Kirk key

Li-interlock tsa Kirk Key ke lisebelisoa tse khethehileng tsa ts'ireletso tsa mochini tse etselitsoeng ho fokotsa likotsi tsa motlakase lits'ebetsong tsa transformer ka mekhoa e tlamang ea ts'ebetso. Ho fapana le lilotlolo tsa mantlha kapa litšireletso tsa elektroniki, likhokahano tsena "tse qabeletsoe-linotlolo" li sebelisa mokhoa oa ho koala le oa ho lokolla ho thibela phihlello e sa lumelloeng ea lisebelisoa tse phelang, tšebeliso e mpe ea li-switchgear ka phoso, le liketsahalo tsa arc flash. Li bohlokoa bakeng sa ho latela litekanyetso tse joalo ka NFPA 70E le melaoana ea polokeho ea motlakase ea OSHA. Tataiso ena e atolositsoeng e hlahloba lintlha tsa bona tsa tekheniki, -mekhoa ea sebele ea ts'ebeliso ea lefats'e, le mekhoa e metle eo motho a ka e sebelisang, e tsepamisitse maikutlo haholo ho kenngoeng ha li-transformer.

 

 

1. Ho hlalosa Kirk Key Interlocks bakeng sa Transformers: Morero & Moralo oa Core

 

Li-interlock tsa Kirk Key ke tsa bohlokoa-litšitiso tse sebetsang tse etselitsoeng ho laola phihlello ea lik'habote tsa transfoma, li-switches, le switchgear ea holimo. Mosebetsi oa bona oa mantlha ke ho netefatsa hore li-transformer li teng feelade{0}matlapele o fuoa monyetla, 'me{0}}a tsosolosoa feela ka mor'a hore ho finyelloe melaoana eohle ea tšireletso (mohlala, ho koaloa ha khabinete, netefatso ea ho fetoha) Ho fapana le linotlolo tsa polokeho tse akaretsang, li rarolla lekhalo le mahlonoko: ho thibela phoso ea motho kaho thiba mmelengdiketso tse sa bolokehang (mohlala, ho bula khabinete ya transformer e phelang) ho ena le ho itshetleha ka ho latela melao ya mosebedisi feela.

 

1.1 Letoto la Sehlahisoa sa Bohlokoa bakeng sa Li-transformers

Mehala e 'meli ea mantlha ea sehlahisoa e sebetsana le tikoloho ea li-transformer, e' ngoe le e 'ngoe e ntlafalitsoe bakeng sa maemo a ikhethileng:

1.1/

SD Series (Kaho ea Brass)

E etselitsoe litlhophiso tsa ka ntle kapa tse bobebe tsa kantle (mohlala, li-transformer tse sirelelitsoeng tsa padmount). Matlo, cylinder housings, le plug/inturn turn shafts li entsoe ka koporo, tse nang le linotlolo tsa nickel-silver (7-pin tumbler style) bakeng sa ho thibela kutu libakeng tse seng thata-. Letoto lena le na le litšenyehelo tse ngata bakeng sa lisebelisoa tse tloaelehileng moo mocheso le mongobo li laoloang.

1.2/

HD Series (Kaho ea Stainless Steel)

E etselitsoe ka ntle ho makukuno,{0}}mocheso o phahameng, kapa tikoloho e senyang (mohlala, li-transformer tse sebelisoang libakeng tse lebopong la leoatle kapa litsing tsa indasteri). Likarolo tsohle tsa bohlokoa-matlo, cylinder, plug, le linotlolo (dowel pin style)-ke tšepe e sa tsitsang, e nolofalletsang ho sebetsa ka mocheso ho fihla ho 700 degrees F (371 degrees ) (vs{8}}℃F/121℃for SD Series).

square d kirk key interlock

1.2 Moeli o Bohloka oa ho Hlokomela

Habohlokoa, Kirk Key ho itšehla thajana ho hokahaneha lia etsoa e le litsamaiso tsa phihlello bakeng sa libaka tse kotsi ka kakaretso(mohlala, libaka tsa polokelo ea lik'hemik'hale tse bapileng le li-transformer). Sepheo sa bona ke ho laola phihlello ea lisebelisoa tsa motlakase le khabinete ea transformer ka ho tsamaisana le{3}}liprothokhole tsa matlafatso.

 

 

2. Kamoo Kirk Key Interlocks e Sebetsang Kateng: Transformer-Specific Workflow

Ntho ea mantlha ea ts'ebetso ea Kirk Key e hotrapped{0}}mochine oa bohlokoa, e hokahanyang ts'ebetso ea lisebelisoa tse peli kapa ho feta (mohlala, switchgear e holimo le khabinete ea transformer). Ka tlase ho na le lintlha tse qaqileng, tsa{3}}ka{4}karolo ea mohato oa tšebetso bakeng sa transformer e tloaelehileng ea padmount:

 

2.1 Naha ea Pele (Transformer E Matlafalitsoe)

  • Transformer e ntse e phela, e nang le sesebelisoa sa "upstream load break" (LBS) sebakeng se "koetsoeng".
  • Sehokelo sa Kirk Key se kentsoe ho LBS: senotlolo (mohlala, Key A-1) keqabeletsoeka har'a sehokelo, 'me boutu ea senotlolo sa tšepe e sa hloekang (5/8" bophara, maeto a tloaelehileng a 3/4") e khutlisetsoa morao-ho sireletsa mofeng oa LBS ho thibela ho buleha ka phoso.
  • Mohatla oa bobeli oa Kirk Key o kentsoe ka har'a khabinete ea transformer: bolt ea eona ea atolosoa, 'me e thibela lemati la khabinete hore le se bule.
 

2.2 Mohato oa 1: Tlosa-Eketsa Transformer Matla

  • Ho fihlella transformer, opareitara e qala ka ho bula LBS e holimo ho fokotsa matla. Ketso ena e hokahanya LBS le "boemo bo bolokehileng" ba interlock.
  • Opereishene e bulela senotlolo se qabeletsoeng (Key A-1) ho LBS interlock: sena se eketsa senotlolo sa senotlolo,ka 'mele e notlela LBS sebakeng se "bulehileng".(thibela{0}}matla hape) le ho lokolla Key A-1.
 

2.3 Mohato oa 2: Fihla ho Kabinete ea Transformer

  • Key A-1 e lokollotsoeng e kentsoe kahare ho khabinete ea transformer. Ho phethola senotlolo ho khutlisa boutu e notletsoeng ea khabinete, ho lumella lemati hore le bulehe.
  • Hang ha lemati la khabinete le bulehile, senotlolo (Key A-1) se fetohaqabeletsoe hapeka har'a kokelo ea khabinete{0}}ho netefatsa hore lemati ha le khone ho koaloa ('me senotlolo ha se khone ho khutlisoa) ho fihlela tlhokomelo e felile.
 

2.4 Mohato oa 3: -Etsa Matla ho Transformer

  • Ka mor'a tlhokomelo, opareitara e koala khabinete ea transformer. Sena se hokahanya khabinete le "boemo bo bolokehileng" ba interlock, se lokolla Key A-1.
  • Senotlolo A-1 e khutlisetsoa ho khokahanyo ea LBS. Ho fetola senotlolo ho hula boutu ea LBS interlock, ho lumella LBS hore e koaloe-ho matlafatsa transformer hape.
 

2.5 Special Case: Multi-Cylinder HD Series Interlocks

Bakeng sa lisebelisoa tse rarahaneng tsa li-transformer (mohlala, li-loop feed tse nang le 2+ switch), HD Series multi-cylinder interlocks e hlokalinotlolo tsohle tse sieo ho kengoa le ho phetholapele senotlolo leha e le sefe se qabeletsoe se ka lokolloa. Ka mohlala, 3-cylinder HD interlock e laolang liswichi tse peli e tla hloka Key 1 (ho tloha ho Switch A) le Key 2 (ho tloha ho Switch B) e kenngoeng pele Key 3 (bakeng sa khabinete) e lokolloa-e eketsa tšireletso bakeng sa lisebelisoa tsa lisebelisoa tse ngata.

kirk key lock

 

 

 

 

 

 

 

3. Likaroloana tsa Motheo le Litlhaloso tsa Setekheniki (Transformer-E tsepamisitse maikutlo)

 

 

Li-interlocker tsa Kirk Key tsa li-transformer li na le{0}karolo ea likarolo tse 'ne tseo ho seng motho ea ka buisanang ka tsona, e 'ngoe le e 'ngoe e na le lintlha tse ntlafalitsoeng bakeng sa polokeho ea motlakase le ho tšoarella nako e telele. Ka tlase ke karohano e qaqileng, ho kenyelletsa le li-nuances tsa tekheniki tse amang kopanyo ea transformer:

Karolo

SD Series Lintlha

HD Series Lintlha

Transformer-Karolo e Itseng

Matlo & Cylinder

Brass (ho bola-e hanana le tikoloho e bobebe); sebopeho se bataletseng/sefahleho{1}}

304/316 Stainless Steel (e hanela letsoai, mongobo le mocheso o phahameng); setaele se tšoanang sa thaba.

E kenyelletsa mekhoa ea ka hare; e hokela khabinete ea switchgear/transformer ka masoba a holang a 0.4062" (10.32mm).

Notlela Bolt

5/8" bophara ba tšepe e sa hloekang; leeto le tsitsitseng la 3/4"; bolelele 0"–7" (e ka tloaeleha).

Boholo bo tšoanang ba bolt / leeto; bolelele 0"–7"; matla a phahameng bakeng sa tshebediso e boima.

Ho thibela 'mele mamati a li-switches / cabinet; e tlameha ho ikamahanya le li-switches tsa transformer (hangata 1-1.5" projeke ea likhabinete tse tloaelehileng).

Senotlolo

Nickel{0}}silefera; 7-tumbler ea pin (moralo o khahlanong le ho khetha); e kenyelelitsoe le silindara ka 'ngoe.

Ts'epe e sa beng le mabali; dowel pin (tamper-resistant); e rekisoang ka thoko.

E tiisa ts'ebetso ea tatellano; Meetso ea 7-pin/dowel e thibela phetiso ea senotlolo e sa lumelloeng.

Litokisetso tsa ho Beha

Bokaholimo{{0}e kentsoeng; Likoti tse 2 (bophara ba 0.4062) bakeng sa li-cylinders tse 1-4.

Ho kenya motheo o tšoanang; 5+ li-cylinders li eketsa likoti{1}} tse kentsoeng (7/8" ho tloha pheletsong e 'ngoe le e 'ngoe).

E netefatsa khokahano e hokahaneng le likarolo tsa transformer (mohlala, mofeng oa LBS, latch ea khabinete). Bakeng sa lisilindara tsa 5+, kakaretso ea bolelele=9.5" (24.13cm) + 1.5" (38.1mm) ka silindara e 'ngoe.

3.1 Litekanyetso tsa Botekgeniki tsa Bohlokoa

  • Mocheso Range: SD Series (-65 degrees F ho ya ho +250℃F/-54℃to +121℃) bakeng sa ditransfoma tsa ka tlung; HD Series (-65℃F ho ya ho +700℃F/-54℃to +371℃) bakeng sa diyuniti tsa kantle/maindasteri.
  • Boima ba 'mele: 1.83 lbs (SD Series, 1-cylinder) vs. 1.58 lbs (HD Series, 1-cylinder) -e bohlokoa haholo bakeng sa ho kenya likhabote tsa transformer tse bobebe.
  • Bolt Projeke: Boholo ba 7" bakeng sa letoto ka bobeli; likhetho tse tloaelehileng bakeng sa li-transformer: 1" (25.4mm) bakeng sa lik'habote tse tšesaane, 1.5" (38.1mm) bakeng sa libaka tse tloaelehileng tsa padmount.

 

 

 

 

4. Tataiso ea ho Kena: Mohato-ka-Mohato oa Transformers

 

Kenyelletso e nepahetseng ke motheo oa ts'epahalo ea Kirk Key{0}}ke feela basebetsi ba nang le bokhoni, ba tšoanelehang(ka koetliso ea polokeho ea motlakase le ho tloaelana le litsamaiso tsa transformer) e lokela ho etsa mosebetsi ona. Ka tlase ho na le lintlha tse qaqileng,{1}}mokhoa oa ho kenya transformer{1}}ka ho khetheha:

 

4.1Pele{1}}Tokisetso ea ho Kenya

(1) Netefatsa Tšebelisano:

  • Netefatsa hore moetsi oa transformer / switchgear o fana ka lipehelo tse ntseng li eketseha bakeng sa interlock ea Kirk Key.
  • Sheba hore na letoto la li-interlock (SD/HD) le lumellana le tikoloho (mohlala, HD bakeng sa li-transformer tsa kantle libakeng tse lebopong la leoatle).
  • Bokella lisebelisoa: cheka (bakeng sa masoba a tloaelehileng, ha ho hlokahala), wrench ea torque (ho boloka liboutu tsa 0.4062"), le setšoantšo sa tekheniki sa interlock.

(2) Tokisetso ea Bohlokoa ba Tsamaiso:

  • Bakeng sa SD Series: Tlosa linotlolo ho silindara e 'ngoe le e 'ngoe (e kenyellelitsoeng le yuniti) 'me u li ngole (mohlala, "LBS Key A-1," "Cabinet Key A-1") ho qoba ho kopana.
  • Bakeng sa HD Series: Netefatsa hore linotlolo tse otarang ka thoko li teng-saeteng; senya linotlolo tse eketsehileng (Kirk ha a ikarabelle bakeng sa likotsi tsa polokeho ho tsoa ho linotlolo tse sa tsejoeng).

 

4.2 Mohato oa 1: Mount Interlocks ho Switchgear (Upstream LBS)

  • Lokisetsa Interlock: Beha sekoahelo e le hore senotlolo sa senotlolo, ha se atolosoa, se tla thibela 'mele ho sebetsana le LBS ho tloha ho ea "koalloa." Tšoaea maemo a masoba a ntseng a hola u sebelisa template ea interlock.
  • Sireletsa Interlock: Qeta masoba a 0.4062" (10.32mm) (haeba ho se{2}lipehelo tse phuntsoeng) 'me u fate sebaka se hokahaneng ka liboutu tse sa jeng ({3}}torque ho 15–20 ft{6}}lbs bakeng sa brass/tšepe).
  • Teko ea Bolt Travel: Atolosa/hula boutu ho netefatsa hore e hokahana le mofeng oa LBS-ha hoa lokela ho ba le likheo (bolt e tlameha ho hokahana ka botlalo ha e atolosoa) .

 

4.3 Mohato oa 2: Mount Interlocks ho Transformer Kabinete

  • Boemo bakeng sa Polokeho: Kenya sehokelo lemating la khabinete kapa foreime e le hore boutu, ha e atolosoa, e thibele lemati ho buleha. Netefatsa hore bolt e hokahana le karolo e thata ea khabinete (mohlala, poleiti ea latch) ho qoba ho kobeha.
  • Sireletsehile le Teko: Tiisa sekoahelo joalo ka Mohato oa 1. Koala khabinete 'me u atolose boutu{1}}netefatsa hore lemati ha le khone ho buloa; hula bolt 'me u netefatse hore lemati le buleha ka bolokolohi.

 

4.4 Mohato oa 3: Teko ea Tatelano ea Sistimi{2}}Boemo

Ona ke mohato oa bohlokoa ka ho fetesisa{0}}ho lekola tšebetso e felletseng ho netefatsa hore ha ho na likheo tsa polokeho:

  • Matlafatsa transformer 'me u tiise hore LBS interlock maraba senotlolo, le khabinete interlock thibela lemati.
  • Tlosa-matla ho LBS, bula senotlolo ho e lokolla, 'me u e sebelise ho notlolla khabinete (senotlolo se tlameha ho koala khabinete e kenang).
  • Koala khabinete, khutlisa senotlolo, 'me u se sebelise-ho matlafatsa LBS hape.
  • Bakeng sa-li-cylinder interlocks tse ngata: Lekola ka linotlolo tsohle tse hlokahalang ho netefatsa hore ha ho linotlolo tse lokollotsoeng ho fihlela li kentsoe kaofela .

 

4.5 Liphoso Tse Tloaelehileng tsa Tlhophiso tseo u lokelang ho li Qoba

  • Bolt e sa sebetseng hantle: Boutu e sa amaneng ka botlalo le sebapi sa switjha/latch ea khabinete e ka hloleha ho thibela liketso tse sa sireletsehang-e sebelisa li-shim ha ho hlokahala ho lokisa maemo.
  • Ho Feta-Torquing Bolts: Ho tiisa ho feta-ho ka ntlafalletsa matlo a SD Series{1}}ho khomarela 15–20 ft-lb torque range.
  • Ho hlokomoloha Key Labeling: Linotlolo tse sa ngolisoang li lebisa liphosong tsa tatelano (mohlala, ho sebelisa senotlolo se fosahetseng bakeng sa khabinete)-sebelisa li-tag tse sa feleng.

 

 

 

 

5. Mekhoa e Molemo ka ho Fetisisa ea Tlhokomelo: Ho Etsa bonnete ba ho Tšepahala-Nako e Telele

 

 

Li-interlock tsa Kirk Key li hloka tlhokomelo e fokolang, empa li itšetlehile ka tlhokomelo ea kamehla ho qoba ho kobeha kapa ho hloleha-haholo bakeng sa polokeho ea transfoma. Ka tlase ke kemiso le mehato e ka etsoang:

5.1 Lenane la Tlhokomelo (Transformer-E khethehileng)

Mosebetsi oa ho hlokomela

Khafetsa

Lintlha tsa SD Series

HD Series Notes (Kantle/Maindasteri)

Tlhahlobo ea Pono

Beke le beke (nakong ea tlhahlobo ea transformer)

Sheba hore na ha ho kutu ea koporo, liboutu tse hlephileng, kapa tšenyo ea linotlolo.

Sheba hore na ha ho na mafome a tšepe e sa hloekang, maloanlahla a silindara kapa liboutu tse kobehileng.

Dry Graphite Lubrication

Likhoeli tse ling le tse ling tse 6 (ka tlung); Likhoeli tse 3 (ka ntle)

Lubricate senotlolo le silindara.

Lubricate inner turn shaft (ka morao ho silindara).

Tlhahlobo ea Sekoahelo se Sireletsang

Khoeli le khoeli

Ho ikhethela (ka tlung); hlahloba mapetsong ha e sebelisoa.

Tlamahano; hlahloba ho kena kapa ho senyeha ha metsi.

Tlhahlobo e Felletseng ea Tatelano

Selemo le selemo (nakong ea tlhokomelo ea transformer)

Lekola senotlolo sa ho ts'oara / ho lokolla le leeto la bolt.

E tšoanang le SD; eketsa tlhahlobo ea kutu bakeng sa liboutu.

 

5.2 Litaelo tse qaqileng tsa ho tlotsa

Ke hobane'ng ha Graphite?: Le ka mohla u se ke ua sebelisa oli kapa mafura{0}tsena li hohela litšila le lerōle, tse tlamellang moqomo ha nako e ntse e ea . Dry powder graphite (Kirk's GL-1 Kit) ea sebetsa 'me e ke ke ea theola likarolo tsa mochini.

SD Series Lubrication:

  • Sebelisa graphite e nyane ho senotlolo (ligrama tse 1-2, tse lekaneng ho roala holim'a metsi).
  • Kenya senotlolo ka har'a silinda 'me u e sebetse ka hare/tsoa makhetlo a 5-6.
  • Fetolela senotlolo ka ho ea ka nako/ho lebahaneng ka makhetlo a 3–4 ho aba graphite ka har'a silinda .

HD Series Lubrication:

  • Tlosa senotlolo 'me u fumane shaft e ka hare (ka mor'a silinda).
  • Sebelisa graphite ka ho toba ho shaft (sebelisa brush e nyenyane ho fihla libakeng tse thata).
  • Kenya senotlolo 'me u se fetole ka makhetlo a 4-5 ho jala graphite.

 

5.3 Likoahelo tse Sireletsang: Ho Sireletsa Li-Interlock tsa Kantle

Bakeng sa li-interlocks tsa HD Series ho li-transformer tsa kantle, sebelisa likoahelo tsa boikhethelo tsa Kirk:

  • Push-Ka Khabara (Karolo C): Bakeng sa{0}}libaka tse tlase tsa sephethephethe; qhoma holim'a silindara ho thibela maloanlahla ho kena.
  • Fetola-Bula Likhase (Karolo F): Bakeng sa{0}}libaka tse phahameng tsa sephethephethe (mohlala, li-transformer tsa padmount tse fihleloang hangata); kenyeletsa lipehelo tsa LOTO (Lockout-Tagout) ho sireletsa tšireletso nakong ea tlhokomelo .

 

5.4 Tharollo ea Mathata a Tloaelehileng

Letšoao

Lebaka

Tharollo

Senotlolo se ke ke sa kenya silinda

Kaho ya ditshila/maloanlahla

Lubricate ka graphite; fokela moea o petelitsoeng ka har'a silindara.

Bolt e ke ke ea hola/ho hulanya morao

Boutu e kobehileng kapa sehokelo se sa lokang

Hlahloba bolt bakeng sa ho kobeha; fetola sehokelo ha ho hlokahala.

Maraba a bohlokoa pele ho nako

Kabinete / switjha ha e "boemo bo bolokehileng"

Hlahloba ho tsamaisana ha sehokelo le sesebelisoa (mohlala, khabinete e sa koaloa ka botlalo).

 

 

 

 

6. Transformer-Lisebelisoa tse Ipehileng: Sebele{2}}Maemo a Tšebeliso ea Lefatše

 

Li-interlock tsa Kirk Key li na le mefuta e mengata ho pholletsa le mefuta ea li-transformer-ho tloha libakeng tsa bolulo tsa padmount ho ea ho li-transformer tsa indasteri. Ka tlase ke lits'ebetso tse atileng haholo, tse nang le ts'ebetso e qaqileng:

 

6.1 Kopo ea 1: Likhabinete tsa Padmount Transformer (Bolulo/Khoebo)

  • Sepheo: Thibela-basebetsi ba sa lumelloeng (mohlala, basebetsi, borakonteraka) ho bula lik'habote tse phelang.
  • Tlhophiso: Khokahano e le 'ngoe mochining o ka holimo oa lisebelisoa (mohlala, switch ea 12kV load break switch) le e 'ngoe khabineteng.
  • Mokhoa oa ho sebetsa: Joalokaha ho hlalositsoe Karolong ea 2-feela ka mor'a hore sesebelisoa sa utility se buloe ('me senotlolo se lokolloe) khabinete e ka fumanoa. Sena se bohlokoa bakeng sa ho fokotsa likotsi tsa arc flash nakong ea tlhahlobo ea metara kapa tlhokomelo e nyane.
Padmount Transformer with Kirk key
Padmount Transformer with Kirk key interlock

 

6.2 Kopo ea 2: Liphetoho tsa Load Break (Industrial Transformers)

Sepheo: Thibela ts'ebetso e ts'oanang ea li-switches tse peli tsa khefu ea mojaro (LBS) ho potoloho ea bobeli ea transformer (e bakang lipotoloho tse khutšoane).

Tlhophiso: Li-interlocks tse peli tsa HD Series (e le 'ngoe ho LBS e' ngoe le e 'ngoe) e hokahantsoeng ka senotlolo se arolelanoang.

Mokhoa oa ho sebetsa:

  • Ha LBS A e koetsoe, senotlolo se qabeletsoe ka har'a interlock ea eona{0}LBS B's interlock bolt ea atolosoa, e thibelang hore e se koale.
  • Ho kwala LBS B, opareitara e bula LBS A, e lata senotlolo, mme e se sebedise ho hula boutu ya LBS B-ho tshwasa senotlolo se hokelang LBS B (e thiba LBS A ho tswala-botjha).
kirk interlocks
Load Break Switches
Loop Feed

6.3 Kopo ea 3: Litsamaiso tsa Lijo tsa Loop (Utility Transformers)

Sepheo: Netefatsa hore ho na le phepelo e le 'ngoe feela (A kapa B) e sebetsang tsamaisong ea phepelo ea loop (e thibela ho tlala ha transformer).

Tlhophiso: A 3-cylinder HD Series interlocking controlling Feed A, Feed B, le khabinete ea transformer.

Mokhoa oa ho sebetsa:

  • Ho kenya Phepelo A, mokhanni o kenya linotlolo tsa Feed B (e tlameha ho buloa) 'me khabinete (e tlameha ho koaloa) ho interlock-e lokolla senotlolo sa Feed A.
  • Ho koala Feed A maraba senotlolo sa eona; ho fetohela ho Fepa B, opareitara e bula Feed A, e lata senotlolo sa eona, ebe e e kenya (hammoho le senotlolo sa khabinete) ho lokolla senotlolo sa Feed B.

 

 

 

 

 

7.Selection Guide: Ho Khetha Setho se nepahetseng sa Kirk Key Interlock bakeng sa Transformer ea Hao

 

 

Ho khetha interlock e nepahetseng ho hloka ho hokahanya lintlha le tikoloho ea transformer ea hau, boholo le litlhoko tsa ts'ebetso. Ka tlase ke mehato{1}ka{2}}mohato oa khetho:

7.1 Mohato oa 1: Fumana Letoto (SD vs. HD)

Sebelisa lethathamo lena ho etsa qeto:

Ntlha

Khetha SD Series

Khetha HD Series

Tikoloho

Ka ntle / ka ntle (ho se na pula e tobileng / letsoai)

Ka ntle / lebopong la leoatle / indasteri (pula, letsoai, mocheso o phahameng)

Mocheso o Feteletseng

<250°F (121°C)

>250℃F (121 degrees) ho fihla ho 700 degrees F (371 degrees)

Kotsi ea Corrosion

Tlase (moea o omileng, o hloekileng)

Phahameng (mongobo, letsoai, lik'hemik'hale)

 

7.2 Mohato oa 2: Kgetha Bolelele ba Bolt

Bolelele ba bolt bo itšetlehile ka sebaka se pakeng tsa interlock le lets'oao la switch / latch ea cabinet. Lekanya sekheo sena (e bitse "G") 'me u kenye 1/8" ho netefatsa hore ho kopana ho feletseng.

1" (25.4mm): Likhabinete tse tšesaane tsa li-transformer tsa ka tlung.

1.5" (38.1mm): Likhabinete tse tloaelehileng tsa transfoma ea padmount.

2".

 

7.3 Mohato oa 3: Khetha Bongata ba Cylinder

  • 1 Cylinder: Litlhophiso tse bonolo (1 switjha + 1 khabinete).
  • Li-cylinders tse 2–4: Li-transformer tsa indasteri tse nang le li-switches tse peli (mohlala, LBS ea mathomo le ea bobeli).
  • 5+ Li-cylinders: Litsamaiso tsa phepelo ea liluru kapa li-transformer tse nang le lintlha tse ngata tsa polokeho (sebelisa foromo ea bolelele: 9.5" + 1.5" ka silindara e 'ngoe) .

 

7.4 Mohato oa 4: Eketsa Li-swichi tsa Thuso (Haeba ho Hlokahala)

Bakeng sa li-transformer tse hlokang tlhokomelo e hole (mohlala, litsamaiso tsa taolo ea indasteri), eketsa li-switches tse thusang:

  • Letoto la SD: Likhetho li kenyelletsa 2 N/O 1 N/C (Karolo ea A) kapa 4 N/O 2 N/C (Karolo ea B).
  • Letoto la HD: Khetho e tloaelehileng ke 1 N / O (Karolo ea E tatellano); Litlhophiso tsa moetlo li hloka ho buisana le sehlopha sa barekisi sa Kirk.

 

7.5 Mohato oa 5: Netefatsa Tumellano le Lisetifikeiti

Netefatsa hore interlock e kopana le maemo a lehae:

  • UL e thathamisitsoe (bakeng sa Amerika Leboea) kapa CSA e netefalitsoeng (bakeng sa Canada).
  • NFPA 70E e lumellana (polokeho ea arc flash).
  • IEC 62271-205 e lumellana (bakeng sa ho tsamaisoa ha machaba).

 

 

 

 

 

8. Ke Hobane'ng ha Kirk Key Interlocks e le ea Bohlokoa Bakeng sa Tšireletso ea Transformer

 

Li-transformer li kotsi-lintho tse ngata tse kotsi-diketsahalo tsa arc flash li ka baka kotsi e mpe kapa lefu, 'me tšenyo ea lisebelisoa e ka fella ka ho tima ka litšenyehelo tse ngata. Li-interlock tsa Kirk Key li sebetsana le likotsi tsena ka litsela tseo ho seng sesebelisoa se seng sa polokeho se ka khonang:

8.1 E tiisa Tšireletseho ea "No Bypass".

Ho fapana le linotlolo tsa elektroniki (tse ka senyehang ha motlakase o khaoha) kapa lilotlolo (tse ka khaoloang kapa tsa hlokomolohuoa), li-interlock tsa Kirk Key li itšetlehile ka tšebetso ea 'mele{0}}ha ho mokhoa oa ho feta tatellano. Ka mohlala, senotlolo se ka har'a khabinete ea transformer se ka tlosoa ka li-bolt cutters, empa senotlolo sa Kirk Key se hloka hore switch ea holimo e tlosoe{2}}matla pele .

 

8.2 E Fokotsa Phoso ea Batho

NFPA 70E e tlaleha hore 70% ea liketsahalo tsa motlakase li bakoa ke liphoso tsa batho (mohlala, ho bula khabinete e phelang). Li-interlocks tsa Kirk Key li felisa sena ka ho etsa liketso tse sa sireletsehangho se kgonehe mmeleng-notlolo ha e khone ho fumanwa hape, le boutu e ka se hulwe morao, ho fihlela sisteme e bolokehile.

 

8.3 Litšenyehelo-Nako e Tlamahatsang-Nako

Le hoja litšenyehelo tsa pele li le holimo ho feta lilotlolo, li-interlock tsa Kirk Key li fokotsa{0}}litšenyehelo tsa nako e telele:

Litšenyehelo tse amanang le likotsi-tse fokolang (likoloto tsa bongaka, likotlo, liqoso).

Nako e fokolang ea ho fokotsa nako (ha ho na tšenyo e tsoang ho misoperation).

Tlhokomelo e fokolang (ho tlotsa ka graphite ho tlase-litjeho ha ho bapisoa le ho khutlisa liloko tsa elektroniki tse sa atlehang).

 