50 kVA Transformer Power Line-13.8/0.12 * 0.24 kV|Guyana 2024

50 kVA Transformer Power Line-13.8/0.12 * 0.24 kV|Guyana 2024

Naha ea Thomello: Guyana 2024
Matla: 50kVA
Matla: 13.8 / 0.12 * 0.24 kVA
Romela Inquiry

 

 

transformer power line

Li-transformer tsa SCOTECH tsa Mokhahlelo o le Mong oa Pole: Matla a Tšepahalang ho tloha ho 10kVA ho isa ho 500kVA bakeng sa Tlhokahalo e 'ngoe le e 'ngoe ea Grid

 

 

01 Kakaretso

1.1 Tlhaloso ea Morero

Odara e tsoang ho moreki oa rona oa Guyana 2024, e leng khamphani ea litšebeletso tsa boenjineri ba motlakase, e kenyelletsa li-transformer tse nang le matla a 25kVA, 50kVA, 75kVA, 100kVA, le 167kVA. 50kVA Ideal bakeng sa libaka tsa bolulo tse mahareng-kapa likhoebo tse nyane.

Transformer e lumellana ka botlalo le litekanyetso tsa IEEE & ANSI C57.12.00. E sebetsa ka matla a mantlha a 13,800V, e theohela ho 120/240V ka lehlakoreng la bobeli, ka maqhubu a 60Hz le mapheo a koporo. The impedance ke 2%, ho fokotsa ho theoha ha motlakase tlas'a mojaro.

E na le sistimi e futhumatsang ea ONAN le NLTC (No Load Tap Changer), e fana ka sebaka sa 10% sa ho theipi (± 2.5% ka pompo), e tsitsisa motlakase oa bobeli leha ho na le liphetoho tsa mantlha. Ha ho-tahlehelo ea mojaro ke 160W, 'me -tahlehelo ea mojaro ke 512W, e leng ho matlafatsang tšebeliso ea matla. Transformer e na le polarity e fokolang le sehlopha sa vector sa Ii0, se hlalosang kamano ea eona ea mohato.

E le moetsi ea ka sehloohong oa li-transformer, re fana ka se phethahetsenglitharollo tsa transformerbakeng sa litlhoko tsa hau tsa kabo ea motlakase.

1.2 Tlhaloso ea Setsebi

50kVA Single phase pole mounted transformer specifications and data sheet

E fetisetsoa ho
Guyana
Selemo
2024
Mofuta
Single phase pole mounted transformer
Standard
IEEE & ANSI C57.12.00
Rated Power
50 kVA
Khafetsa
60HZ
Polarity
Subtractive
Sehlopha sa Vector
Ii0
Voltage ea mantlha
13800 V
Motlakase oa bobeli
120/240 V
Lintho Tse Hlahang
KOPI
Tšitiso
2%
Mokhoa oa ho Pholisa
ONA
Tlanya Changer
NLTC
Tlanya Range
±2X2.5%(Kakaretso ea mefuta=10%)
Ha ho Tahlehelo ea Mojaro
160 W
Ho Lahleheloa ke Moroalo
512 W
Lisebelisoa
Tlhophiso e Tloaelehileng

 

 

1.3 Litšoantšo

50kVA Single phase pole mounted transformer litekanyo le lintlha tsa boima

image003 image005

 

 

02 Tlhahiso

2.1 Ntlha ea bohlokoa

Monyetla oa sebopeho sa mokokotlo oa leqeba ke hore o lumella thepa ea ferromagnetic ho sebelisa ka botlalo thepa ea eona e phahameng ea motlakase, ho fokotsa coefficient ea tahlehelo ea mantlha. Leoto le joko li tšela-karolo ea leqeba le le leng-ka bobeli li na le khutlonnetsepa hape li na le maqeba a sa khaotseng ka tšepe ea makenete, e fokotsang haholo{3}tahlehelo ea mojaro,{4}}ha ho{4}}moroalo oa hona joale, le lerata la transformer.

wound core

 

2.2 Ho tsubella

high-purity enameled round copper wire

Fensetere ea rona e sebelisa terata e pota-potileng ea enameled e phahameng{{0}e nang le enameled e pota-potileng, e nang le motlakase o motle haholo le mohatsela o kopaneng. Ho roala ha enamel ho fana ka ts'ebetso e ts'oanang le matla a ka tšeptjoang a dielectric. Etsa hore ho be le mokhoa o ntlafetseng oa li-coil tse matsoelintsoeke bakeng sa-likhoele tse fehlang motlakase o tlase 'me li fetisoha ka terata bakeng sa-likhoele tsa "voltage" tse phahameng, tse netefatsang ts'ebetso e tsitsitseng, ts'epahalo, le ts'ebetso ea mocheso.

 

2.3 Tanka

Tanka ea tšepe e bonolo e nang le mekotla ea ho phahamisa e cheselitsoeng le masakata a hanger bakeng sa ho toba{{0}ho{1}ho kenya lipalo. Tekanyo ea KVA leboteng la tanka. Liaparo tse sireletsang li sebelisoa litanka ho fokotsa ho bola. Ho netefatsa ts'ebetso e bolokehileng ea li-transformer tsena tsa motlakase ho sa tsotellehe ho pepesehela maemo a leholimo a thata le libaka tsa bona tse hōle, ho tšepahala ho hahiloe ka litlhaloso tsa bona.

transformer specifications

 

2.4 Kopano ea ho Qetela

core coil drying

1. Kopano e Phethahalang:Tsamaisa mapheo a HV/LV holim'a konokono ea laminated, ho etsa bonnete ba hore ho ba le tlhophiso e nepahetseng le bots'epehi.

2. Lihokelo tsa Motlakase:Ho hokela matsoelintsoeke ho lebisa ho chencheng ea pompo, lihlahla le likarolo tse ling, ebe o sireletsa le ho kenya manonyeletso.

3. Ho Omisa Likhoele:{1}}Beha karolo e sebetsang e kopaneng (konokono + windings) ka ontong e omisang bakeng sa ho futhumatsa vacuum ho tlosa mongobo.

4. Ho Kenya Tanka:Phahamisa karolo e omisitsoeng e sebetsang ka tankeng, e behe ka mokhoa o sireletsehileng, 'me u netefatse hore ho na le metsi a nepahetseng maboteng a tanka.

5. Ho hlomamisa lisebelisoa:Kenya lihlahla, valve e fokotsang khatello le lisebelisoa tse ling, ebe u hlahloba ho lutla.

6. Ho Tlatsa Oli le ho Lokisa:Vacuum-tlatsa oli e sireletsang, degas, 'me u lumelle ho tsitsa pele u hlahloba maemo a oli le matla a dielectric.

 

 

03 Ho etsa liteko

Teko e Tloaelehileng

1. Litekanyo tsa ho hanyetsa

2. Karo-karolelano Liteko

3. Polarity Test

4. Ha ho Tahlehelo ea Mojaro 'me Ha ho na Mojaro Hona Joale

5. Litahlehelo tsa Meroalo le Matla a Matla a Impedance

6. Teko ea Voltage e sebelisitsoeng

7. Induced Voltage E mamella Teko

8. Tekanyo ea ho hanyetsa Insulation

9. Teko ea Leak e nang le Khatello ea Li-transformers tse qoelitsoeng ka Metsi

10. Teko ea Dielectric ea Oli

transformer power line test

Liphetho tsa liteko

Che.

Ntho ea Teko

Yuniti

Melao ea ho Amohela

Litekanyetso Tse Lekanyelitsoeng

Qetello

1

Litekanyo tsa ho hanyetsa

/

/

/

Feta

2

Liteko tsa karo-karolelano

/

Phapang ea karo-karolelano ea motlakase ho theipi ea mantlha: Ka tlase ho kapa ho lekana le 0.5%

Letšoao la khokahano: Ii0

-0.04

Feta

3

Liteko tsa polarity

/

Subtractive

Subtractive

Feta

4

Ha ho{{0}tahlehelo ea thepa le thabo ea hona joale

%

kW

I0 :: fana ka boleng bo lekantsoeng

P0: fana ka boleng bo lekantsoeng

mamello ea ho se lahleheloe ke moroalo ke +10%

0.95

0.130

Feta

5

Litahlehelo tsa meroalo, motlakase oa impedance, tahlehelo e felletseng le bokhoni

/

kW

kW

T:85 likhato

Z%: boleng bo lekantsoeng

Pk: boleng bo lekantsoeng

Pt: boleng bo lekantsoeng

mamello ea impedance ke ± 10%

mamello ea tahlehelo ea boima kaofela ke +6%

2.08

0.518

0.648

99.02

Feta

6

Teko ea Voltage e sebelisitsoeng

/

HV: 34KV 60s

LV: 10kV 60s

Ha ho ho putlama ha motlakase oa liteko

Feta

7

Teko ea ho mamella Voltage e kentsoeng

/

Matla a sebelisoang (KV):

2 Ur

Nako: 48

Hangata (HZ): 150

Ha ho ho putlama ha motlakase oa liteko

Feta

8

Tekanyo ea ho hanyetsa Insulation

HV{{0}LV ho ea fatše

LV-HV ho ea fatše

HV&LV ho ea fatše

83.6

76.9

75.3

/

9

Leakage Test

/

Khatello e sebelisitsoeng: 20kPA

Nako: 12h

Ha ho na leakage le che

Tšenyo

Feta

10

Teko ea Dielectric ea Oli

kV

E kholo ho feta kapa e lekana le 45

51.41

Feta

 

04 Ho paka le ho Romela

transformer power line packing transformer power line shipping
 

05 Sebaka le Kakaretso

Ea rona50kVA e le 'ngoe-pase pole{2}} transformer e kentsoengbakeng sa Guyana e netefatsa kabo ea motlakase e sebetsang hantle, e tsitsitseng le e sireletsehileng.

E entsoe ka{{0}maphepelo a boleng bo phahameng ba koporo,{1}}moko oa maqeba a tahlehang, le tanka e tšoarellang ka ntle-e ts'epahalang{3}ha nako e telele le maemong a boima.

50 kVA transformer power line

 

 