeng sa seteishene, joalo ka ha ho boletsoe litšoantšong tsa tlhophiso e akaretsang ea moetsi. Bakeng sa-voltage switchgear, lithapo tsa lithapo tsa litekanyo tse loketseng li lumella lithapo hore li phuthoe sebakeng pele li emisoa.
  • Mefuta ea Motheo.Litlhophiso tse 'maloa tsa motheo li fumaneha ho latela maemo a sebaka le litlhoko.
  • Bakeng sa ho kenya mobung o tsitsitseng,{0}o kolobisitsoeng hantle, lehlohlojane le lekantsoeng le ka sebetsa e le motheo. Moalo oa lehlohlojane o lokela ho atoloha bonyane 500 mm ka nqane ho sebaka sa seteishene ka nqa tsohle, ka kakaretso ea sebaka sa lehlohlojane sa bolelele ba seteishene le 1,000 mm ka bophara ba seteishene le 1,000 mm.
  • Bakeng sa maemo a boima haholo, letlapa la konkreite le tiisitsoeng la botenya bo loketseng (hoo e ka bang 150 mm) ka ho otloloha{1}}setšeng le fana ka sebaka se tsitsitseng, sa boemo bo holimo. Letlapa le lokela ho hahoa ka menyetla ea ho kenya lithapo 'me le tlameha ho mamella boemo bo ka hare ho ± 1 mm ho feta 1 mithara.
  • Maemong a hlokang ho kengoa sebakeng se phahameng kapa moo ho amehang sebaka sa fatše, maballo a tšehetso a konkreite a tšeloa ka har'a liforo tse peli moo ho nang le serame- kapa liqubu tsa konkreite tse behiloeng k'honeng e 'ngoe le e 'ngoe ea seteishene, li fana ka botsitso bo ntlafetseng.
  • Ho Tiisa le Tšireletso ea Tšireletso.Ka mor'a hore ho kenngoe lithapo ho phetheloe, liphahlo tsa motheo li lokela ho koaloa ho thibela ho kena ha litoeba, likokoanyana le mongobo. Likhetho li kenyelletsa ho tlatsoa ka lehlabathe kapa lehlohlojane tse lateloang ke topping e tšesaane ea samente, kapa morero oa ho kenya{1}lijana tsa sekoaelo tse fepelang seteishene.

 

2.3 Tekolo ea Pele ho-Tlhahlobo ea Lisebelisuoa tsa ho Instola

Pele o qala ho kenya, seteishene se ka tlaase le likarolo tsa sona li tla hlahlojoa ka botlalo ho netefatsa ho phethahala le ho tseba tšenyo leha e le efe e bileng teng nakong ea lipalangoang.

  • Tlhahlobo ea Kantle.Hlahlobisisa sebaka se kampetsoeng bakeng sa tšenyo e bonahalang karolong e ka ntle, makhopho, makoeba, litšepe tse phatlohileng, kapa litiiso tse senyehileng. Netefatsa hore{1}}anti-corrosion coating e lula e tsitsitse, u ela hloko lihuku, mathōko, le libaka tsa ho phahamisa.
  • Tlhahlobo ea ka hare.Bula liphaposi tsohle 'me u hlahlobe likarolo tsa kahare ho kenyelletsa switchgear, transformer le lisebelisoa tse thusang bakeng sa matšoao a tšenyo, likarolo tse hlephileng kapa lintho tse kantle ho naha. Netefatsa hore likhokahano tsa motlakase li lula li sirelelitsoe ka thata le hore likhoele li tsamaisitsoe hantle le ho ngoloa lileibole.
  • Netefatso ea Litokomane.Netefatsa hore litokomane tsohle tse hlokahalang li teng, ho kenyeletsoa libuka tsa ho kenya, litšoantšo tsa potoloho, bili ea thepa, le lintlha tsa tiisetso. Netefatsa hore data ea nameplate e lumellana le litlhaloso tse laetsoeng, ho kenyeletsoa matla a rekiloeng, maemo a voltage, nomoro ea serial, le letsatsi la tlhahiso.
  • Tlhahlobo ea lisebelisoa.Netefatsa hore lisebelisuoa tsohle tse fanoeng li na le tlaleho, ho kenyeletsoa le mehatla ea ho sebetsa, litšoelesa tsa cable, liatlana tse sireletsang, setima-mollo, le likarolo tse ling tsa boikhethelo tse boletsoeng taelong.

 

 


 

 

compact substation transport

3. Lipalangoang le ho Tšoara

Mekhoa e nepahetseng ea lipalangoang le ea ho sebetsana le eona e bohlokoa ho thibela tšenyo ea setsi sa motlakase nakong ea ho tsamaea ho tloha fekthering ho ea sebakeng sa ho qetela sa ho kenya.

3.1 Maikutlo a Lipalangoang

Liteishene tse nyane li tsamaisoa ho tloha fekthering ntle le ho phutheloa ka botlalo, leha mehato ea ts'ireletso joalo ka litšireletsa tsa sekhutlo sa lepolanka le filimi ea polasetiki e ka sebelisoa bakeng sa sebaka se selelele kapa ho romelloa kantle ho naha.

Nakong ea lipalangoang tsa 'mileng, seteishene se tlameha ho tiisoa ka thata ho teraka kapa tereilara ho thibela ho sisinyeha, ho thefuleha, kapa tšenyo ea tšusumetso. Mabala a tšehetso ea lipalangoang a ka bang bolelele ba 75 mm le bophara ba 150 mm a lokela ho behoa ka tlas'a seteishene maboteng a karohano. Mahlo a khoele a ka tlosoang a kentsoeng lihukung tse kaholimo tsa sebaka se kampetsoeng a fana ka lintlha tse sireletsehileng bakeng sa marapo a thibelang. Lithapo ha lia lokela ho fetisoa holim'a marulelo a setsi, kaha sena se ka senya mohaho oa marulelo le ho qeta holimo.

Bohare ba matla a khoheli a seteishene ha se bohare ba yuniti, haholo ha transformer e le fektheri-e kentsoeng ka har'a sebaka se kampetsoeng (e leng se ka bang teng bakeng sa litlhophiso tse itseng). Lisebelisoa tsa lipalangoang le mekhoa ea ho boloka li tlameha ho ikarabella bakeng sa kabo ena ea boima ba offset.

 

3.2 Ts'ebetso ea ho phahamisa

Ho phahamisetsa seteishene se senyenyane ho tloha koloing ho ea ho motheo oa sona ho hloka moralo o hlokolosi le ts'ebetso ho netefatsa polokeho ea basebetsi le bots'epehi ba lisebelisoa.

Boholo ba li-substations tsa compact li fanoa ka mahlo a phahamisang kapa masoba a khomaretsoeng marulelong kapa foreimi ea sebopeho ka ho khetheha bakeng sa ts'ebetso ea ho phahamisa. Likoti kaofela li tla sebelisoa ha u tsamaisa sesebelisoa{1}ha ho sebaka sa ho phahamisa se lokelang ho tloheloa, kaha phallo e sa leka-lekaneng ea mojaro e ka etsa hore seteishene se kobehe kapa se sothe.

Nakong ea ho phahamisa, boholo bo boholo ba likhoele tse phahamisang hook ea crane ha ea lokela ho feta likhato tse 60. Bolelele ba thapo e 'ngoe le e 'ngoe e phahamisang e lokela ho fetoloa e le hore seteishene se seke sa sekamela ho feta likhato tse 3 nakong ea ho phahamisa. Lithapo tsa ho phahamisa tse hlophisitsoeng hantle li netefatsa hore setsi sa matla a khoheli se lula ka ho toba ka tlas'a hook ea crane, ho thibela ho thekesela ho sa laoleheng kapa ho tlama.

Crane le lisebelisoa tsa ho phahamisa li tlameha ho lekanyetsoa bakeng sa mojaro o lekaneng ho sebetsana le boima bo felletseng ba seteishene, se tlohang ho lithane tse 10 tsa metric (ntle le-voltage switchgear) ho fihla ho 17 metric tons (e nang le switchgear le transformer ka botlalo). Ka tšohanyetso, ho sisinyeha ha methapo nakong ea ho phahamisa ho tlameha ho qojoa.

Basebeletsi ha baa lokela ho ema ka tlas'a mojaro nakong ea mesebetsi ea ho phahamisa, leha e le hore motho leha e le ofe ha aa lokela ho tsamaea kapa ho ema marulelong a seteishene ka nako efe kapa efe. Lithapo kapa lihakisi tse phahamisang li se ke tsa lahleloa marulelong, kaha sena se ka senya pente le bokaholimo.

 

3.3 Maemo a Motheo

Ha setsi se phahamisitsoe 'me se behiloe holim'a motheo o lokiselitsoeng, se tla theoleloa butle-butle ebe se tataisoa sebakeng sa sona sa ho qetela. Meeli ea motheo e tlameha ho hlokomeloa ho netefatsa teka-tekano e nepahetseng ea ho kena ha cable le ho buleha ha mamati.

Ka mor'a hore seteishene se senyenyane se behoe, boemo bo tla netefatsoa. Liphetoho li ka etsoa ho sebelisoa lipoleiti tsa ho paka ka tšepe ka tlas'a likhutlo tsa moralo oa motheo. Liboutu tsa ankora tsa boholo bo loketseng le mofuta li tla kengoa ho tiisa seteishene ho motheo, ka litorque tse tiisang tse sebelisoang joalo ka ha ho boletsoe ke moetsi.

 


 

4. Mekhoa ea ho kenya

compact substation installation

4.1 Sebaka sa Sebaka se Koaletsoeng le ho Sireletsa

Ka seteishene se behiloeng holim'a motheo 'me se lokisoa ho ea boemong, se tla kenngoa sebakeng. Likoti tse ka har'a foreimi ea motheo li ka sebetsa e le litempele tsa ho cheka masoba a ankora bolt motheong oa konkreite. Li-bolts tsa ankora li tla fetisetsoa ho litekanyetso tse boletsoeng litokomaneng tsa ho kenya.

Haeba seteishene se na le{0}marulelo a kentsoeng, ha ho hlokahale hore ho tlosoe marulelo. Litlhophisong tseo transformer e sa kang ea kenngoa fekthering-, marulelo a tlameha ho tlosoa ho lumella transfoma sebaka pele ho tsoela pele ka likhokahano.

 

4.2 Ho Kenya Cable le Lihokelo

Ho kenya lithapo ho etsa karolo e kholo ea-mosebetsi oa motlakase sebakeng seo 'me ho hloka tlhokomelo e hlokolosi ho netefatsa ts'ebetso e tšepahalang, e telele{1}.

Keno ea Cable.Lithapo tsa -motlakase oa motlakase o mahareng,{1}}kabo ea motlakase o tlase-, phepelo ea motlakase ka hare, tšireletso e sirelletsang fatše, le lithapo tsa taolo li tla tsamaisoa ka litsela tse keneng ka har'a foundation le substation base plate. Likenyo tsa li-cable hangata li fumaneha ka tlase ho seteishene ho thusa ho felisoa ka kotloloho ho li-switchgear le li-transformer.

Theha ea Cable.Pakeng tsa-voltage switchgear le li-inverter tse hoketsoeng, lithapo tse tharo{1}}li hloka hore ho be le tlhophiso e khethehileng. Moo ho nang le lithapo tse tharo tse arohaneng tsa lithapo tsa AC (mohlala, likanale tse arohaneng tsa lithapo), sebaka se pakeng tsa lithapo tsa cable se tlameha ho ba bonyane bophara ba thapo ea AC habeli ho thibela ho se leka-lekane ha hona joale. Mokhanni oa mohala o le mong ho tloha karolong e 'ngoe le e' ngoe (L1, L2, le L3) o lokela ho behoa ka lekhetlo le leng le le leng ho netefatsa hore kabo e leka-lekaneng ea hona joale.

Ho Felisoa ha Cable.Ho tima likhebula tse mahareng- ho tla etsoa ho sebelisoa lisebelisoa tse loketseng tsa ho emisa tse tsamaisanang le mofuta oa switchgear bushing. Mekhoa ea ho felisa e kenyelletsa ho honyela ha serame, ho honyela ha mocheso, le lisirela tse ka sebelisoang hape tse sireletsang. Bakeng sa ho emisa ho batang, 'mele oa ho felisa o fektheri-o atolosoa holim'a motheo o tlosoang; ha mokokotlo o tlosoa, 'mele oa rabara oa silicone o honyela ka mokhoa o sireletsehileng haufi le ntlha e lokiselitsoeng, 'me o etsa hore ho be le tiiso e tiileng ea metsi{4} ntle le ho hloka mocheso kapa lisebelisoa tse khethehileng.

Bakeng sa lisirela tse khonang ho sebelisoa hape, seleifa se kenyellelitsoeng le khiti ea ho felisa se tlameha ho fetana ka 50 mm mohatong ka mong. Karolo e kopantsoeng ea bushing e tlameha ho hloekisoa ka ho feletseng, ka ho khetheha e sebelise thepa e senyang, ho tlosa ntho leha e le efe ea ho lokolla silicone e ka bang teng holim'a bushing. Mohato ona o bohlokoa ho etsa bonnete ba hore -tiiso e tiileng ea metsi ka mor'a hore pheliso e felile.

Ha o emisa likhoele ho lihlahla tsa transformer kapa li-sockets tsa switchgear, litekanyetso tse nepahetseng tsa torque li tla hlokomeloa. Ka mohlala, ho lokisa liboutu bakeng sa li-ring switch bushings (hangata li-bolt tsa M16 hex) ho hloka torque e tiisang hoo e ka bang 95 Nm.

Cable Clamping le Tšehetso.Lithapo li tla tiisoa hantle kapa li tšehelitsoe pele li emisoa ho qoba ho beha khatello ea kelello holim'a lihlahla le ho emisa. Tšehetso e sa nepahalang e ka baka tšenyo ea lihlahla le ho hloleha qetellong. Bakeng sa lithapo tse tsamaisitsoeng ho li-switchgear tse mahareng-tse-tse kentsoeng pele{3}} tse khomaretsoeng maboteng a likarolo li fana ka ts'ebetso ea nako e telele.

Tšireletso Screen Earthing.Sekirini sa tšepe se sireletsang sa thapo e 'ngoe le e 'ngoe ea- ea motlakase se tla behoa qetellong ea switchgear feela. Ho thella ha lefatše lipheletsong ka bobeli ho ka etsa hore ho be le maqhubu a potolohang a bakang ho futhumatsa le ho fokotsa matla a cable.

 

4.3 Ho kenya Transformer

Haeba seteishene sa compact substation se fanoa ntle le feme-transformer e kentsoeng, transformer e tlameha ho kengoa ka mor'a hore sebaka se kampetsoeng se behoe. Marulelo a tla phahamisoa ka hloko ho fana ka monyetla oa ho kena phaposing ea transformer. Lisebelisoa tsa ho phahamisa tse bolokiloeng ka kamoreng ea transformer li ka sebelisoa bakeng sa ho tlosa marulelo, ho khomarela bohareng ba gable ka 'ngoe ea marulelo.

Transformer e tla phahamisetsoa ka phaposing ea transfoma ebe e behoa fatše holim'a lintlheng tse behiloeng tse fanoeng. Moo ho nang le sekoti sa pokello ea oli (e tloaelehileng litlhophisong tse itseng), transformer e lokela ho behoa holim'a maballo a lehong a behiloeng ka har'a sekoti. Mabala ana a sebeletsa merero e 'meli: a aba meroalo ea mochini ho sireletsa tlase ea transformer,' me a sebetsa e le li-dampers tsa vibration bakeng sa seteishene sohle.

Ka mor'a hore transformer e behoe, lithapo tse mahareng- tse tsoang ho switchgear le likhokahano tse tlase- tsa motlakase ho switchboard li tla emisoa ho li-switcher bushings. Bakeng sa li-transformer tse nang le li-terminals tse bulehileng, li-cable lugs li hokahanya ka ho toba le lihlahla. Bakeng sa lintlha tse kholoanyane tse hlokang matla a holimo, ho ka fanoa ka lihokelo tsa litheminale tse arohaneng.

Letlapa la tekanyo ea transformer le tlameha ho lula le bonahala ho tloha monyako oa tlhahlobo ho thusa ho tsebahatsa le ho hlophisa kemiso ea tlhokomelo.

 

4.4 Substation Earthing

Ho beha fatše ho nepahetseng (grounding) ke e 'ngoe ea likarolo tsa bohlokoa tsa polokeho ea ts'ebetso efe kapa efe ea motlakase, mme litsi tse nyane li hloka tlhokomelo e khethehileng moralong le ts'ebetsong ea sistimi ea lefatše.

  • Morero oa Earthing.Seseteme e sebetsang hantle ea ho etsa lefatše e fana ka-tsela e thibelang matla hore e khutlele mohloling, e fokotsa ho phahama ha motlakase nakong ea bothata, e tsitsisa menyetla ea potoloho mabapi le mobu, le ho netefatsa hore sebaka se kampetsoeng le likarolo tse tsamaisang tse pepenene li lula li le haufi kapa li le haufi le lefela nakong ea ts'ebetso e tloaelehileng. Ho beha fatše ka nepo ho sireletsa basebetsi le lisebelisoa maemong a kotsi a motlakase a ka bakang ts'abo, mollo kapa tšenyo ea lisebelisoa.
  • Sisteme Grounding.Sebaka se sa nke lehlakore sa motlakase oa bobeli oa transformer se tla thehoa. Sistimi ena e fokotsa ho phahama ha motlakase nakong e le 'ngoe-mokhahlelo-ho-ho tloha fatše,' me e fana ka matla a motlakase a bohlokoa bakeng sa ts'ebetso e nepahetseng ea li-relay tse sireletsang le lisebelisoa tsa metering.
  • Thepa ea Thepa.Libaka tsohle tsa tšepe tse ka har'a seteishene, ho kenyeletsoa-mohaho oa motlakase oa motlakase,{1}}motlakase oa motlakase o tlase, tanka ea transfoma, le sebaka sa seteishene se ka tlase, li tla kopanngoa 'me li hoketsoe ho theminale e kholo ea lefatše. Thepa ea lisebelisoa e sebetsa haholo-holo ts'ireletseho ea basebetsi: ha ts'ebetso ea ho kenya letsoho e etsahala ka har'a sesebelisoa, motlakase o phalla ka har'a mokhanni oa fatše ho ea fatše ho e-na le ho feta ho motho ea ka 'nang a kopana le thepa.
  • Earthing Conductors.Sebaka sa-karolo sa li-conductor tsa lefatše se tlameha ho khethoa ho ipapisitsoe le maemo a holimo a lebelletsoeng a phoso le ho phahama ho lumelletsoeng ha mocheso. Libaka tse tloaelehileng tsa cross-likhondara tsa copper earthing ka har'a compact substations li kenyelletsa 30 mm² bakeng sa likhokahano tse kholo, 35 mm² bakeng sa-voltage switchgear le transformer earthing, le 95 mm² bakeng sa khokahanyo ea -voltage neutral busbar.
  • Li-Elektrode tsa Earthing.Khokahano lipakeng tsa sistimi ea lefatše le lefats'e ka bolona e fumaneha ka li-electrode tsa fatše tse kang koporo-lithupa tsa tšepe tse kentsoeng mobung, lipoleiti tsa fatše tse epetsoeng ka ho rapama, kapa litheipi tsa koporo tse epetsoeng. Lithupa tsa fatše hangata li khannoa ka botebo ba limithara tse 2,5 ho isa ho tse 3. Lithupa tse ngata li arotsoe bonyane ka limithara tse 5 ho eketsa katleho. Marang-rang a lefats'e ka kakaretso a hahoa ka lithupa tsa ho khanna likhutlong tse 'nè tsa motheo le ho li kopanya le loop ea conductor e patiloeng.
  • Khanyetso ea ho Grounding.Sepheo sa ho hanyetsa tsamaiso ea mobu ea setsi sa motlakase hangata ke 5 ohms kapa ka tlase, leha lisebelisoa tse ling li rala lisebelisoa tsa tsona ho finyella likarolo tse seng kae tsa leshome tsa 1 ohm. Li-additives tse kang resistivity-litheolelo li ka 'na tsa hlokoa mobung o phahameng- o hanyetsanang le ho finyella litekanyetso tse amohelehang tsa ho hanyetsa.
  • Litlhoko tsa Khokahano.Sebaka sa seteishene se ka tlase se tlameha ho hokeloa ka mokhoa o ts'epahalang ho marang-rang a mobu libakeng tse peli tse arohaneng. Theminale e kholo ea lefatše, eo hangata e leng ka har'a phaposi ea motlakase e tlase-, e sebetsa e le khokahanyo lipakeng tsa sistimi ea ka hare ea setsi sa lefatše le khondatara ea kantle ea sistimi. Ka lisistimi tsa TN-C, protective earth and neutral conductor (PEN) li kopantsoe 'me li hokahantsoe le busbar ea PEN. Ka lisisteme tsa TN{{5}S tse nang le likhondara tse arohaneng le tse sirelletsang, khondara ka 'ngoe e hokahana le busbar ea eona, 'me lefatše le sirelelitseng le hokahantsoe mohloling feela.

 

4.5 Litlhahlobo tsa ho Qetela tsa Tlhophiso

Kamora ho phethoa ha ho kengoa ha mochini, ho emisoa ha li-cable, le likhokahano tsa lefatše, tlhahlobo ea ho qetela e tla etsoa pele o tsoela pele ho fana ka taelo.

Netefatsa hore mamati ohle a buleha le ho koaloa hantle ntle le ho tlama kapa ho sebelisa matla a feteletseng. Netefatsa hore likhokahano tsohle tse koetsoeng ka liboutu tse tiisitsoeng nakong ea ho kenya li lula li sireletsehile, u ela hloko ka ho khetheha likhokahano tsa libese, ho emisoa ha lithapo le li- earthing bond. Hangata li-fasteners tsa feme- li tšoauoa ka pente e le sesupo sa torque e nepahetseng; hlahloba hore na matšoao ana ha a so suthe.

Lekola likenyo tsohle tsa cable ho netefatsa hore li tiisitsoe hantle khahlano le ho kenella ha mongobo le ho kenella ha litoeba. Netefatsa hore lileibole tsa temoso li teng 'me li khomaretsoe ka nepo libakeng tsohle tse hlokahalang. Tlosa lintho life kapa life tse tsoang kantle ho naha, ho kenyeletsoa likurufu tse hlephileng, linate, lithulusi, kapa maloanlahla, likarolong tsohle.

 

 


 

 

compact substation commissioning

5. Ho laela

5.1 Pele ho-Litlhahlobo tsa Matla

Pele seteishene sa compact se ka matlafatsoa le ho kengoa tšebetsong, ho tlameha ho etsoe letoto le hlophisitsoeng la licheke le liteko ho netefatsa hore sets'oants'o se se se loketse ho sebetsa le hore lits'ebetso tsohle tsa polokeho li sebetsa joalo ka ha ho reriloe.

Litlhahlobo tsa Pele.Etsa litlhahlobo tse latelang ka li-switchgear kaofela tse maemong a-ea matla:

Netefatsa hore -likokello tsa li-switch{0}} le li-circuit breaker li maemong a OFF pele o tsoela pele. Netefatsa ts'ebetso e nepahetseng ea li-interlock tsa mochini le tsa motlakase, tse etselitsoeng ho thibela tatellano e sa sireletsehang ea ts'ebetso. Bakeng sa SF6-insulated switchgear, hlahloba letšoao la khatello ea khase ho netefatsa hore khatello e ntse e le ka har'a moeli o boletsoeng (hangata pointer e lokela ho ba sebakeng se setala holim'a gauge).

Etsa bonnete ba hore motlakase oa taolo oa fumaneha le hore li-relay tsohle tsa tšireletso le limithara li setiloe ka nepo ebile lia sebetsa. Etsa teko ea tšebetso ea ring main unit le{1}}low voltage panel control and protection systems, u bone tšebetso e nepahetseng ea ho bula le ho koala li-circuit breaker.

Teko ea Insulation.Lekanya khanyetso ea insulation ho lefats'e ea mokhanni ka mong oa mohato. Tloaelo e tloaelehileng e hloka hore ho be le li-insulation resistance counts tse seng ka tlase ho 200 mega-ohms. Litekanyetso tse tlase li ka bonts'a litšupiso tse senyehileng kapa tse silafetseng, 'me lipatlisiso tse ling lia hlokahala pele li tsoela pele.

Teko ea Dielectric.Haeba ho hlokoa ho ea ka melao ea lehae kapa lintlha tsa morero, ho ka etsoa teko ea -frequency standstand voltage test. Matla a teko a tla sebelisoa sebakeng sa marang-rang hangata ke 80% ea boleng ba tlhahlobo ea feme e boletsoeng ho IEC 60694, e sebelisitsoeng nako e boletsoeng.

Netefatso ea Tatelano ea Mokhahlelo.Netefatsa hore tatellano ea karolo ea phepelo ea motlakase e kenang-e lumellana le ho potoloha ho hlokahalang bakeng sa transfoma le lisebelisoa tse tlase. Tatellano e fosahetseng ea mohato e ka etsa hore li-motor li khutlele morao 'me li ka ama ts'ebetso ea li-relay tse ling tse sireletsang.

 

5.2 Mohato{1}ka-Mohato oa Tatelano ea Khomishene

Ha litlhahlobo kaofela{0}} li khotsofetse, seteishene se ka romelloa ho sebelisoa tatellano e latelang.

Mohato oa 1 - Netefatso ea Boinotšing.Pele o tsoela pele, netefatsa hore li-switch element kaofela li maemong a tsona a HO TLOHILE kapa HO OPEN, ho kenyeletsoa-voltage switchgear, medium-voltage switchgear, le li-circuit breaker leha e le life tse nyenyane tse laolang li-circuits tse ling.

Mohato oa 2-Ho Matlafatsa Motlakase o Mahareng.Ke basebetsi ba lumelletsoeng feela ba koetlisitsoeng ka polokeho ea motlakase ba ka hokelang sesebelisoa sa -voltage se mahareng ho transfoma. Mochine o motlakase{{2}o tla buleha ho latela litaelo tsa tšebetso tsa moetsi. Ka nako ea ho fana ka matla, basebetsi ba lokela ho ema ka ho hlaka 'me ba shebe lisebelisoa bakeng sa melumo leha e le efe e sa tloaelehang, arcing, kapa matšoao a mang a ho se sebetse hantle.

Mohato oa 3-Ho Hlahloba Motlakase o Tlase.Ka mor'a hore transformer e matlafatsoe, hlahloba motlakase oa AC o tlase o teng ho -voltage switchgear e tlaase. Lekanya phapang ea motlakase pakeng tsa li-conductors tsa mela 'me u tlalehe litekanyetso tsena tlalehong ea khomishene. Matla a fokolang a lekantsoeng a lokela ho ba ka hare ho ± 5 volts ea inverter nominal voltage. Haeba ho kheloha ho feta mokhoa ona, lipompo tsa transformer li tlameha ho lokisoa ho sebelisoa-load tap-changer, ebe motlakase o lekanngoa hape{7}}le ho netefatsoa.

Mohato oa 4-Khokelo ea Phepelo ea Matla ka Hare.Haeba seteishene se na le transfoma e ka hare ea motlakase, phepelo ea motlakase e kahare bakeng sa seteishene ka bosona e lokela ho hokeloa ka ho koala sekheo sa potoloho e kholo botong ea-ea kabo ea seteishene. Ebe u koala likhechana tsa potoloho tse nyane bakeng sa mabone a seteisheneng, sets'oants'o sa lefatše (ho netefatsa hore sesebelisoa se kopaneng sa masala se sebetsa), li-fentilation tsa moea, lisebelisoa tsa metering le lisebelisoa tsa puisano.

Mohato oa 5-Khokelo ea Phepelo ea Matla a Inverter.Koala sekhechana sa potoloho se ngotsoeng "Voltage supply SC1" bakeng sa inverter ea pele. Haeba li-inverters tse peli li kentsoe, koala sekhechana sa potoloho se lumellanang bakeng sa inverter ea bobeli.

Mohato oa 6-Ho Matlafatsa Motlakase o Tlaase ho Switchgear.Ha licheke kaofela li felile, -motlakase oa ho switjha motlakase o ka tlase o ka buloa ho fana ka motlakase ho netweke ea phano e tlase. Mokhoa o ikhethileng oa ho matlafatsa{2}}voltage switchgear o hlalositsoe ka botlalo litokomaneng tsa moetsi oa switchgear.

Mohato oa 7-Inverter Commissioning.Kamora ho matlafatsoa ka katleho ha seteishene le netefatso ea maemo a nepahetseng a motlakase, li-inverter tse hokahaneng li ka romelloa ho latela litaelo tsa moetsi oa li-inverter.

 

5.3 Litokomane tsa Komisi

Ts'ebetso ea ts'ebetso e tlameha ho ngoloa ka botlalo. Bakeng sa likopo tsa tiisetso le tiisetso hore li lule li sebetsa, ho na le litlhoko tse itseng. Haholo-holo, ho qala{2}}ho ka hloka hore ho etsoe ke moetsi oa lisebelisoa kapa moemeli oa bona ea lumelletsoeng, kapa tlaleho ea taelo e tlatsitsoeng ka botlalo le e saennoeng e tlameha ho romelloa ho moetsi pele a kenya sesebelisoa ts'ebetsong.

Litokomane tsa kopo li lokela ho kenyelletsa:

  • Nomoro ea serial ea seteishene le mofuta oa khetho
  • Aterese ea sebaka sa ho kenya
  • Litekanyo tsa motlakase tse tlalehiloeng
  • Liphetho tsa tlhahlobo ea ho hanyetsa insulation
  • Netefatso ya tatellano e nepahetseng ya mokgahlelo
  • Netefatso ea litlhophiso tse nepahetseng tsa phepelo ea tšireletso
  • Rea elelloa hore likhokahano tsohle tsa mochini le tsa motlakase li sebetsa ka nepo
  • Phaello ea ho qetela-ke moenjiniere ea ikarabellang

 

5.4 Kamohelo ea ho Qetela

Ka mor'a hore seteishene se matlafatsoe 'me liteko tsohle tsa ts'ebetso li netefatsoe hore lia khotsofatsa, ho kenngoa ho amoheloa bakeng sa tšebeletso. Litokomane tsa khomishene li tla kenngoa le litokomane tsa sistimi bakeng sa seteishene, tse fumanehang habonolo bakeng sa tšebeliso ea nako e tlang ke basebetsi ba tlhokomelo.

Linotlolo tsohle tsa linotlolo tsa mamati li tla ntšoa linotlolong ebe li bolokoa sebakeng se sireletsehileng, se khethetsoeng se fihlellehang ho basebetsi ba lumelletsoeng feela. Sebaka sa seteishene se senyenyane se tla notleloa ho thibela ho kena ka mokhoa o sa lumelloeng, joalokaha ho hlokoa ke melao ea tšireletso le mekhoa e tloaelehileng ea ts'ebetso.

 

 


 

6. Ts'ebetso

Packer-type Substation

6.1 Maemo a Tlwaelehileng a Tshebetso

Li-substations tse nyenyane li etselitsoe hore li sebetse kamehla tlas'a maemo a itseng a tšebeletso. Mokhanni o tlameha ho etsa bonnete ba hore maemo ana a hlokomeloa nakong eohle ea bophelo ba setsi sa seteishene.

  • Litekanyetso tsa Motlakase.Matla a motlakase a sebelisitsoeng le mojaro oa motlakase ha oa tlameha ho feta litekanyetso tse kentsoeng tse boletsoeng ho nameplate ea seteishene. Ts'ebetso e tsoelang pele ka holimo ho litekanyetso tse lekantsoeng e baka mocheso o feteletseng, ho tsofala ho potlakisa ho koala, 'me ho ka tsosa lisebelisoa tse sireletsang.
  • Maemo a Ambient.Seteishene se tla sebetsa ka har'a mocheso o itseng oa tikoloho, oo hangata e leng −20℃ho +45℃bakeng sa tlhophiso e tloaelehileng. Mongobo o lekanyelitsoeng o tlameha ho bolokoa lipakeng tsa 15% le 95% (o sa nyenyefatse-). Ho sebetsa libakeng tse ka holimo ho limithara tse 1,000 ho hloka ho fokotsoa ha matla a ho mamella matla.
  • Moea oa moea.Seteishene se itšetlehile haholo ka ho potoloha ha moea oa tlhaho ka li-louvers tse mamating a phaposi bakeng sa ho pholile. Menyako ea phaposi ea li-transformer ha ea lokela ho sitisoa, 'me limela tse melang ho pota-pota seteishene li tla fokotsoa ha ho hlokahala ho boloka moea o lekaneng.

 

6.2 Mekhoa ea Ts'ebetso

  • Ts'ebetso e Tloaelehileng ea ho Fetola.Ha o sebelisa li-unit tsa mantlha kapa lisebelisoa tse ling ka har'a seteishene, tatellano e nepahetseng ea ts'ebetso e tla bonoa. Bakeng sa polokeho, pele o bula sekoaelo sa phaposi ea lithapo, phepelo e amanang le eona e tlameha ho koaheloa le ho netefatsoa hore e feletsoe ke{1}}matla.
  • Mechanical Interlocks.Seteishene sena se na le li-interlocks tsa mochini tse etselitsoeng ho thibela tatelano e sa bolokehang ea ts'ebetso, joalo ka ho bula lemati la phaposi ea lithapo pele potoloho e koaheloa. Motsoako o tlameha ho tlosoa ka nepo pele opereishene ka 'ngoe e lekoa; ho qobella ho feta sehokelo ho bontsha tatelano e fosahetseng ya tshebetso e ka bakang kotsi.
  • Insulated Operating Tools.Molamu oa ts'ebetso oa insulated o tla sebelisoa neng kapa neng ha ho hlokahala ts'ebetso ea letsoho. Mohele oa ts'ebetso o fanoeng le seteishene sa motlakase hangata o loketse morero ona.
  • Lipontšo Tse Bonahalang.Pele o etsa ts'ebetso efe kapa efe ea ts'ebetso, matšoao a capacitive voltage a lokela ho hlahlojoa. Letšoao le khanyang le bontša boteng ba motlakase oa mohala; sesupo se sa bonesoang se bontša ho se be teng ha motlakase, leha ho ntse ho hlokahala tlhokomeliso ho netefatsa ho felloa ke matla-ka mekhoa e meng pele u tšoara li-conductors.

 

6.3 Tekolo ea Ts'ebetso ea Ka mehla

Nakong ea ts'ebetso e tloaelehileng, nako le nako basebetsi ba lokela ho shebella seteishene bakeng sa matšoao a maemo a sa tloaelehang.

  • Lipontšo Tse Utloahalang.Mamela lerata le sa tloaelehang la li-transformer joalo ka ha ho lla ho fetotseng molumo oa lentsoe kapa molumo, melumo e hlabang e ka bontšang ho tsoa ka mokhoa o sa fellang, kapa ho reketla ho tsoang likarolong tse hlephileng.
  • Lipontšo Tse Bonahalang.Ela hloko 'malo oa motlakase le oa morao-rao ho lisebelisoa le limithara, u shebeletse ho feto-fetoha ho sa tloaelehang kapa ho baloa ka ntle ho mekhahlelo e lebelletsoeng. Etsa bonnete ba hore matšoao ohle a boemo le mabone a lemosang a hlaha ka nepo le hore ha ho matšoao a alamo a khantšitsoeng.
  • Tlhokomelo ea Tikoloho.Nako le nako hlahloba mocheso ka hare le maemo a mongobo ka har'a phaposi ka 'ngoe. Mocheso o feteletseng o ka 'na oa bontša maemo a mangata kapa moea o thibelang moea. Ho koaheloa ka har'a liphaposi ho ka 'na ha bontša hore thepa ea ho futhumatsa kapa ea ho tlosa mongobo ha e sebetse hantle.

 


 

package substation

7. Tlhokomelo

7.1 Filosofi ea Tlhokomelo

Tlhokomelo ea kamehla, e hlophisitsoeng e bohlokoa bakeng sa ho netefatsa ts'ebetso e tsoelang pele e bolokehileng le e ts'eptjoang ea seteishene se senyane sa komporo bophelo bohle ba sona ba ts'ebeletso. Lenaneo -le reriloeng hantle la tlhokomelo le lemoha mathata a teng pele ho nako, le lumella hore ho lokisoe pele liphoso li etsahala, kahoo le thibela ho tima ho sa reroang, liketsahalo tsa polokeho le litokiso tse bitsang chelete e ngata.

Mesebetsi ea tlhokomelo e arotsoe ka mekhahlelo e meraro:

  • Tlhahlobo e Tloaelehileng.E etsoa ka ntle ha seteishene se ntse se sebetsa. Tlhahlobo ea ka mehla e kenyelletsa ho netefatsa matla a motlakase le lipalo tsa hajoale, ho lekola lerata kapa monko o sa tloaelehang, le ho bona maemo a tikoloho ho potoloha seteishene. Tlhahlobo ena hangata ke karolo ea lipaterole tse tloaelehileng tsa setsi.
  • Tlhahlobo ea Nako le Nako.E etsoa ka linako tse reriloeng ha seteishene se ntse se sebetsa (tlhahlobo e tloaelehileng) kapa -e feletsoe ke matla (tlhahlobo e felletseng). Tlhahlobo e tloaelehileng e shebane le maemo a kantle a kang ho bokellana ha tšilafalo le ho bola. Tlhahlobo e qaqileng e hloka tšitiso ea ts'ebetso 'me e kenyelletsa mesebetsi ea ts'ireletso, litsamaiso tsa taolo, mekhoa ea ho koala, le tlhahlobo ea ka hare ea lisebelisoa.
  • Ho sebeletsa.E etsoa ha tlhahlobo e senola maemo a sa tloaelehang kapa ha palo e boletsoeng ea lipotoloho tsa ts'ebetso e fihletsoe (mohlala, ts'ebetso ea 1,000 bakeng sa lisebelisoa tse itseng tsa switching).

 

7.2 Linako tse Khothallelitsoeng tsa Tlhokomelo

Linako tsa tlhokomelo li fapana ho latela maemo a tikoloho, mosebetsi oa ts'ebetso, le bohlokoa ba lisebelisoa. Lenane le latelang le fana ka tataiso e akaretsang:

  • Tlhahlobo ea Pono:Khoeli le khoeli, kapa khafetsa tlas'a maemo a thata joalo ka tikoloho ea mabopo a leoatle, libaka tse phahameng- tse nang le tšilafalo ea liindasteri, kapa libaka tse nang le lerole le leholo kapa lehlabathe.
  • Tlhokomelo ea Kamehla:Likhoeli tse ling le tse ling tse 6 ho isa ho tse 12, ho latela tikoloho ea ts'ebetso le maemo a mojaro.
  • Phetoho e felletseng:Lilemo tse ling le tse ling tse 3 ho isa ho tse 5 bakeng sa lisebelisoa tse ngata, kapa ho latela likhothaletso tse khethehileng tsa moetsi-.
  • Tlhahlobo e felletseng ea mekhoa ea ts'ebetso:Hoo e ka bang lilemo tse ling le tse ling tse 6 bakeng sa lisebelisoa tsa sekhechana sa potoloho le lisebelisoa tse ling tse sebelisoang khafetsa.

 

7.3 Mekhoa ea Tlhokomelo

  • Tlhahlobo ea Pono.Tsamaea{0}kahare ho pota-pota le ho hlahloba bokantle ba seteishene. Lekola sebaka se kampetsoeng hore na ho na le mafome, sebopehile, se senyehile, kapa ho senyehile ha anti{2}}anti-corrosion coating. Netefatsa hore matshwao ohle a temoso le dileibole di dula di le teng mme di a balehe. Netefatsa hore mamati le liphaposi li koetsoe ka nepo le hore litšepe li lula li sa sitisoe.
  • De-Ho Hloekisa ka Matla.Ha ho etsoa litokiso tse felletseng, seteishene se tlameha ho felloa ke matla-le ho notleloa ka ntle ho latela mekhoa ea ts'ireletso e sebetsang. Ka mor'a ho itšehla thajana, lerōle le lithōle li tla tlosoa likarolong tsohle. Li-insulators, lihlahla le libaka tse ling tsa ho kenya li lokela ho hloekisoa ka mochini o hloekisang kapa moea o omileng o hatelitsoeng. Li-deposit tse khomaretsang kapa tse mafura li ka tlosoa ka lesela{4}lesela le sa lefelloeng le kenngoeng nthong e amohetsoeng ea ho hloekisa.
  • Khokahano e Matlafatsa.Ka lebaka la lipotoloho tsa ho hola le ho fokotseha ha mocheso, likhokahano tsa li-terminal li ka theoleha ha nako e ntse e ea. Nakong ea tlhokomelo ea nako le nako, likhokahano tsohle tsa libese, ho emisoa ha lithapo, le libonto tsa lefatše li tla ts'oaroa hape ho litekanyetso tse boletsoeng tsa torque ho sebelisa wrench ea torque e lekantsoeng.
  • Mechanical Component Check.Mekhoa ea ts'ebetso ea li-circuit breakers, disconnectors, le switches e lokela ho sebetsoa ka makhetlo a ka bang 10 ho isa ho a 12 ho netefatsa ts'ebetso ea mochini. Sheba ho tsamaea hamonate ha lirolara, lithakhisa le likarolo tse thellang. Tlosa lisebelisoa tsa mochini ka ho sebelisa mafura a lumelletsoeng joalo ka ha ho boletsoe litokomaneng tsa moetsi; setlolo sa khale se tlameha ho ntšoa pele ho sebelisoa setlolo se secha.
  • Teko ea Motlakase le Mocheso.Etsa tlhahlobo ea ho hanyetsa insulation ea li-circuits tse kholo ho netefatsa botšepehi ba dielectric. Thermographic scanning (tlhahlobo ea infrared) e tla etsoa ho bona libaka tse nang le li-hotspots tse bonts'ang likhokahano tse hlephileng, li-circuits tse imetsoeng, kapa liphoso tse tlang. Liteko tse sebetsang li tla etsoa ho li-relay tsa ts'ireletso, matšoao a phoso, le lisebelisoa life kapa life tse laoloang hole.
  • Tlhokomelo ea Khatello ea Khase.Bakeng sa SF6-insulated switchgear, netefatsa hore letšoao la khatello ea khase le lula sebakeng se setala (hangata 0.25 ho 0.5 bar khatello e amanang le likhato tse 20). Haeba khatello e atamela moeli oa alamo, boemo bo tla hlahlojoa. Li-monitor tsa khatello ea khase tse nang le alamo le mabitso a maeto li fana ka tsebiso e ikemetseng ea maemo a tlase a khatello.
  • Netefatso ea Sisteme ea Grounding.Sheba tsoelo-pele ea tsamaiso ea mobu libakeng tsohle tse fumanehang. Lekanya khanyetso ea fatše nako le nako ho netefatsa hore e lula e le ka har'a meeli e amohelehang (hangata 5 ohms kapa ka tlase). Tlhahlobo ea pono ea likhokahano tsa fatše e lokela ho netefatsa hore libonto tsohle li lula li tiile 'me li se na kutu.
  • Litlhahlobo tsa sistimi e thusang.Netefatsa tšebetso e nepahetseng ea mabone a phaposi, li-switches-tse sebelisoang ke mamati, lilaola mocheso le mongobo, tšebetso ea fene, le lisebelisoa life kapa life tse kentsoeng tsa ho lemoha mollo kapa mosi. Haeba li-fan li sa qale ka botsona, molaoli oa mocheso o lokela ho feto-fetoha hore o be maemong a ka tlase ho mocheso o teng hona joale ho qala litšepe bakeng sa liteko.

 

7.4 Lits'oants'o tse Khethehileng bakeng sa Likaroloana tse Ikhethileng

  • Ring Units Main.RMU e etselitsoe ho lokisoa- mahala, e hloka feela ho hloekisoa ka mokhoa o tloaelehileng le ho hlahlojoa nako le nako. Leha ho le joalo, likarolo tsa khase-tse tiisitsoeng li lula li beiloe leihlo ke matšoao a khatello ea khase, 'me ha li hloke hore nako le nako li lokisoe. Ho khothaletsoa tlhahlobo e felletseng ea mekhoa ea ts'ebetso hoo e ka bang lilemo tse ling le tse ling tse 6.
  • Li-transformer.Bakeng sa oli-liphetoho tse qoelitsoeng ka metsing, mocheso oa oli le mocheso oa matsoelintsoeke li tla beoa leihlo. Setsi sa tšireletso sa transformer se lokela ho hlophisoa ka litlhophiso tse nepahetseng tsa mocheso. Nako le nako hlahloba hore na ha ho na ho lutla ha oli, haholo-holo ho pota-pota manonyeletso a samenteng, li-gaskets le litiiso tse bushing. Boemo ba bushing bo lokela ho hlahlojoa bakeng sa matšoao a ho lateloa, ho phunyeha kapa ho silafala.
  • Tlase{{0}Motlakase Switchgear.Hlahloba li-circuit breakers bakeng sa matšoao a ho chesa haholo, ho kenyelletsa le ho fifala ha li-terminals kapa ho qhibiliha ha insulation. Netefatsa hore lisebelisoa tse setseng tsa hajoale (RCDs) li sebetsa ka nepo ka ho etsa liteko ho latela litaelo tsa moetsi.

 

7.5 Tšireletseho ea Tlhokomelo

Mosebetsi oohle oa ho lokisa o tla etsoa feela ke basebetsi ba nang le litsebo ba tsebang litšobotsi tse ikhethang tsa switchgear le lisebelisoa tse amanang le tsona.

Pele mosebetsi ofe kapa ofe o etsoa seteisheneng, lisebelisoa li tlameha ho tlosoa-matla. Melao e Mehlano ea Tšireletso ea Boenjiniere ba Motlakase e tlameha ho hlokomeloa ka thata:

  • Isolate (tloha mehloling eohle ea phepelo)
  • Sireletsa khahlanong le ho koala hape
  • Netefatsa ho itšehla thajana ho sireletsehileng ho tsoa phepelong
  • Lefatše le potoloho e khutšoane-
  • Sekoahelo kapa mokoallo o haufi le likarolo tse phelang

Ha mosebetsi o etsoa ka lisebelisoa tse matlafatsoang (mohlala, nakong ea ho rarolla mathata), lisebelisoa tse nepahetseng tsa polokeho ho kenyeletsoa liatlana tse sirelelitsoeng, limmete tse sireletsang motho, le lisebelisoa tse ling tse loketseng tsa ho itšireletsa li tlameha ho sebelisoa.

Mesebetsi ea tlhokomelo e hlokang ho bula lemati la phaposi ea transformer e kanna ea notleloa le yuniti e kholo ea selikalikoe; ho sebetsa li-interlock tsena ka phoso ho ka hlahisa maemo a kotsi, kahoo tatellano e nepahetseng e hlalositsoeng litaelong tsa ts'ebetso e tlameha ho lateloa.

 


 

8. Tharollo ea mathata le Maemo a sa Tloaelehang

Vehicle-mounted mobile substation

8.1 Mathata a Tloaelehileng le Liketso tsa Tokiso

  • Lerata le sa tloaelehang le tsoang ho Transformer.Haeba transformer e hlahisa ho lla, ho lla ha molumo o fetohileng, kapa melumo e meng e sa lebelloang, lisosa tse ka bang teng li kenyelletsa ho hlephisa, ho tsoelipana, ho tsoa ka mokhoa o sa fellang, kapa moroalo o boima. Mojaro o lokela ho fokotsoa 'me transformer e hlahlojoe.
  • Mocheso o Feteletseng.Lithempereichara tse phahameng tsa ts'ebetso li ka bakoa ke maemo a mangata, moea o fokolang, mocheso o phahameng oa tikoloho, kapa ho se sebetse ha thepa ea ka hare. Netefatsa maemo a mojaro, tšitiso e hlakileng ho tsoa liphaepheng tsa moea, 'me u sebelise setšoantšo sa mocheso ho tseba mohloli oa ho futhumatsa.
  • Alamo ea Khatello e Tlase ea SF6.Khatello ea khase e theohang e ka bontša ho lutla ka tanka e koetsoeng. Ho hlokahala tokiso ea hang-hang, kaha ts'ebetso e tsoelang pele tlas'a khatello e tlase e ka sitisa ho koala le arc{1}}bokhoni ba ho tima. Ho lutla ho tla fumanoa le ho lokisoa, 'me khatello ea khase e khutlisetsoe boemong bo lekantsoeng.
  • Pontšo ea Phoso ea Motheo.Ha sesupo sa phasese ea phoso kapa phetiso ea tšireletso e bontša phoso ea fatše, potoloho e amehileng e lokela ho tsejoa le ho aroloa. Patlisiso e lokela ho fumana hore na phoso ke ea nakoana (mohlala, e bakoa ke mongobo oa nakoana kapa liphoofolo tse hlaha) kapa ka ho sa feleng (tšenyo ea ho koala lithapo kapa ho hloleha ha ka hare).

 

8.2 Nako ea ho Iteanya le Moetsi

Maemo a mang a hloka tšehetso ea bahlahisi kapa basebetsi ba feme{0}ba lumelletsoeng ho sebetsa. Ikopanye le moetsi ha:

  • Seteishene se senyenyane se hloka hore ho nkeloe sebaka sa likarolo tse khōlō tse sa rereloang tšebeletsong ea tšimo
  • Ho bile le phoso e kholo ea motlakase ka hare ho arc
  • Litokiso tse rarahaneng ho SF6-insulated switchgear lia hlokahala
  • Ho na le maemo a sa tloaeleheng a sa sebelisoeng ke tataiso ena kapa thepa-litokomane tse khethehileng.
  • Litlhophiso tsa relay ea ts'ireletso li hloka ho balloa bocha kapa ho hlophisoa bocha ho feta liphetoho tse tloaelehileng

 


 

Prefabricated substation

9. Kakaretso ea Polokeho

 

Lintlha tse latelang tsa polokeho li bohlokoa haholo nakong eohle ea ho kenya, ho sebetsa le ho hlokomela liteishene tse nyane tse kopaneng.

  • Kotsi ea Tšisinyeho ea Motlakase.Li-voltage tse phahameng li teng ka har'a seteishene. Pele mosebetsi ofe kapa ofe o etsoa, ​​seteishene se tlameha ho tlosoa-matla ho tsoa mehloling eohle, ho kenyeletsoa{2}}voltage switchgear, medium-voltage switchgear, le phepelo efe kapa efe ea motlakase ea kantle. Ka mor'a ho-matla, netefatsa hore ha u na motlakase pele u tšoara li-conductors.
  • Arc Flash Hazard.Liteishene tse nyane tse etselitsoeng IEC 62271-202 li kenyelletsa likarolo tsa kahare tsa arc tse nang le matla a arc ka har'a libaka tse hlalositsoeng. Leha ho le joalo, mesebetsi eohle e mabapi le lisebelisoa tse matlafalitsoeng kapa haufi le eona e ntse e tlameha ho etsoa ka lisebelisoa tse nepahetseng tsa ts'ireletso le ho latela litekanyetso tse sebetsang tsa polokeho ea arc flash.
  • Chesa Kotsi.Likarolo tse ling, haholo li-fuse le lihlahla tsa transformer, li ka chesa nakong ea ts'ebetso e tloaelehileng. Apara liatlana tse loketseng ha u tšoara kapa u sebetsa haufi le likarolo tsena, 'me u lumelle nako e lekaneng ea ho pholisa pele u lokisa.
  • Kotsi ea Mollo.Sebaka sa tšireletso sa bonyane 5,000 mm ho tloha linthong tse tukang se tla bolokoa. Seteishene sena hangata se fana ka setima-mollo e le karolo ea phepelo e tloaelehileng, e tla lula e fumaneha le ho hlahlojoa khafetsa bakeng sa ts'ebeletso.
  • Polokeho ea Tikoloho.Ha o sebetsana le khase ea SF6 ho tloha ho switchgear, ho tla sebelisoa mekhoa e lumellanang le tikoloho. Lisebelisoa tsa ho khutlisa khase li thibela ho lokolloa ha SF6, e leng khase e matla ea mocheso.

 


 

10. Litaelo tsa Ts'ebetso ea Transformer e Amanang le Ts'ebetso

Lits'oants'o tse nyane li kopanya li-transformer le switchgear sebakeng se koaletsoeng hantle sa sebaka bakeng sa kabo ea kantle. Bakeng sa mefuta ea li-transformer tsa setso tse nang le meralo e fapaneng ea ho hlongoa, e pholileng kapa e kampetsoeng, ka kopo sheba litataiso tse latelang tse inehetseng.

 

 

 


 

 

11. Litšupiso

Liteishene tse nyenyane tsa Compact ke tsa mofuta-tse lekiloeng ho ea khatisong ea morao-rao ea IEC 62271-202, e hlakisang litlhokahalo tsa liteishene tsa compact tsa bobeli. Litekanyetso tse ling tse sebetsang li kenyelletsa IEC 62271-1 bakeng sa lintlha tse tloaelehileng tsa switchgear, IEC 62271-100 bakeng sa li-circuit breakers, IEC 62271-200 bakeng sa li-switchgear cubicles, IEC 62271-102 bakeng sa li-di-connectors le li-switches tsa earthing, IEC 62271-105 ts'ireletso ea IEC 62271-105 bakeng sa khefu ea 105 ea IEC li-ennclosures (IP codes), IEC 60076 bakeng sa li-transformer tsa matla, le IEC 61439 bakeng sa likopano tsa switchgear tse tlase.

Bakeng sa lipotso leha e le life kapa mathata a tekheniki mabapi le ho kenya, ho sebetsa, kapa ho lokisoa ha seteishene se senyenyane, ikopanye le mohala oa litšebeletso tsa moetsi oa thepa ka lintlha tse latelang tse fumanehang habonolo: nomoro ea serial ea seteishene, mofuta oa mofuta, le aterese ea sebaka sa ho instola.

 