Pole Mounted Transformer Installation le Tataiso ea Ts'ebetso
Apr 14, 2026
Siea molaetsa

Tataiso ena e akaretsa ts'ebetso, ts'ebetso le tlhokomelo ea li-transformer tse kentsoeng ka karolo e le 'ngoe ea oli. E ipapisitse le libuka tsa botekgeniki tsa lisebelisoa le litekanyetso tsa indasteri joalo ka IEEE C57.12.00. Ho kenya ts'ebetso e nepahetseng, ts'ebetso e nepahetseng, le tlhokomelo ea kamehla li bohlokoa bakeng sa ts'ebeletso e bolokehileng le e ts'epahalang ea li-transformer. Tataiso ena e kenyelletsa ho amohela le ho ts'oara, ho kenya, likhokahano tsa motlakase, ho theola fatše, ho hlahloba pele le ka mor'a matla, ts'ebetso ea sesebelisoa sa ts'ireletso, tlhahlobo ea kamehla, le ts'ebetso ea mokelikeli.
Thepa e koahetsoeng: Li-transformer tsa kabo ea oli ea mokhahlelo o le mong (letoto le tloaelehileng)
Litekanyetso tse sebetsang: IEEE C57.12.00, IEEE C57.12.90, NEMA TR1, NFPA 70E
1. Kakaretso Polokeho
1.1 Litlhaloso tsa boemo ba kotsi
|
Lentsoe la pontsho |
Tlhaloso |
|
KOTSI |
Boemo bo kotsi bo haufi, boo, ha bo sa qojoe, bo tla fella ka lefu, kotsi e mpe kapa tšenyo ea lisebelisoa. |
|
TLHOKOMELO |
Boemo bo ka bang kotsi boo, ha bo sa qojoe, bo ka bakang lefu, kotsi e mpe kapa tšenyo ea lisebelisoa. |
|
TLHOKOMELO |
Boemo bo ka bang kotsi boo, ha bo sa qojoe, bo ka bakang kotsi e nyane/e itekanetseng kapa tshenyo ea thepa. |
1.2 Litlhokahalo tse akaretsang tsa polokeho
Feelabasebetsi ba tšoanelehang(ea koetliselitsoeng ho kenya lisebelisoa tse phahameng tsa motlakase, tlhokomelo, ts'ebetso, ts'ebeliso e nepahetseng ea PPE, le thuso ea pele) e ka sebetsa sesebelisoa sena.
Pele ho tlhokomelo kapa tlhahlobo efe kapa efe:
- Fokotsa matla a transformer ho tsoa ho asebaka se hole.
- Sebelisa sesebelisoa se nepahetseng sa motlakase ho netefatsali-voltage tsa zero ho lihlahla tsohle tse phahameng tsa motlakase le tse tlase.
- Tlosa li-terminals tsohle hantle(ea mathomo le ea bobeli).
- Nahana ka monyetla oa ho fepa ka morao (mohlala, jenereithara ea standby).
Le ka mohla u se ke ua itšetleha feela ka ho tlosoa ha fuse kapa ho fetola boemo e le bopaki ba ho tima matla.
Apara PPE e loketseng (liatlana tse sireletsang tšireletso, thebe ea sefahleho, sutu ea arc-flash) joalokaha ho hlokoa ke NFPA 70E.
Se ke oa sebelisa lisebelisoa tse feto-fetohang tse kenngoeng ke metsi ha mocheso oa mokelikeli o kenang ka tlase o le ka tlase:
- Oli e tloaelehileng ea liminerale kapa mokelikeli oa silicone: -20 degree
- R‑ Mokelikeli oa mocheso: 0 degree
- FR3™ mokelikeli oa tlhaho oa ester: -10 degree
2. Ho Amohela, Ho Tšoara le ho Boloka
2.1 Ho fumana tlhahlobo (pele ho laolloa)
|
Ntho |
Ketso |
|
Letlapa la mabitso |
Netefatsa nomoro ea seriale, kVA, lintlha tsa HV/LV, impedance, tatellano ea mofuta oa mokelikeli. |
|
Tšenyo ea kantle |
Sheba li-dents, li-scratches, li-radiator tse holofetseng, tšenyo ea pente. |
|
Ho dutla |
Hlahloba li-welds, lihlahla, li-gauge, li-valve bakeng sa matheba a oli. |
|
Lisebelisoa |
Netefatsa tekanyo ea khatello / vacuum gauge, tekanyo ea boemo ba oli, thermometer, valve ea drain, li-cup, li-fuse, libuka, mangolo a temoso a teng. |
|
Khatello-vacuum gauge |
Ho bala ho lokela ho fapana le mocheso o tikolohong. Lefela la kamehla le ka supa ho dutla. |
Haeba tšenyo kapa khaello e fumanoa,lengolo la molao la thepa, nka linepe, kenya kopo ho mofani oa thepa, 'me u tsebise moetsi.
2.2 Ho phahamisa le ho tšoara
Crane / hoist lifting:
- Sebelisafeela lisebelisoa tsa ho phahamisa tse fanoeng. Se ke oa phahamisa lihlahla, li-radiator kapa masoba a tlamang.
- Lisebelisoa tsa ho phahamisa (lihakisi, li-slings, slinger bar) li tlameha ho lekanyetsoa bakeng sa boima ba kakaretso (sheba nameplate).
- Sebelisa sethala ho boloka likhoele tse otlolohileng (ka tlase ho kapa ho lekana le likhato tse 20 ho tloha holimo).
- Ho sekama ho hoholo nakong ea lifti:15℃ho tloha holimo.
- Ha mocheso o le ka tlase ho -20 degrees, tšoara ka hloko ho qoba tšenyo e senyang.
Ho sebetsana le forklift:
- Ke feela bakeng sa li-transformer tse kentsoeng ka mokhoa o sireletsehileng holim'a pallet ea ho tsamaisa thepa.
- Lifereko li tlameha ho atolosa ka ho feletseng tlas'a pallet.
- Le ka mohlaphahamisa transformer e sa palamang ka forklift.
2.3 Polokelo
Nako e khuts'oane: Boloka ka har'a sephutheloana sa mantlha sebakeng se hloekileng, se omileng, se sa senyeheng.
Long‑term (>Likhoeli tse 3):
- Boloka sebakeng se tiileng, se lekaneng. Sebelisa liraka tsa polokelo.
- Se ke oa bokellanali-transformer - kotsi ea ho senyeha ha tanka le lihlahla.
- Hlahloba likhoeli tse ling le tse ling tse 3: tekanyo ea khatello, boemo ba oli, ho lutla, ho bola.
- Haeba tekanyo ea khatello e bala lefela kapa ho theoha ha oli, etsa lipatlisiso 'me u lokise ho lutla.
- Boloka khatello e nyane e ntle (3-4 PSIG) ka moea o omileng kapa naetrojene ha ho khonahala.
3. Mehato ea ho kenya
3.1 Khetho ea sebaka
Latela IEEE C57.12.00 "Usual Service Conditions":
- Bophahamo bo Tlase kapa bo lekana le 1000 m
- Thempereichara ea tikoloho -25℃ho isa ho +40 degree
- Ha ho lerōle le feteletseng, likhase tse senyang, ho thothomela, kapa kotsi ea likhohola.
Kenya sebakeng se ka fihlellehang feela ke basebetsi ba lumelletsoeng (mohlala, letlapa le notletsoeng kapa palo).
Boloka li-radiator (haeba li le teng) li se na litšitiso.
3.2 Ho kenya lipalo
Sebelisa masakana a hanger a fanoeng bakeng sa ho hloma lipalo ka kotloloho.
Matla a pole a tlameha ho ts'ehetsa boima bo felletseng ba transformer (sheba nameplate).
Ka mor'a ho hloella, sekamela ka tsela efe kapa efeha ea lokela ho feta likhato tse 3. Ho sekama ho feteletseng ho ka:
- Fokotsa ho koahela metsi a sireletsang likarolo tse phelang.
- Senya ho potoloha ha pholiso.
- Fana ka litekanyo tse fosahetseng tsa oli.
3.3 Ho beha fatše
Sebelisa lesebaka se inehetseng sa motheo kapa nateka tanka.
Khondara ea fatše (hangata koporo, E kholo ho feta kapa e lekanang le 16 mm²) e tlameha ho lumellana le likhoutu tsa lehae.
Ho hanyetsa fatše ho lokela ho ba tlase ho ea kamoo ho hlokoang ke melao ea lehae (hangata Ka tlase ho kapa ho lekana le 10 Ω).
Le ka mohlasebelisa li-hanger brackets, lihlahla kapa likarolo tse ling tseo e seng tsa motheo bakeng sa ho thea fatše.
Kopanya bohle ba fumanehang ho se nke lehlakore ho tsamaiso e sa nke lehlakore.
3.4 likhokahano tsa HV le LV
Hloekisa 'me u bethefatsa libaka tsohle tsa likhokahanyo tsa ho nyalana pele u hokela.
Latela setšoantšo sa khokahanyo letlapeng la mabitso.
Tiisa liboutu ho boleng ba torque e fanoeng ho Lethathamo la 3 (sheba Karolo ea 8).
Qoba meroalo e mengata ea li-cantilever holim'a lihlahla (u se ke ua hula li-conductors ka thata haholo) - ho seng joalo ho ka ba le tšenyo ea bushing kapa gasket.
Li-terminal caps tse kentsoeng ka lehlakoreng la HV li thusa ho thibela ho kopana le liphoofolo tse hlaha.
3.5 Ho hlophisa bocha likhokahano tsa kahare tsa LV (haeba ho hlokahala)
Boemo: Transformer e nang le lihlahla tse tharo tsa LV, feme-set bakeng sa E/2E (mohlala. 120/240 V), empa e hloka motlakase oa E (mohlala. 120 V).
Mokhoa:
- Fokotsa matla, fatše, imolla khatello (sebetsa PRV).
- Tlosa sekoahelo sa transformer kapa sekoahelo sa letsoho (sheba Karolo ea 8.7).
- Hokela hape LV ho tloha letotong ho ea ho tse tšoanang joalo ka ha ho bonts'itsoe setšoantšong sa nameplate.
- Etsa bonnete ba hore likhokahano tsohle li tiile (sebelisa tafole ea torque), li-lead li kentsoe hantle, 'me ha li ame tanka kapa tse ling.
- Kenya sekoaelo hape, tlatsa boemo bo nepahetseng, lumella lihora tse 24 ho lula, ebe u etsa tlhahlobo ea karolelano ho netefatsa.
Ikopanye le moetsi haeba o sa tiisehe.


4. Tlhahlobo ea Pele ho Matla le Liteko
Transformer ha ea lokela ho matlafatsoa ho fihlela licheke le liteko tse latelang li phethiloe ka katleho.
|
Che. |
Teko / Hlahloba |
Lintlha |
Boemo ba ho amohela |
|
1 |
Teko ea tekanyo (TTR) |
Sebelisa tlhahlobo ea karo-karolelano ea li-transformer libakeng tsohle tsa lipompo |
Ka tlase ho kapa ho lekana le ±0.5% |
|
2 |
Ho hanyetsa mocheso |
1000 V megger; sebaka se matsoelintsoeke le se matsoelintsoeke |
E kholo ho feta kapa e lekana le 1.0 GΩ (hloekile/omileng) |
|
3 |
Boemo ba ho switjha ha li-multiple-voltage |
Beha joalo ka letlapa la mabitso, sekoti sa ho notlela se kentsoe |
Boemo bo nepahetseng |
|
4 |
Tlanya boemo ba switjha |
E behiloe ho matla a lekantsoeng (hangata theipi e bohareng) |
Boemo bo nepahetseng |
|
5 |
Ho thethefatsa |
Tekanyo ea pono + ea ho hanyetsa fatše |
Sireletsehile, ka har'a moeli oa lehae |
|
6 |
Lihokelo tse koetsoeng |
Tlhahlobo ea torque ho ea ho Litafole 1-4 |
Ka har'a sebaka sa torque |
|
7 |
Boemo ba mokelikeli |
Level gauge kapa sight plug |
Pakeng tsa "Phahameng" le "Low" |
|
8 |
Mocheso oa metsi |
Bala thermometer |
Ha e tlase bonyane bo lumelletsoeng (sheba ka tlase) |
|
9 |
Internal Fault Detector (IFD) |
Tlosa senotlolo sa orange |
Senotlolo se tlositsoe |
|
10 |
Li-transformer tsa hajoale (CTs) |
Haeba e sa hokahane le mojaro, lithapo li tlameha ho khutsufatsoa le ho theoa fatše |
Ha ho potoloho e bulehileng |
|
11 |
Wiring ea lisebelisoa |
Taolo, li-circuits tsa alamo - ha ho na likhokahano tse hlephileng kapa li-insulation tse senyehileng |
Boemo bo botle |
|
12 |
Qetellong ea tanka |
Pente - ha ho na tšenyo, mafome |
E amohelehang |
Bonyane mocheso o lumelletsoeng oa mokelikeli pele o matlafatsa:
- Oli ea liminerale / silicone: -20 likhato
- Mocheso oa R‑: 0 degree
- FR3: -10 likhato
Haeba mokelikeli o bata haholo, o futhumale butle-butle (mohlala, ka likobo tsa ho futhumatsa) pele o ka o matlafatsa.


5. Litlhahlobo tsa Post-Energization
Kamora ho fumana matla a pele (haholo-holo ho tsoa sebakeng se hole), etsa:
- Netefatsa motlakase oa bobeli- E lokela ho ba ka hare ho ± 5% ea boleng bo lekantsoeng ba nameplate.
- Hlahloba ho dutla- Lekola litšepe, lihlahla, li-valve, li-gauge bakeng sa phepelo efe kapa efe ea oli.
- Sheba ts'ebetso- Ha ho na ho thothomela ho sa tloaelehang, mosi, tlhase kapa lerata le sa tloaelehang.
- Sheba li-gauge- Boemo ba oli bo lokela ho nyoloha (ha mocheso o ntse o eketseha), thermometer e lokela ho eketseha butle-butle, tekanyo ea khatello-vacuum e lokela ho bontša khatello e ntle.
- Molumo o utloahalang- E tloaelehileng ke "hum" e tsitsitseng (magnetostriction).
Ho petsoha / ho qhoma ha nakoana → ho qhalana ho ka bang teng holim'a lihlahla.
Ho lla ka molumo oa arcing → khokahano e hlephileng ea kahare kapa taba ea mantlha.
Ho lla haholo → ho hlasimoloha ho feta tekano kapa ho tlala matla.
- Infrared thermography (boikhethelo)- Lekola likhokahano tsa terminal bakeng sa libaka tse chesang.
6. Ts'ebetso ea ho fetola le ho sireletsa lisebelisoa
6.1 Melao e akaretsang
- Sebelisa asesebelisoa sa mohala (hot stick kapa shotgun stick)bakeng sa lisebelisoa tse etselitsoeng ts'ebetso e joalo. Le ka mohla u se ke ua sebetsa ka letsoho.
- Kamehla fokotsa matla 'me u thehe fatše pele u sebelisa sesebelisoa leha e le sefe kapa u fetola li-fuse.

6.2 Mochine oa ho fetola lipompo o se nang matla
E sebetsa feela ha transformer e feletsoe ke matla.
Mokhoa:
- Ho fokotsa matla le ho theoha.
- Tlosa sekoti sa ho notlela (haeba se fanoe).
- Fetola sebapa ho ea sebakeng seo u se batlang (sheba ho nameplate le ho daela).
- Kenya hape sekoti sa ho notlela.
Boemo ba fektheri hangata ke boemo ba voltage e lekantsoeng.
6.3 Li-switch tsa motlakase tse ngata
- Hape ts'ebetso e se nang matla feela.
- Boemo ba feme hangata ke boemo bo phahameng ka ho fetisisa ba motlakase.
- Haeba lipompo ka bobeli le li-multiple-voltage windings li le teng, etsa bonnete ba hore toipi e boemong bo bontšitsoeng ho nameplate ha sesebelisoa sa multiple-voltage se le sebakeng se bapileng.
6.4 Sekhechana sa potoloho se tlase-tlase
- E lutse ka lehlakoreng la tanka, e sebetsoa ka thupa e chesang.
- Tšoara maemo:O= BULA,C= E TLWAELETSWE,R= TLHOMA TSELA
- After trip: turn toR, ebe hoC.
- Ho ikhethela lever ea tšohanyetso ea maemo a tšohanyetso: potoloha ho "EO" bakeng sa bokhoni ba nakoana ba boima bo feteletseng (≈30% ka holimo ho tekanyo). Fokotsa tšebeliso ho qoba bophelo bo fokotsehileng ba li-transformer.
- Leseli la pontšo (ho ikhethela): le khantša ka mor'a ho imeloa haholo; seta hape ha sebapi se reteletsoaR.
TLHOKOMELO: Le ha sekheo se bulehile, capacitive coupling e ka baka kotsi e ts'oenyehileng litsing tsa bobeli tse se nang motheo. Kamehla u theole li-terminals tsa bobeli pele u sebetsa.

6.5 Magnex interrupter
Sesebediswa sa ka hare sa oli se qoeletseng ho feta tekano le mocheso o feteletseng bakeng sa lehlakore la HV.
Ho sebetsa ka hot stick:
- Bula: fetosa motshwaro ho ya hodimo (ho fapana le wa tshupanako) ho ya ho BULA boemo.
- Koala: retelletsa setshwano se shebileng tlase (ho ya ka tshupanako) ka thata kgahlanong le setopong sebakeng se TLOLWENG.
- Seta bocha kamora leeto: pele ho BULA, ebe ho TLOA.
Tlamo ea maemo a tšohanyetso (EO) ka boikhethelo: sebakeng sa OPEN, fetola lever ea EO ho ea ho EO, ebe u koala.
Pontšo ea leeto la boikhethelo: lense ea lamunu e hlaha ha e khoptjoa.
6.6 Li-Fuse
Khokahano e fokolang ea fuse: e behiloe setsing sa HV bushing kapa switch; e sireletsa khahlanong le boima bo feteletseng le liphoso tsa ka hare.
Fuse e fokotsang mefuta e sa fellang: ka letoto le nang le sehokelo se fokolang; e fokotsa matla bakeng sa mathata a mangata a ka hare.
Phetoho:
- Hlalosa le ho lokisa sesosa sa ts'ebetso pele o kenya e 'ngoe.
- Sebelisa lintlha le litšobotsi tse tšoanang.
- Fokotsa matla, fatše, tanka e bulehileng (sheba Karolo ea 8.7) ho fihlella.

6.7 Sekoahelo sa surge
- Motho ea ts'oereng kantle: cheke li-lead le likhokahano tsa fatše li tiile (tafole ea 3 ea torque).
- Mots'oari oa ka hare oa MOV (ho ikhethela): ho qoelisoa ka oli; karolelano mocheso oa mokelikeli ha oa lokela ho feta likhato tse 90, max 125℃.
- Pele o etsa liteko tse ka bang teng ka tšohanyetso kapa tse susumetsoang, khaola sets'oants'o(ka ntle le ka hare). Kopana hape ka mor'a tlhahlobo.
7. Ts'ebetso ea Bushings, Gauges le Accessories
|
Sesebelisoa |
Lesupa / tshebediso e tlwaelehileng |
E sa tloaelehang/ Ketso |
|
Khatello-vacuum gauge |
E fapana ka mojaro le mocheso; positive, ha ho chesa, e ka ba mpe ha ho bata |
Kamehla lefela → ho lutla ho ka bang teng, batlisisa |
|
Tekanyo ea boemo ba oli |
Ka likhato tse 25, pointer pakeng tsa "H" le "L"; e nyoloha ka mocheso |
Ka tlase ho "L" → eketsa mokelikeli 'me u hlahlobe ho lutla |
|
Thermometer ea oli |
Mocheso o phahameng oa oli hangata o ka tlase ho kapa o lekana le likhato tse 85; khubelu hula letsoho direkoto max |
>95℃→ hlahloba mojaro, pholiso, boemo ba mokelikeli |
|
Sesebediswa sa ho hula / sampole |
Hlakola kapa u nke lisampole ka tlase ho tanka |
E dutlang → nka sebaka sa gasket kapa valve |
|
Valve ea ho imolla khatello ea maikutlo (PRV) |
E bula ha khatello ea ka hare e feta tekanyo e behiloeng, ebe e tsosolosa |
Ka mor'a ts'ebetso, batlisisa sesosa |
|
Internal Fault Detector (IFD) |
E hlahisa folakha e sa khoneng ho hlophisoa bocha ha ho hlaha phoso ea ka hare ea arcing |
Folakha ea Orange e bonahala → transformer e na le phoso,se fe matla |
Tlhokomeliso ea IFD: IFD ke sesupo sa pono feela, eseng ho khaoha ha motlakase. Esita le haeba IFD e sa sebetse, transformer e ntse e ka ba le phoso. Le ka mohla u se ke ua itšetleha ka eona e le sesebelisoa sa tšireletso se timang matla.

Khatello-vacuum gauge

Tekanyo ea boemo ba oli

Thermometer ea oli

Sesebediswa sa ho hula / sampole

Radiator

Internal Fault Detector (IFD)
8. Tlhokomelo le Tokiso
8.1 Linako tse khothaletsoang tsa tlhokomelo
|
Karohano |
Ketsahalo |
|
Khoeli le khoeli (mosebetsi o boima kapa tikoloho e thata) |
Tlhahlobo ea ho lutla ha pono, boemo ba oli, molumo o sa tloaelehang, IR thermography |
|
Likhoeli tse ling le tse ling tse 6 |
Tlhahlobo ea pente, tiisa liboutu, li-radiator tse hloekileng |
|
Selemo le selemo |
Sampling ea oli (matla a dielectric, litaba tsa metsi, acidity, DGA) |
|
Lilemo tse ling le tse ling tse 3 |
Khanyetso ea insulation, tlhahlobo ea karolelano, tlhahlobo ea matla |
|
Ka mora phoso kapa ntho e sa tloaelehang |
Tlhahlobo ea oli e potlakileng le liteko tsa motlakase |
8.2 Qetello ea ho penta ka ntle
Haeba primer kapa tšepe e se nang letho e pepesitsoe, lokisa hang-hang ho thibela kutu:
- Hlahisa sebaka seo ho tlosa mafome le pente e hlephileng.
- Hloekisa ka solvent (tlosa oli, grease).
- Sebelisa sebolaea-mafome sa pele.
- Tšela lijase tse peli tse kaholimo (sebelisa pente ea moetsi haeba e le teng).
8.3 Ho lokisoa ha metsi a lutlang
Netefatso e dutseng:
- Hloekisa sebaka se belaetsang, sebelisa talc kapa mokelikeli o lemohang ho lutla.
- Tobetsa tanka e nang le moea o omileng kapa naetrojene ho 3-4 PSIG, ema lihora tse 1-2, hlahloba.
Mekhoa ea ho lokisa:
- Ho lutla ha sekoti kapa seketsoana sa weld holim'a tanka: fokotsa matla, drain, weld (welder ea tšoanelehang).
- Radiator leak: u se ke ua cheselletsa (lisebelisoa tse tšesaane); fetola kapa sebelisa lisebelisoa tsa ho lokisa epoxy.
- Leak: leka ho tiisa liboutu tsa li-clamp (torque Letlapa la 2); haeba e hloleha, nka sebaka sa gasket.
- Ho dutla ha valve kapa gauge: nka sebaka sa gasket kapa karolo e felletseng.
8.4 Tlhokomelo ea mokelikeli o thibelang metsi
Mokhoa oa ho etsa mohlala:
- Ho fokotsa matla le ho theoha.
- Hlakola valve ea drain ka oli e nyane.
- Nka sampole ka sejaneng se hloekileng, se omeletseng, qoba khanya ea letsatsi.
- Tiisa hang-hang 'me u romele bakeng sa tlhahlobo.
Mekhoa e tloaelehileng ea ho amohela (oli ea liminerale):
|
Paramethara |
Boleng bo amohelehang |
|
Matla a dielectric |
E kholo ho feta kapa e lekana le 26 kV |
|
Likahare tsa metsi |
Ka tlase ho kapa ho lekana le 35 ppm |
|
Asiti |
Ka tlase ho kapa ho lekana le 0.1 mg KOH/g |
|
Ntho ea matla @25 degree |
Ka tlase kapa ho lekana le 0.5% |
Sefa:
- Sebelisa mochini oa ho hatisa ho fihlela matla a dielectric A maholo ho feta kapa a lekana le 26 kV.
- U se ke ua kopanya mefuta ea mokelikeli; mochini o hloekisang o tlameha ho se be le litšila tse tsoang marong a mang.
Ho tlatsa hape:
- Sebelisa mofuta o tšoanang hantle le mofuta oa mokelikeli.
- Pompa butle ho tloha tlase ho tanka ho qoba lipululana tsa moea.
- Tlatsa moleng o tšoailoeng ka har'a tanka, ebe u lumella lihora tse 24 hore moea o tsoe pele o matlafatsa.
8.5 Liteko tsa motlakase (nako le nako kapa tsa tlhahlobo)
|
Teko |
Mokhoa |
Kamohelo |
|
Ho hanyetsa mocheso |
1000 V kapa 2500 V megger |
E kholo ho feta kapa e lekana le 1 GΩ (e omileng) |
|
Karolelano (TTR) |
Mohlahlobi oa TTR |
±0.5% |
|
Insulation power factor |
2.5 kV kapa 10 kV borokho |
Ka tlase ho kapa ho lekana le 0.5% @20 degree |
|
Winding DC khanyetso |
Microohmmeter |
Ho kheloha Ka tlase ho kapa ho lekana le 2% lipakeng tsa mekhahlelo |
8.6 Litataiso tsa torque
Letlapa la 1 - Li-fasteners tsa ka ntle
|
Mofuta oa fastener |
Torque ka lebitso (ka-lbs) |
Sebaka sa torque (ka-lbs) |
|
3/8 ″ bolt |
240 |
220‑260 |
|
Bolt ea sekoahelo sa letsoho |
144 |
129‑158 |
|
Koahela band bolt |
180 |
170‑185 |
|
surge arrester mounting bolt |
420 |
372‑468 |
Letlapa la 2 - Hardware ea ka ntle ea bushing mounting
|
Mofuta oa Bushing |
Torque ka lebitso (ka-lbs) |
Sebaka sa torque |
|
LV e entsoeng ka Tri‑Clamp (ha e na selikalikoe), 3/8″ stud |
60 |
40‑80 |
|
LV e bōpiloeng (e nang le lesale la clamp), 3/8 ″ stud |
120 |
90‑150 |
|
LV porcelain (e nang le selikalikoe sa clamp), 1/2 ″ stud |
80 |
70‑90 |
|
Tri‑Clamp e entsoeng ka HV, 3/8 ″ stud |
60 |
40‑80 |
|
HV e bōpiloeng (e nang le lesale la clamp), 3/8 ″ stud |
120 |
90‑150 |
|
HV porcelain |
80 |
70‑90 |
Lethathamo la 3 - Lihokelo tsa li-terminal tsa kantle
|
Mofuta oa terminal |
Torque ka lebitso (ka-lbs) |
Sebaka sa torque |
|
HV porcelain bushing eye-bolt |
210 |
180‑240 |
|
HV porcelain bushing end cap |
168 |
156‑180 |
|
LV bushing 5/8 ″ jeme nut |
600 |
480‑720 |
|
LV bushing 1″ jeme nut |
600 |
480‑720 |
|
LV bushing 1‑1/4″ jeme nut |
720 |
600‑840 |
|
Molato oa ho ts'oara kantle |
180 |
162‑198 |
|
Motlatsi oa ka ntle oa pele oa fatše |
180 |
162‑198 |
Letlapa la 4 - Lisebelisoa
|
Karolo |
Torque ka lebitso (ka-lbs) |
Sebaka sa torque |
|
Liboutu tsa lihokelo tse fokolang tse kentsoeng ka Bushing |
85 |
80‑90 |
|
Polaka ea pono ea boemo ba mokelikeli |
960 |
900‑1020 |
|
Tlatsa polaka |
960 |
900‑1020 |
|
Hlakola polaka |
960 |
900‑1020 |
|
Valofo ea ho ntša metsi |
600 |
480‑720 |
|
PRV 1/4″ NPT |
180 |
160‑200 |
|
PRV 1/2″ NPT |
360 |
324‑396 |
|
Neutral strap fastener (setulong sa fatše) |
160 |
140‑180 |
|
Tlanya nate e ntseng e hola |
120 |
96‑144 |
Ka lebaka la khatholoho ea gasket, torque e lekantsoeng e ka ba tlase ho feta ka lebitso. Se ke oa itlama ho feta tekano - kotsi ea ho peperana kapa ho hatella ho feta tekano.
8.7 Ho bula tanka ea transformer
Feela ha ho hlokahala ka ho feletseng(mohlala, ho fetola fuse ka hare, ho lokisoa bocha ha LV, ho lokisa switch ka hare).
Mokhoa:
- Fokotsa matla, fatše, imolla khatello (sebetsa PRV ka thupa e chesang - hlokomela mokelikeli o chesang).
- Hloekisa sebaka se pota-potileng sekoahelo kapa mokoti ho thibela litšila ho kena.
- Tlosa liboutu, phahamisa sekoaelo ka hloko (sireletsa gasket).
- Haeba mokelikeli o tlameha ho theoleloa, pompa ka lijaneng tse hloekileng, tse omeletseng (o se ke oa theola mokelikeli ka tlas'a core/coil clamp pan - li-coil li tlameha ho lula li koahetsoe).
- Nakong ea mosebetsi: sebelisa likoahelo tse hloekileng, tse se nang letlapa; tlama lisebelisoa ka likhoele tsa polokeho ho thibela ho oela ka tanka.
- Se ke oa tlohela tanka e butsoe nako e fetang lihora tse peli.Haeba e sitisoa, koala hape 'me u tlatse ka moea o omileng kapa naetrojene.
- Pele o kenya sekoaelo hape, tlosa gasket e senyehileng. Tiisa liboutu ho torque ea Tafole ea 1.
- Tlatsa butle butle, lumella lihora tse 24 ho lula, ebe u etsa tlhahlobo ea ho hanyetsa insulation pele u matlafatsa.
9. Tataiso ea ho rarolla mathata
|
Letšoao |
Seo e ka bang sesosa |
Ketso |
|
Matla a bobeli a fosahetse |
Boemo ba ho theipi bo fosahetseng, khokahanyo e fosahetseng ea HV, fuse e fefotsoeng |
Fokotsa matla, hlahloba switjha ea pompo, wiring, fetola fuse |
|
Ho chesa haholo |
Ho jara, li-radiator tse koetsoeng, boemo bo tlase ba oli, phoso ea kahare |
Fokotsa mojaro, hloekisa li-radiator, eketsa oli, mohlala oa oli |
|
PRV e sebetsa |
Arc e ka hare, boima bo feteletseng, tlhahiso ea khase |
Fokotsa matla, hlahloba IFD, etsa DGA - u se ke ua tsosolosa matla ka bofofu |
|
folakha ea lamunu ea IFD e bonahala |
Phoso ea ka hare ea arcing |
Transformer e na le phoso - fetola unit |
|
Ho hanyetsa ho fokotseha ho fokolang |
Mongobo oa oli, lihlahla tse litšila, li-insulation tsa khale |
Hloekisa lihlahla, sefa kapa u nke sebaka sa oli, omella |
|
Lerata le sa tloaelehang (eseng hum e tloaelehileng) |
Motheo o hlephileng, motsamao o tsoelipanang, ho tsosoa ho feteletseng |
Fokotsa matla, karo-karolelano ea tlhahlobo le hona joale ha ho na moroalo |
|
Boemo ba oli bo theoha butle-butle |
Dutla |
Fumana 'me u lokise ho lutla, tlatsa holimo |
|
Khatello-vacuum gauge e lula e le zero |
Tanka Tiiso e lahlehile |
Teko ea dutla, lokisa, ebe o tsoa le ho tlatsa hape |
10. Litaelo tsa Ts'ebetso ea Transformer e Amanang le Ts'ebetso
Li-transformer tse kentsoeng ka lipalo li sebeletsa melapo ea kabo e holimo, empa lits'ebetso tse ngata tsa matla li hloka mekhoa e meng ea ho hola kapa mefuta e koetsoeng. Bakeng sa sete e felletseng ea ts'ebetso le ts'ebetso ea li-transformer, bona litataiso tse ling tse latelang.
- Tataiso ea Ts'ebetso ea Transformer ea Substation
- Tataiso ea Ts'ebetso ea Transformer ea Matla le Ts'ebetso
- Pad Mounted Transformer Installation le Tataiso ea Ts'ebetso
- Mofuta o omileng oa ho kenya Transformer le Tataiso ea Ts'ebetso
- Tataiso ea Ts'ebetso ea Compact Substation le Tataiso ea Ts'ebetso
11. Likarolo tsa Spare, Warranty le Disposal
10.1 Ho odara likarolo tse ling
Fana kanomoro ea serial ea transformer(ho nameplate), tlhaloso ea karolo, le bongata.
Ikopanye le thekiso ea moetsi kapa tšebeletso ea tekheniki.
10.2 Tiisetso
Tsebisa moetsi hang-hang haeba mathata a hlaha nakong ea waranti.
Litokiso tsohle tsa tiisetso li tlameha ho amoheloa kapa ho etsoa ke moetsi.
10.3 Ho lahla
Hlatsoa mokelikeli oohle o sireletsang pele o hlakola transformer.
Lahla lero ho latelamelaoana ea tikoloho ea lehae(o seke oa tšolla).
Tanka ea tšepe, mapheo a mantlha le a koporo a ka sebelisoa hape.
Mokelikeli o tsoang ho li-transformer tsa khale (pele ho 1970s) e kanna ea ba le li-PCB - tšoara joalo ka litšila tse kotsi.