500 KVA Distribution Transformer-11/0.415 KV|Australia 2025
Matla: 500 kVA
Matla: 11/0.415 kV
Tšobotsi: Lebokose la theminale le nang le{0}}sesebediswa sa anticondensation
Jiangshan Scotech Electrical Co., Ltd ke e mong oa baetsi le barekisi ba ka tšeptjoang ka ho fetisisa ba 500 kva distribution transformer-11/0.415 kv|Australia 2025 Chaena. Ka kopo, ikutloe u lokolohile ho reka lihlahisoa tse baballang litšenyehelo tse rekisoang mona le ho fumana litšoantšo ho tsoa femeng ea rona. Ikopanye le rona bakeng sa lintlha tse ling.

Motlakase o tsitsitseng, pholiso e phahameng - oli{0}}e qoelisoang ke motlakase oa phepelo, pelo e tšepahalang ea kabo ea matla.
01 Kakaretso
1.1 Tlhaloso ea Morero
500 kVA oli-transformer e qoelisoang ea ho tsamaisa oli e ile ea isoa Australia ka 2025. Matla a lekantsoeng a transformer ke 500 kVA e nang le pholile ea KNAN. Motlakase o phahameng ke 11 kV le ± 2 * 2.5% tapping range (NLTC), motlakase o tlaase ke 0.415 kV, ba thehile sehlopha sa vector sa YNd11.
E etselitsoe libaka tse kantle le tse pepenene joalo ka Sehlekehleke sa Barrow, Australia Bophirima, yuniti ena e lumellana le maemo a IEC 60076 le AS/NZS 60076. E etselitsoe mocheso o phahameng oa tikoloho (ho fihla ho likhato tse 50) le maemo a matla a tikoloho, ho kenyeletsoa moea oa cyclonic (260 km/h) le ts'ebetso ea tšisinyeho ea lefatše (0.11G).
Lintlha-khōlō Tsa Botekgeniki
1. Oli ea FR3 (Natural Ester Fluid)
- Mofuta: FR3 ester ea tlhaho(ho e-na le MIDEL 7131, joalokaha e fanoe ke moetsi)
- Melemo:K{{0}sehlopha, sebaka se phahameng sa mollo (E kholo ho feta kapa e lekana le 300 degrees ), e ka senyeha, 'me e baballa tikoloho. E ts'ehetsa moralo oa tanka o koetsoeng ka botlalo,{3}o se nang khase{3}o se nang seboloki kapa mosamo oa nitrogen.
2. HV Cable Box
- Mofuta:Lebokose la cable le kentsoeng, le ka hatelloang le likhokahano tse ntšoang
- Boemo ba IP:IP56 (lerole-e tiileng ebile e sirelelitsoe khahlanong le lifofane tse matla tsa metsi)
- Likaroloana:E amohela lithapo tsa 11 kV, tse kenyeletsang lithapo tsa HV neutral termination, hape e ts'ehetsa ho kena ka tlase ka -ho emisa setsoe (ho ikhethela).
3. Lebokose la Cable la LV + Li-Busbars tsa Koporo tse Atolositsoeng le Litšehetso
- Pheliso ea LV:Lebokose la thapo le nang le libese tsa koporo tse atolositsoeng le litšehetso tse inehetseng tsa libese
- Bokhoni:E etselitsoe lithapo tsa koporo tsa 4 × 240 mm² XLPE/PVC ka mohato
- Keno:Keno e ka tlase kapa e ka lehlakoreng, e nang le li-terminal block (eseng -ho robeha litsoe)
4. Terminal Box e nang le Anti{1}}Sefuthumatsi sa Condensation
- Mofuta:IP56 theminal box e nang le-se futhumatsang sebaka
- Tlhaloso ea Heatere:230 VAC, 50 W (koporo)
- Mosebetsi:E thibela condensation ka hare, ho netefatsa ts'ebetso e ka tšeptjoang maemong a mongobo kapa a feto-fetohang a leholimo.
5. Mabitso a Bobeli a Mabitso (A Thuso / Alamo / Mabitso a Leeto)
- Letšoao la Mocheso oa Mocheso (WTI):Alamo ka likhato tse 110, Leeto ka likhato tse 130
- Lesupa la Mocheso oa Oli:Mabitso a alamo le leeto
- Sesebelisoa sa ho Imolla Khatello:Mabitso a alamo le leeto
- Tekanyo ea boemo ba oli:Alamo ea boemo bo tlase ba oli
- Laola Voltage:Mabitso ohle a thusang a fuoe lintlha tse 230 VAC
1.2 Tlhaloso ea Setsebi
500 kVA oli-mofuta oa litlhophiso tsa phepelo e qoelitsoeng le leqephe la lintlha
|
E fetisetsoa ho
usa
|
|
Selemo
2025
|
|
Mofuta
Transformer e kentsoeng ka pampiri
|
|
Standard
IEC60076
|
|
Rated Power
500 kVA
|
|
Khafetsa
50HZ
|
|
Mokhahlelo
3
|
|
Mofuta oa ho Pholisa
KNAN
|
|
Voltage ea mantlha
11 kV
|
|
Motlakase oa bobeli
0.415 kV
|
|
Lintho Tse Hlahang
Koporo
|
|
Sehlopha sa Vector
YNd11
|
|
Tšitiso
5.75%±7.5%
|
|
Katleho
E kholo ho feta kapa e lekana le 99.16%
|
|
Tlanya Changer
NLTC
|
|
Tlanya Range
±2*2.5%
|
|
Ha ho Tahlehelo ea Mojaro
Ka tlase ho kapa ho lekana le 0.95 kW
|
|
Ho Lahleheloa ke Moroalo
Ka tlase ho kapa ho lekana le 5.8 kW
|
1.3 Litšoantšo
500 kVA oli-setakanyo le boholo ba sefetoleli sa phepelo e qoelisang.
![]() |
![]() |
02 Tlhahiso
2.1 Ntlha ea bohlokoa

Moko oa mantlha o sebelisa tšepe ea silicon ea CRGO e nang le moaho oa li-step-lap ho fokotsa tahlehelo ea hona joale ea hysteresis le eddy. Tahlehelo e lekantsoeng ea ho se be le moroalo (0.728 kW) le ha ho na moroalo hona joale (0.60%) li ka tlase ho 0.95 kW le 1.2%, li tsamaellana ka botlalo le ho lumellana le IEC 60076. Liteko tsa kamehla li netefalitse ts'ebetso e tsitsitseng ea mocheso (HV winding e lekana le 59.25 K le Les60 K) haholo le Les60.25 K (46.9 dB(A) khahlano le. 75 dB(A) moeli). Boleng bo netefatsoa ke tlhahlobo ea 100% ea thepa e kenang le taolo ea marang-rang. Ntlha ea bohlokoa ea tlhahiso ke tahlehelo e tlase, ea mantlha e khutsitseng e fetang litlhoko tse sebetsang hantle.
2.2 Ho tsubella
Li-windings li tsoa ho 99.9% ea koporo ea electrolytic bakeng sa conductivity e phahameng le matla a mochine. Tahlehelo ea meroalo (5.657 kW) le ho sitisa potoloho e khuts'oane (5.91%) li ts'oana le tse hlokahalang Ka tlase kapa ho lekana le 5.8 kW le 5.75% ±7.5%, tlasa IEC 60076. Liteko tsa dielectric tse fetisitsoeng ho kenyeletsoa matla a lehalima (75 kV), voltage e sebelisitsoeng (28 kV HV / LV) ho phahama ha mocheso e ne e le 59.25 K bakeng sa HV le 58.23 K bakeng sa LV (ka bobeli e le Ka tlase ho kapa e lekana le 60 K). Boleng ba moea bo laoloa ke ho lekola tsitsipano, tlhahlobo ea 100% ea ho kenya letsoho, le ho omisa vacuum pele ho tlatsoa oli. Ntlha ea bohlokoa ke bokhoni bo phahameng ba ho mamella potoloho e khuts'oane bakeng sa ts'ebeletso e thata ea kantle.

2.3 Tanka

Tanka ea tšepe e tiisitsoeng ka botlalo ha e na sebolokelo kapa mosamo oa naetrojene mme e fana ka tšireletso ea IP56. Ho phahama ha mocheso oa oli (48.89 K) ho ka har'a moeli oa 55 K, 'me tanka e fetisitse teko ea ho lutla ha lihora tse 15 kPa / 24 ntle le ho lutla, ho kopana le IEC 60076. Boleng bo tiisetsoa ka ho tjheseletsa ho laoloang, ho lemoha ho lutla ha parafine ea 100%, le sandblasting pele ho penta. Tanka e koahetsoe ka RAL 7035 polyurethane (bonyane 100 μm DFT) bakeng sa kutu le ho hanyetsa UV, e etsa hore e tšoanele libaka tse nang le letsoai le phahameng joalo ka Barrow Island.
2.4 Kopano ea ho Qetela
Setsi se kopantseng se kopanya likarolo tsohle tse boletsoeng ke morero: FR3 tikoloho ea tlhaho ester fluid (mollo o phahameng o moholo ho feta kapa o lekana le 300 degree, biodegradable, K-class), lebokose la cable le tlatsitsoeng ka khase la HV le likhokahano tse ka senyehang, lebokose la cable la LV le nang le mekoallo ea koporo e atolositsoeng le litšehetso, lebokose le nang le mochini o thibelang ho hema (lebokose la mohala) ho shebella mocheso oa oli, mocheso o tsoelipanang le khatello. Lisebelisoa tsohle li lumellana le litekanyetso tsa transformer 'me li lumellana le IEC 60076 le AS/NZS 60076. Liteko li netefalitse ts'ebetso e nepahetseng ea mocheso oa mocheso (WTI), khanyetso e tsitsitseng ea "no-load tap changer" (NLTC), 'me e fetisitse ho mamella mocheso oa potoloho ea bobeli. Boleng bo netefatsoa ka ts'ebetso ea FAT le tlhahlobo ea ho hula mabitso a bobeli. Ntlha ea bohlokoa ea tlhahiso ke mabokose a modular cable le lebokose la anti-condensation, le loketseng tikoloho ea lihlekehleke tse mongobo, tse phahameng tsa mocheso.

03 Teko
Liteko tsohle tsa tloaelo li entsoe ho latela IEC 60076 mme li pakiloe. Liphetho tsa bohlokoa: ha ho tahlehelo ea moroalo 0.728 kW (Ka tlase kapa e lekanang le 0.95), tahlehelo ea mojaro 5.657 kW (Ka tlase kapa e lekanang le 5.8), impedance 5.91% (5.75% ± 7.5%), ho phahama ha oli e kaholimo ho 48.89 K (Ka tlase ho kapa ho lekana le 55 K / 5), moea o nyolohang 52 K / 5. (Ka tlase kapa ho lekana le 60 K), matla a lehalima (75 kV) a fetisitsoe, matla a sebelisitsoeng (28/3 kV) a fetile, boemo ba molumo bo Tlase kapa bo lekana le 46.9 dB (A) ( Ka tlase kapa ho lekana le 75), le 15 kPa / 24h leak teko e fetisitsoeng ntle le ho lutla.


04 Ho paka le ho Romela
4.1 Ho paka

Transformer e pakiloe holim'a skid ea lepolanka kapa setsi sa tšepe se nang le sekoaelo se sa keneleng metsi le likhoele tsa tšepe tsa maemo a kantle ho naha. Li-bushings tsohle, li-cable box le lebokose la li-terminal li kenngoa ka li-caps tse sireletsang, 'me desiccant e kenngoa ka har'a mokotla o tiisitsoeng ho thibela mongobo o kenang. Ho paka ho ikamahanya le ditlhoko tsa ho romelwa ka ntle ho lewatle (AS/NZS) mme ho kenyeletsa tshireletso ya tshoso le mafome. Boleng bo tiisetsoa ke cheke ea ho qetela ea motlakase pele e paka, litokomane tsa lifoto, le sehokelo sa tlaleho e felletseng ea tlhahlobo le setšoantšo sa lebitso.
4.2 Ho tsamaisa thepa
Ho romelloa ho etsoa ka har'a sets'oants'o se bulehileng sa 40-ft kapa rack e sephara e nang le transformer e kopaneng ka botlalo. E sirelelitsoe ka liboutu tse tlase, litšepe tsa lehong, likhoele tsa tšepe le meseme e thibelang ho skipa. Khatello e ntle (moea o omileng kapa naetrojene) e bolokiloe nakong ea lipalangoang ho qoba ho kenella ha mongobo. Thepa e latela melao ea machaba e seng kotsi (FR3 ke mokelikeli oa tikoloho oa K-class). Letšoao la ho ts'oha le tlameletsoe pele le tloha 'me le hlahlojoe ha le fihla ho netefatsa hore ha le tšoaroe hampe.

05 Kakaretso
500kVA 11/0.415kV enatransformer e qoelisoang ka olie lumellana ka botlalo le litlhaloso tsa projeke ea tekheniki. E kenyelletsa FR3tikolohoOli, HV le mabokose a cable a LV (a morao-rao a na le mekoallo e atolositsoeng ea koporo le litšehetso), lebokose la li-anti-condensation, le likhokahano tsa bobeli tsa likhoele. Litekanyetso tsohle li lumellana le IEC 60076 le AS/NZS 60076. Ho tšepahala ho pakoa ke tlaleho ea tlhahlobo e tloaelehileng: tahlehelo e tlase ho feta e tiisitsoeng, likhahla tse lekaneng tsa ho phahama ha mocheso, liteko tsohle tsa dielectric le impulse li fetile, leak-tight, le lerata le tlaase haholo. Boleng bo netefatsoa ke ts'ebetso ea tlhahiso e ka latelloang ea ISO 9001. Ka tanka ea eona ea masenke e tiisitsoeng ka hermetically, ts'ireletso ea IP56 le likarolo tsa tikoloho e mongobo / letsoai, transformer ena e loketse hantle libaka tse pepeneneng tse kang Barrow Island, WA.

Hot Tags: 500 kVA kabo ea transformer, moetsi, mofani oa thepa, theko, litšenyehelo
You Might Also Like
2000 kVA Power Distribution Transformer-20/0.4 kV|Al...
400 kVA Mofuta o omileng oa Motlakase Transformers-0...
75 kVA 3 Phase Distribution Transformer-0.22/0.415 k...
2000 KVA Distribution Transformer-11/0.433 KV|Malays...
2000 KVA Cooper Power Systems Pad Mounted Transforme...
750 KVA Phatlalatso ea Motlakase Transformer-11 / 0....
Romela Inquiry